SENECA T201DC100 Installation Manual

Preliminary Warnings

The word WARNING preceded by the symbol [warning] indicates conditions or actions that put the user's safety at risk.

The word ATTENTION preceded by the symbol [attention] indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.

WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.

The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.

Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.

Documentation

SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287

Contact Information

Technical support: support@seneca.it

Product information: sales@seneca.it

This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.

Document ID: MI00353-4-EN

Module Layout

The module has the following dimensions:

Container Material: PA6 black colour.

Preliminary Instructions for Use

The T201DC100 can be mounted in any position and place, in compliance with the expected environmental conditions. Use the supplied accessory in the case of DIN rail mounting.

Note: Magnetostatic fields of considerable magnitude can alter the measurement. Please avoid installing the module near permanent magnets, electromagnets, or ferrous masses that induce strong alterations in the magnetic field. If the zero error is greater than the declared one, try a different arrangement or orientation.

Technical Specifications

Category Specification
NORMS EN61000-6-4 Electromagnetic emission, in industrial environment.
EN61000-6-2 Electromagnetic immunity, in industrial environment.
EN60950 Safety.
Note: Use with copper conductor, in environments with pollution degree 2 and with class 2 power supply unit.
CONNECTIONS Removable 4-way screw terminals, 5 mm pitch, for loops: 4 to 20 mA
OVERVOLTAGE CATEGORY Bare conductor Category III (up to 300 V)
Insulated conductor Category III (up to 600 V)
INPUT SCARES Monopolar 0 - 10 A, Bipolar -10 - 0 - +10 A
Monopolar 0 - 25 A, Bipolar -25 - 0 - +25 A
Monopolar 0 - 50 A, Bipolar -10 - 0 - +50 A
Monopolar 0 - 100 A, Bipolar -25 - 0 - +100 A
AC OVERRIDE F (35 Hz) Measurable peak value: -30 - +120 A
Double half-wave rectified: -20 - 80 A
Single half-wave rectified: -10 - 40 A
ENVIRONMENTAL CONDITIONS Temperature: -20°C to +70°C
Humidity: 10% to 90% non-condensing.
Storage temperature: -40°C to +85°C
Protection degree: IP20
CONNECTIONS Extractable terminal pitch 5 mm, cables less than or equal to 2.5 mm², for loops 4 to 20 mA.
Tightening torque 7.0 Lb•inch = 0.8 N•m.
21 mm through-hole for power cable.
POWER SUPPLY OUTPUT TYPE: Passive current loop 4 to 20 mA
LIMITS: Internal over-temperature fault: 3.5 mA; Under-range / Over-range: 3.6 / 21.0 mA; Valid measurement: 3.8 / 20.5 mA.
LOOP VOLTAGE MIN. - MAX.: 6 V – 28 V.
OTHER PROTECTIONS: Reverse polarity, Loop current limitation in case of failure, Over-temperature protection.
PRECISION MAXIMUM ERRORS: Measuring section: 0.1 % + 14 mA; Output section: 0.05 % + 4 μA.
TEMPERATURE COEFFICIENT: less than 150 ppm/K.
ERROR FOR EMI: less than 50 μA, test on bare bar diameter 10 mm.
SPEED RESPONSE: Without filter: 100 ms; With filter: 600 ms.

Electrical Connections

[attention] Please, turn off the power supply before wiring.

Current Output for Loop 4 ÷ 20 mA

A diagram illustrates the current output connection for a 4-20 mA loop. It shows a power source (U) and a current meter (mA) connected in series with the device. The text states: "It is possible to connect directly on the 4 ÷ 20 mA loop in T201DC100 output a maximum voltage of 28 V."

Current Input

[attention] Please, install the module as shown in the figure. Pay attention to the direction of the current flow.

To measure the current passing through a cable, insert the cable into the central hole of the T201DC100. The maximum current that can be measured by T201DC100 is 100A.

To increase the current measurement sensitivity, insert the cable several times into the central hole of the T201DC100, creating a series of coils. The current measurement sensitivity is proportional to the number of turns. For example, if the full scale is set and the wire is wrapped around the hole 5 times, this creates 4 coils. The full scale will be 5 times lower, and the measurement will be more sensitive.

Arrange the coils symmetrically to preserve the precision of the instrument.

DIP-SWITCH SETTINGS

Use the dip-switches to choose the monopolar or bipolar scale and whether or not to activate the filter.

Monopolar Scale Bipolar Scale Filter
1234 1234 1234
0–10 A -10–10 A Disable
0–25 A -25–25 A Enable
0–50 A -10–50 A
0–100 A -25–100 A

A diagram shows the DIP switch configuration with a key indicating 'ON' position.

Models: T201DC100 AC DC Stromwandler, T201DC100, AC DC Stromwandler, DC Stromwandler, Stromwandler

PDF preview unavailable. Download the PDF instead.

mi00353-4-en Adobe PDF Library 17.0 Adobe InDesign 18.5 (Windows)

Related Documents

Preview SENECA T201DC100 Installation Manual and Technical Specifications
This document provides comprehensive installation instructions, technical specifications, and usage guidelines for the SENECA T201DC100 DC current transducer. It covers electrical connections, module layout, safety precautions, and performance data for industrial applications.
Preview T201DC100 DC Current Transducer Installation Manual
Installation manual for the SENECA T201DC100 DC current transducer, covering preliminary warnings, module schematics, technical specifications, electrical connections, and DIP switch configurations.
Preview T201DC100 Current Transducer Installation Manual
Installation manual for the SENECA T201DC100 current transducer, covering preliminary warnings, module layout, technical specifications, electrical connections, and dip-switch settings.
Preview SENECA R203 Installation Manual: Comprehensive Guide
This comprehensive installation manual provides detailed instructions for the SENECA R203 industrial measurement and control device. It covers module layout, technical specifications, electrical connections for various inputs and outputs including Rogowski sensors, Ethernet configuration, and safety warnings. Essential for qualified electricians performing installation and setup.
Preview T201DC100 Current Transducer Installation Manual
Installation manual for the SENECA T201DC100 current transducer, detailing technical specifications, connections, and usage instructions.
Preview SENECA T201DCH-MU Series User Manual: AC/DC Current Transducers
Comprehensive user manual for SENECA T201DCH-MU series AC/DC True RMS and DC Bipolar Current Transducers. Details device features, configuration via dip switches or Easy Setup software, Modbus RTU protocol, register tables, and testing procedures for industrial automation.
Preview SENECA R-KEY-LT / R-KEY-LT-P Installation Manual - Industrial Gateway
Comprehensive installation manual for SENECA R-KEY-LT and R-KEY-LT-P industrial gateways. Covers setup, configuration, technical specifications, and electrical connections.
Preview SENECA R203 Installation Manual
This installation manual provides detailed instructions, technical specifications, electrical connections, and configuration guidelines for the SENECA R203 series of measurement and monitoring devices.