Product Overview
The Danfoss Hansen UQD is engineered for thermal management applications, available in 4 sizes and 2 color options. It complies with OCP (Open Compute Project) specifications and surpasses required performance characteristics. Danfoss UQD couplings offer color identification (red and blue) and are guaranteed 100% helium-leak tested.
Product Features
- Designed per OCP (Open Compute Project) UQD specification
- Push-to-connect design
- High flow and no spillage
- Double shut off - flat face valves
- Exceeds OCP flow ratings by at least 25%, resulting in reduced overall energy consumption
- Best in class force to connect
- Standard seal material: EPDM-P (Peroxide cured)
- Standard material: 303 stainless steel provides broad fluid compatibility
- Color anodized aluminum sleeves
- Color coded (red/blue) sleeves on socket and O-rings on plug
- Compact socket versions for sizes -02, -04, -06 to better fit in data center applications
- QR code identification to help track parts
- Wide range of terminal end options: ORB, BSPP on plug and push on hose on socket. Additional configurations available upon request
- Operating temperature: 10°C - 65°C (50°F - 149°F)
- Typical working pressure: 6.9 bar, up to 20 bar for smaller sizes
- All wetted o-rings/seals are qualified/certified as per IEC/UL 6268-1 G.15.2.3
Solutions to your liquid cooling challenges
Inner Rack Solutions
Danfoss' direct-to-chip cooling solutions extend into racks through efficient routing of flexible, kink-free hoses, and leak-free, helium-tested couplings. Danfoss has a comprehensive portfolio of premium fluid conveyance products to meet your thermal management system needs.
The UQD Universal Quick Disconnect Coupling is designed for high flow rate and no spillage, making it perfect for in-rack applications with smaller hose lines.
Technical Specifications
Physical Characteristics
Size | Body Dia. (in) | Nominal Flow (mm) | Max operating pressure (bar) (psi) | Min burst pressure (bar) (psi) | Rated Flow (lpm) (gpm) | Cv Value | Air Fluid Loss (cc. max.) | ||||
Socket / Female Half | Plug / Male Half | Socket / Female Half | Plug / Male Half | Connected | |||||||
UQD02 | 1/8 | 3.16 | 20 / 290 | 20 / 290 | 20 / 290 | 60 / 870 | 60 / 870 | 60 / 870 | 2.1 / 0.6 | 0.33 | 0.004 / 0.007 |
UQD04 | 1/4 | 6.3 | 16 / 232 | 16 / 232 | 16 / 232 | 48 / 696 | 48 / 696 | 48 / 696 | 6.4 / 1.7 | 1.37 | 0.024 / 0.01 |
UQD06 | 3/8 | 7.9 | 6.9 / 100 | 6.9 / 100 | 6.9 / 100 | 20.7 / 300 | 20.7 / 300 | 20.7 / 300 | 11.4 / 3.0 | 2.37 | 0.027 / 0.022 |
UQD08 | 1/2 | 10 | 6.9 / 100 | 6.9 / 100 | 6.9 / 100 | 20.7 / 300 | 20.7 / 300 | 20.7 / 300 | 17.8 / 4.7 | 5.32 | 0.029 / 0.03 |
Applications & Markets
- Liquid cooling application
- Data center application
Seal Elastomer Data
Seal Elastomer | Operation Temperature Range | |
C° | F° | |
EPDM-P | -40°C +150°C | -40°F +302°F |
Performance Parameters
Size | Force to Connect | Recommended Torque | ||||
N | lb | ORB size | BSP Size | |||
N-m | N-m | |||||
UQD02 | 48 | 10.79 | 7/16-20 | 11-12 | 1/8" | 8-9 |
UQD04 | 50 | 11.24 | 9/16-18 | 18-20 | 3/8" | 18-20 |
UQD06 | 73 | 16.41 | 3/4-16 | 52-57 | 3/8" | 18-20 |
UQD08 | 87 | 19.56 | 7/8-14 | 58-64 | 1/2" | 34-37 |
Graphical Data
Force to Connect vs Pressure: A line graph titled 'Force to Connect vs Pressure' shows the relationship between connection force (in Newtons) and air pressure (in PSI). Four distinct lines represent different UQD sizes (UQD02, UQD04, UQD06, UQD08), illustrating how connection force varies with pressure for each size.
Flow Data: A graph titled 'Flow Data' displays flow rate in liters per minute (lpm) on the left y-axis and gallons per minute (gpm) on the right y-axis, against a logarithmic scale for flow rate (gpm) on the x-axis. It shows the flow rate characteristics for different UQD sizes. A table below provides specific flow rates at 5 m/s for each size in both lpm and gpm.
Size | Flow at 5m/s (lpm) | Flow at 5 m/s (gpm) |
UQD02 | 2.4 | 0.62 |
UQD04 | 9.4 | 2.5 |
UQD06 | 14.7 | 3.9 |
UQD08 | 23.6 | 6.2 |
Part Details
Socket (Female) Part
Figures 1 and 2 illustrate the push-on socketless fitting design for the socket (female) part. Figure 3 shows the male ORB connection type. The table below provides part numbers, order numbers, thread/end sizes, and detailed dimensions (A, B, C, D, Hex) for each UQD size.
UQD | Part number | Order number | Thread / end size | Fig. | Dimensions A | Dimensions B | Dimensions C | Dimensions D | Hex (mm) (in) | |||||||
Hose Tail | ORB | n° | (mm) | (in) | (mm) | (in) | (mm) | (in) | (mm) | (in) | ||||||
UQD02 | 2UQS25HABLS11 2UQS25HARDS11 | - | 1/4 | - | 1 | 38.4 | 1.51 | 18.5 | 0.73 | 14.0 | 0.55 | 19.1 | 0.75 | - | ||
UQD04 | 4UQS37HABLS11 4UQS37HARDS11 | - | 3/8 | - | 1 | 49.5 | 1.95 | 24.6 | 0.97 | 19.0 | 0.75 | 23.7 | 0.93 | - | ||
4UQS25HABLS11 4UQS25HARDS11 | - | 1/4 | - | 1 | 51.2 | 2.01 | 24.6 | 0.97 | 19.0 | 0.75 | 22 | 0.87 | - | |||
UQD06 | 4UQS56ORMBLS11 4UQS56ORMRDS11 | - | 9/16 | 3 | 50.3 | 1.98 | 24.6 | 0.97 | 21 | 0.83 | 9.9 | 0.39 | 19 | 0.75 | ||
6UQS50HABLS11 6UQS50HARDS11 | - | 1/2 | - | 1 | 52.3 | 2.06 | 27.8 | 1.10 | 23 | 0.9 | 25.8 | 1.01 | - | |||
6UQS75ORMBLS11 6UQS75ORMRDS11 | - | 3/4 | 3 | 52.5 | 2.06 | 27.9 | 1.09 | 22 | 0.87 | 11.1 | 0.44 | 22 | 0.86 | - | ||
UQD08 | 8UQS62HABL 8UQS62HARD | - | 5/8 | - | 2 | 68.4 | 2.69 | 35 | 1.38 | 30 | 1.18 | 39 | 1.54 | 27 | 1.06 |
Plug (Male) Part
Figure 4 shows the Male ORB ISO 11926-3 connection type, and Figure 5 shows the ISO 1179-3 type. The table below provides part numbers, order numbers, thread/end sizes, and detailed dimensions (E, F, G, H, J, Hex) for each UQD size.
UQD | Part number | Order number | Thread / end size | Fig. | Dimensions E | Dimensions F | Dimensions G | Dimensions H | Dimensions J | Hex (mm) (in) | ||||||||
BSP | ORB | n° | (mm) | (in) | (mm) | (in) | (mm) | (in) | (mm) | (in) | (mm) | (in) | ||||||
UQD02 | 2UQP43ORMBL 2UQP43ORMRD | 2UQP43ORMBL 2UQP43ORMRD | - | 7/16-20 | 4 | 6.65 | 0.26 | 16.17 | 0.64 | 8.7 | 0.34 | 9.1 | 0.36 | 29.3 | 1.15 | 14 | 0.55 | |
2UQP12MBSBL 2UQP12MBSRD | 2UQP12MBSBL 2UQP12MBSRD | 1/8 | - | 5 | 6.65 | 0.26 | 17.32 | 0.68 | 8.7 | 0.34 | 8 | 0.31 | 30.4 | 1.20 | 15 | 0.59 | ||
UQD04 | 4UQP56ORMBL 4UQP56ORMRD | 4UQP56ORMBL 4UQP56ORMRD | - | 9/16-18 | 4 | 11.07 | 0.44 | 19.63 | 0.77 | 9.8 | 0.39 | 9.9 | 0.39 | 37.9 | 1.49 | 17 | 0.67 | |
4UQP37MBSBL 4UQP37MBSRD | 4UQP37MBSBL 4UQP37MBSRD | 3/8 | - | 5 | 11.07 | 0.44 | 25.40 | 1.00 | 9.8 | 0.39 | 11.2 | 0.44 | 37.9 | 1.49 | 22 | 0.87 | ||
UQD06 | 6UQP75ORMBL 6UQP75ORMRD | 6UQP75ORMBL 6UQP75ORMRD | - | 3/4-16 | 4 | 14.3 | 0.56 | 25.40 | 1.00 | 10 | 0.39 | 11.1 | 0.44 | 41.6 | 1.64 | 22 | 0.87 | |
6UQP37MBSBL 6UQP37MBSRD | 6UQP37MBSBL 6UQP37MBSRD | 3/8 | - | 5 | 14.3 | 0.56 | 25.40 | 1.00 | 10 | 0.39 | 11.2 | 0.44 | 41.6 | 1.64 | 22 | 0.87 | ||
UQD08 | 8UQP87ORMBL 8UQP87ORMRD | 8UQP87ORMBL 8UQP87ORMRD | - | 7/8-14 | 4 | 17.48 | 0.69 | 31.18 | 1.23 | 12 | 0.47 | 12.7 | 0.50 | 47.6 | 1.87 | 27 | 1.06 | |
8UQP50MBSBL 8UQP50MBSRD | 8UQP50MBSBL 8UQP50MBSRD | 1/2 | - | 5 | 17.48 | 0.69 | 34.64 | 1.36 | 12 | 0.47 | 14.5 | 0.57 | 47.6 | 1.87 | 30 | 1.18 |
Note 1: To obtain connected length of coupling, add dimensions A (Fig. 1) and G (Fig. 2) together.
Note 2: For color options, RD suffix corresponds to RED and BL suffix to BLUE.