Danfoss Hansen® FD83 Series Coupling

Thermal Management

Danfoss Hansen's FD83 coupling is designed for fluid transfer and electronics cooling applications where full flow, fluid compatibility, and safety are essential. The FD83 identical halves include two interlock features to eliminate spills and ensure maximum safety. Valves cannot be opened until the coupling halves are mated and coupling halves cannot be disconnected until both halves are closed.

NEW! The FD83 coupling is now available in size 2”.

Product Features

*For reference only, based on Danfoss recommended temperatures.

Applications & Markets

Physical Characteristics

Coupling Size (in) Max. Operating Pressure Min. Burst Pressure Rated Flow (lpm) Rated Flow (gpm) Fluid Loss cc. max CV value
Connected (bar) Connected (psi) Socket/Female Half (bar) Socket/Female Half (psi) Connected (bar) Connected (psi) Socket/Female Half (bar) Socket/Female Half (psi)
1 10 150 10 150 10 150 20 300 189 50 2.6 127
2 New! 10 150 10 150 10 150 20 300 800 211 5.0 30

Flow Data

Test Fluid: Water at 70°F

A graphical representation of pressure drop versus flow rate is provided. The graph shows pressure drop in PSI and bar on the Y-axis and flow rate in l/min and gpm on the X-axis. Multiple lines represent different flow rates and their corresponding pressure drops.

Dimensions

Part Number Order Number Body Port Size Size Thread Type Dimensions mm (in) Hex mm (in)
Fig. A B
FD83-2052-16-16 FD83-2052-16-16 1 1 1-11-1/2 Female NPTF 1 95.5 (3.76) 71.6 (2.82) 41 (1.63)
FD83-2052-12-16 FD83-2052-12-16 1 3/4 3/4-14 Female NPTF 1 70.1 (2.76) 71.6 (2.82) 41 (1.63)
FD83-2046-16-16 FD83-2046-16-16 1 1 NA 1" Hose Barb 2 84.2 (3.31) 71.6 (2.82) -
FD83-2092-16-16 FD83-2092-16-16 1 1 NA 1" Hose Barb 90° 3 125 (4.92) 71.6 (2.82) -
FD83-2096-16-16 FD83-2096-16-16 1 1 15/16-12 Male ORB 5 95.5 (3.76) 71.6 (2.82) 41 (1.63)
FD83-2140-16-16 FD83-2140-16-16 1 1 G1-11 Male BSPP 5 95.5 (3.76) 71.6 (2.82) 41 (1.63)
FD83-2126-16-16 FD83-2126-16-16 1 1 G1-11 Female BSPP 1 84.3 (3.32) 71.6 (2.82) 41 (1.63)
FD83-2128-16-16 FD83-2128-16-16 1 1 NA Sanitary Flange 1" 4 79.6 (3.13) 71.6 (2.82) -
FD83-2126-32-32 FD83-2126-32-32 2 2 G2-11 Female BSPP 1 122.4 (4.82) 105.3 (4.15) 70 (2.76)
FD83-2046-32-32 11349026 2 2 NA 2" Hose barb 2 156.8 (6.17) 105.3 (4.15) -
FD83-2046-24-32 11349477 2 1 1/2 NA 1 1/2" Hose barb 2 149.8 (5.90) 105.3 (4.15) -
FD83-2046-20-32 11349492 2 1 1/4 NA 1 1/4" Hose barb 2 141.6 (5.57) 105.3 (4.15) -
FD83-2128-32-32 FD83-2128-32-32 2 2 NA Sanitary Flange 2" 4 102.4 (4.03) 105.3 (4.15) -
FD83-2052-32-32 FD83-2052-32-32 2 2 2-11-1/2 Female NPT 1 122.4 (4.82) 105.3 (4.15) 70 (2.76)

Other end connections available upon request.

Danfoss can accept no responsibility for possible errors in catalogs, brochures, and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without subsequent changes being necessary in specifications already agreed. All trademarks in this material are the property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

2 | Danfoss | Produced by Power Solutions | May 2025 AM430256898395en-000103

PDF preview unavailable. Download the PDF instead.

AM430256898395en-000601 Danfoss A/S GPL Ghostscript 10.05.0

Related Documents

Preview Danfoss Hansen UQDB Universal Quick Disconnect Blind-Mate Coupling for Data Centers
Technical overview of the Danfoss Hansen UQDB, a universal quick disconnect blind-mate coupling designed for efficient liquid cooling and thermal management in data centers. Features include self-alignment, dry-break design, high flow, and 100% helium-leak testing, complying with OCP specifications.
Preview Danfoss Data Center Liquid Cooling Solutions: Efficient, Reliable, Sustainable
Explore Danfoss' comprehensive fluid conveyance solutions for data center liquid cooling, offering enhanced performance, energy efficiency, and reliability. Learn about their direct-to-chip cooling technology, hoses, couplings, and fittings designed for modern data centers.
Preview Danfoss Data Center Liquid Cooling Solutions: Efficient, Reliable, Sustainable
Explore Danfoss' advanced fluid conveyance solutions for data center liquid cooling, offering enhanced performance, energy efficiency, and sustainability with direct-to-chip and rack cooling technologies.
Preview Danfoss Hansen FD83 Coupling Operator's Manual
Operator's manual for the Danfoss Hansen FD83 Coupling, providing detailed instructions for connecting, disconnecting, and troubleshooting procedures, along with company information.
Preview Danfoss SOCKETLESS, FD83, and UQD Hose Assembly Instructions
Detailed instructions for assembling SOCKETLESS, FD83, and UQD series hose fittings with Boston EHW094 and EHW194 hoses. Includes assembly, disassembly steps, and clamp information.
Preview Boston by Danfoss Emperor EHW094 Liquid Cooling Hose - Technical Datasheet
Detailed technical specifications and features of the Boston by Danfoss Emperor EHW094 thermoplastic liquid cooling hose, designed for high performance and reliability in demanding applications.
Preview Danfoss Hansen FD83 Coupling Operator's Manual
Operator's manual for the Danfoss Hansen FD83 Coupling, detailing connection, disconnection, troubleshooting, and quality checks. Includes company information and product listings.
Preview Danfoss Hose Assembly Instructions for Boston EHW094 & EHW194 Hose with SOCKETLESS, FD83, and UQD Connectors
Comprehensive guide for assembling and disassembling hydraulic hose connections using Danfoss SOCKETLESS, FD83, and UQD connectors with Boston EHW094 and EHW194 hoses. Includes clamp information and assembly steps.