INSTALLATION MANUAL
R-32DIDO / R-32DIDO-P
PRELIMINARY WARNINGS
The word WARNING preceded by the symbol [Warning Symbol] indicates conditions or actions that put the user's safety at risk. The word ATTENTION preceded by the symbol [Attention Symbol] indicates conditions or actions that might damage the instrument or the connected equipment. The warranty shall become null and void in the event of improper use or tampering with the module or devices supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manual are not followed.
[Warning Symbol] WARNING: The full content of this manual must be read before any operation. The module must only be used by qualified electricians. Specific documentation is available via QR-CODE shown on page 1.
The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electrostatic discharges. Take appropriate measures during any operation.
Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to recycle electrical and electronic waste.
Documentation for R-32DIDO and R-32DIDO-P is available.
CONTACT INFORMATION
SENECA s.r.l.; Via Austria, 26 – 35127 – PADOVA – ITALY; Tel. +39.049.8705359 - Fax +39.049.8706287
Technical support: support@seneca.it
Product information: sales@seneca.it
This document is the property of SENECA srl. Copies and reproduction are prohibited unless authorised. The content of this document corresponds to the described products and technologies. Stated data may be modified or supplemented for technical and/or sales purposes.
Document code: M100596-0-EN
MODULE LAYOUT
Dimensions: 106.6 mm width, 90.0 mm height, 32.2 mm depth.
Weight: 170 g; Enclosure: UL94-V0 self-extinguishing PC/ABS material, black.
The module features various ports: Digital Inputs/Outputs (terminals 10-22, 40-52, 53-65), External Power Supply (terminals 10, 50, 51, 52), Ethernet Switch (ports PORT1, PORT2), RS485 (terminals 23, 24, 25).
SIGNALS VIA LED ON FRONT PANEL
LED | STATUS | LED meaning |
---|---|---|
PWR | On | Device powered |
Off | Device not powered | |
IO1/IO32 | On | Digital input/output active |
Off | Digital input/output not active | |
OUT | On | Digital inputs/outputs powered |
SUP | Off | Digital inputs/outputs not powered |
STS (Status) | On | IP address set |
Flashing | Waiting for the IP address from the DHCP | |
COM (R-32DIDO-P version only) | Off | No Profinet communication |
Flashing | Profinet communication present | |
FAIL | On | Digital output in FAIL |
Off | Digital output OK | |
RX (R-32DIDO version only) | On | RS485 port wiring error |
Flashing | Reception of data packet completed on RS485 | |
TX (R-32DIDO version only) | Flashing | Transmission of data packet completed on RS485 |
ETH TRF (Yellow) | Flashing | Packet transit on Ethernet port |
ETH LNK (Green) | Flashing | The Ethernet port is connected (LINK) |
TECHNICAL SPECIFICATIONS
Certifications: CE, UKCA. Further details available at: https://www.seneca.it/products/r-32dido/doc/CE_declaration
INSULATION
1500 Vac
POWER SUPPLY
Voltage: 10÷40Vdc; 19÷28Vac; 50÷65Hz; Absorption: 3W max; Dissipation: 6.5W max.
ENVIRONMENTAL CONDITIONS
Operating temperature: from -25°C to +65°C. Humidity: 10% ÷ 90% non condensing. Storage temperature: from -30°C to +85°C. Protection rating: IP20.
CONFIGURATION
With integrated WEB Server.
CONNECTIONS/COMMUNICATION PORTS
3.5 mm pitch terminal block, 1.5 mm² max cable section.
- 1 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 (R-32DIDO-1 model)
- 2 Ethernet (with LAN fault-bypass function) 100 base T on RJ45 (R-32DIDO-2 model)
- 1 RS485 port on terminals 23-24-25 (only R-32DIDO-1/ R-32DIDO-2 versions)
DIGITAL INPUTS
Number of channels: 32; Voltage: Threshold ON: >9V; Threshold OFF: < 4 V; Vmax: 24 V; Impedance 9kΩ. Individually configurable.
DIGITAL OUTPUTS
Number of channels: 32, MOSFET, PNP; Max voltage/current: 0.2 A / 24 V. Individually configurable.
COUNTERS
Number of counters: 32 at 32 bit, maximum speed: 50 Hz.
ELECTRICAL CONNECTIONS
[Warning Symbol] CAUTION: The upper power supply limits must not be exceeded, as this could cause serious damage to the module. Switch the module off before connecting inputs and outputs.
To meet the electromagnetic immunity requirements:
- Use shielded signal cables;
- Connect the shield to a preferential instrumentation earth system;
- Separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).
Power Supply Connections
Terminal 20: + / ~
Terminal 21: ~ | -
Terminal 22: +
RS485 SERIAL PORT
Terminal 23: B(-)
Terminal 24: A(+)
Terminal 25: GND
Connection to the RS485 port. Polarity is not standardised; in some devices of other brands it may be inverted.
Digital Inputs (PNP)
Inputs from 1 to 8 (Terminals 10, 11, 12, ...)
Inputs from 9 to 32 (Terminals 40, 41, 42, ...)
For correct instrument operation, power the I/Os via the I/O Ext Supply 1 and 2 terminals (e.g., 17, 18+, 19-) at the same time.
Digital Outputs (PNP)
Outputs from 1 to 8 (Terminals 40, 41, 42, ...)
Outputs from 9 to 32 (Terminals 63, 64+, 65-, ...)
[Warning Symbol] CAUTION: The power supply must be sized according to the expected load at the outputs. Terminals 18-64 and 19-65 can be connected together on the same power supply.
DAISY-CHAIN (R-32DIDO-2 / R-32DIDO-2-P ONLY)
[Warning Symbol] CAUTION: IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES.
Using the daisy-chain connection it is not necessary to use switches to connect the devices. Diagrams illustrate correct daisy-chain connections without loops.
There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches must be connected eliminating any loops. Diagrams illustrate incorrect connections with loops.
The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less than 100m.
ETHERNET CONNECTION RULES
For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required. CAT6 for industrial environments.
FACTORY IP ADDRESS
The default module IP address is static: 192.168.90.101.
WEB SERVER
To access the maintenance Web Server with the 192.168.90.101 factory IP address:
Default user: admin; Default password: admin. Access via: http://192.168.90.101
[Warning Symbol] CAUTION: DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.
DIP - SWITCH SETTINGS
[Warning Symbol] WARNING: The DIP-switch settings are read only at boot time. At each change, perform a restart.
DIP-SWITCH SW1: through DIP-SWITCH-SW1 it is possible to set the IP configuration of the device:
DESCRIPTION | DIP 1 | DIP 2 |
---|---|---|
To obtain the configuration from the Flash memory, both SW1 DIP switch selectors must be set to OFF | OFF | OFF |
To reset the device to factory settings both SW1 DIP switches must be set to ON | ON | ON |
To force the device's IP address to the standard value of SENECA Ethernet products: 192.168.90.101 | ON | OFF |
Reserved | OFF | ON |
[Warning Symbol] WARNING: DIP-SWITCHES are located on the back of the device. To access the DIP-SWITCH it is necessary to remove the bottom of the instrument.