Samsung Service Guide: E913 Error Code
Subject: E913 Error Code
Models: CHILLER
Title: Water Flow Switch Error
Revision Date: 12/16/2024
Tech Support: (888)-699-6067 (7am to 6pm CST, M-F)
Issue
System will not restart because "Water flow switch error" has been detected 6 times.
Troubleshooting Steps
- Make sure the water circulating pump is running.
- Check pressure drop across heat exchanger and verify proper gallons per minute (GPM) are flowing through the heat exchanger. Refer to Technical Data Book (TDB) for pressure drop charts. Hyperlink to Chiller TDB
- Verify there are no flow control valves, isolation valves or bypass valves closed.
- Verify the strainer is clear.
- After verifying proper water flow, locate and test pressure transducers for inlet and outlet of heat exchanger located on the hydro board utilizing transducer charts below.
Pressure Charts
High Pressure Chart
High Pressure | High Pressure | High Pressure | High Pressure | Low Pressure | Low Pressure | Low Pressure | Low Pressure | ||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Vout | PSIG | Vout | PSIG | Vout | PSIG | Vout | PSIG | Vout | PSIG | Vout | PSIG | Vout | PSIG | Vout | PSIG |
0.5 | 0 | 1.5 | 181 | 2.5 | 363 | 3.5 | 544 | 0.5 | 0 | 1.5 | 73 | 2.5 | 145 | 3.5 | 218 |
0.6 | 18 | 1.6 | 199 | 2.6 | 381 | 3.6 | 562 | 0.6 | 7 | 1.6 | 80 | 2.6 | 152 | 3.6 | 225 |
0.7 | 36 | 1.7 | 218 | 2.7 | 399 | 3.7 | 580 | 0.7 | 15 | 1.7 | 87 | 2.7 | 160 | 3.7 | 232 |
0.8 | 54 | 1.8 | 236 | 2.8 | 417 | 3.8 | 598 | 0.8 | 22 | 1.8 | 94 | 2.8 | 167 | 3.8 | 239 |
0.9 | 73 | 1.9 | 254 | 2.9 | 435 | 3.9 | 616 | 0.9 | 29 | 1.9 | 102 | 2.9 | 174 | 3.9 | 247 |
1.0 | 91 | 2.0 | 272 | 3.0 | 453 | 4.0 | 635 | 1.0 | 36 | 2.0 | 109 | 3.0 | 181 | 4.0 | 254 |
1.1 | 109 | 2.1 | 290 | 3.1 | 471 | 4.1 | 653 | 1.1 | 44 | 2.1 | 116 | 3.1 | 189 | 4.1 | 261 |
1.2 | 127 | 2.2 | 308 | 3.2 | 490 | 4.2 | 671 | 1.2 | 51 | 2.2 | 123 | 3.2 | 196 | 4.2 | 268 |
1.3 | 145 | 2.3 | 326 | 3.3 | 508 | 4.3 | 689 | 1.3 | 58 | 2.3 | 131 | 3.3 | 203 | 4.3 | 276 |
1.4 | 163 | 2.4 | 344 | 3.4 | 526 | 4.4 | 707 | 1.4 | 65 | 2.4 | 138 | 3.4 | 210 | 4.4 | 283 |
4.5 | 725 | 4.5 | 290 |
Diagrams and Components
The document includes a visual of a circuit board with specific areas highlighted. Red boxes indicate connections related to pressure transducers. Arrows point to two connectors on the board.
Additionally, a diagram labeled "CN402-PRESSURE SENSOR" details the pin connections:
- #: 1
- #2: PHE_IN SIGNAL
- #3: GND
- #4: 5V
The text "Molex pin connections" is also present.
Proper Personal Protective Equipment (PPE) Required. These photos may not represent your exact system.
For use by Samsung HVAC Trained & Licensed Service Providers Only. www.SamsungHVAC.com