Installation Configuration
Configuration: Left side install
Units: Millimeters (mm)
Main Unit Dimensions and Connections
Overall Width: 540 mm
Height: 1955 mm
Connections:
- Electrical Circuit: Connection point for electrical supply, compliant with AS/NZS 3000. An "ISOLATION POINT" is indicated by a green circle with a central dot [electrical isolation].
- Hot Water Outlet: Connection point for hot water output, indicated by a red circle with a central dot [hot water outlet].
- Cold Water Supply: Connection point for cold water input, indicated by a blue circle with a central dot [cold water inlet].
Plumbing/Electrical Reference Lines:
- Distance from slab top to hot water connection: 1000 mm.
- Distance from slab top to isolation point: 350 mm.
- Distance from slab top to cold water connection: 100 mm.
Slab and Leveling
The unit is to be installed on a "SLAB".
Slab Height: 100 mm
Level Reference:
- "00 Course level" is aligned with the top of the slab.
- "Ground Level (-01 Courses)" is indicated below the slab.
Clearances (Diagram 2)
Required Clearances:
- Space from unit to wall/obstruction: 1000 mm (left side, as shown in Diagram 2).
- Space between units: 500 mm.
- Space from unit to wall/obstruction: 150 mm (right side, as shown in Diagram 2).
Installation Responsibilities
Builder: Completes all pre-lay plumbing and electrical works.
Plumber: Responsible for running hot & cold lines to the iStore tank location.
Electrician: Responsible for running a new 15A (2.5mm) circuit from the electrical meter box to the tank location. An AC isolator must be installed. The unit must not be energized until the tank is filled with water.
Note: All valves are supplied.