Vortice LINEO 250 Technical Data Sheet

CODE 17181

Mixed flow extractor fans

Certifications

CE, UKCA, CB TEST CERTIFICATE

Description

Enclosures made of fire resistant plastic resin, E2 class, according with ISO EN 11925-2: 2010, in areas close to motor and electrical components.

Nominal diameter 250 mm.

Induction motor, thermally protected, with shaft mounted on ball bearing supports, coupled with a centrifugal impeller.

High water resistance: IPX5 (if installed in a duct).

Speed adjustable through Vortice speed devices.

Technical and Performance Data

ParameterValueParameterValue
Frequency (Hz)50-60Max airflow at Mid speed at 60 Hz (m³/h)1060
Insulation classIIMax airflow at Min speed (l/s)344,4
IPX5Max airflow at Min speed at 60 Hz (l/s)187,5
Max absorbed current at max speed at 60 Hz (A)0,95Max airflow at Min speed at 60 Hz (m³/h)675
Max absorbed current at Max speed (A)0,65Max pressure at 60 Hz (mmH2O)49,3
Max absorbed current at Mid speed (A)0,55Max pressure at Max speed (mmH2O)37,6
Max absorbed current at Mid speed at 60 Hz (A)0,70Max pressure at Max speed (Pa)368,7
Max absorbed current at Min speed (A)0,42Max pressure at Max speed at 60Hz (Pa)483,5
Max absorbed power at Max speed (W)150Max pressure at Mid speed (mmH2O)31,6
Max absorbed power at Max speed at 60 Hz (W)215Max pressure at Mid speed (Pa)309,9
Max absorbed power at Mid speed (W)125Max pressure at Mid speed at 60Hz (mmH2O)28
Max absorbed power at Mid speed at 60 Hz (W)160Max pressure at Mid speed at 60Hz (Pa)274,6
Max absorbed power at Min speed at 60 Hz (W)100Max pressure at Min speed at 60Hz (mmH2O)11,9
Max ambient temperature for continuous operation (°C)50Max pressure at Min speed at 60Hz (Pa)116,7
Max continuous operation room temperature at 60 Hz (°C)40Max RPM2760
Nominal diameter (mm)250Max speed at 60 Hz (Rpm)3050
Power absorbed at 1st speed (W)95Mid speed at 60 Hz (Rpm)2000
Voltage (V)220-240Min RPM1610
Weight (Kg)5,3Min speed at 60 Hz (Rpm)1320
Airflow at 1st speed (l/s)241,7Sound power at supply side at Min speed LWA [dB (A)]64,7
Airflow at 1st speed (m³/h)870Pressure at 1st speed (mmH20)20,1
Breakout sound power LWA at Max speed [dB (A)]64,7Pressure at 1st speed (Pa)197,1
Breakout sound power LWA at Mid speed [dB (A)]61,3RPM at Mid speed2280
Breakout sound power LWA at Min speed [dB (A)]56,0Sound power at extract side at Max speed LWA [dB (A)]75,5
Breakout sound pressure at 3m at Max speed Lp [dB (A)]44,1Sound power at extract side at Mid speed LWA [dB (A)]71,7
Breakout sound pressure at 3m at Mid speed Lp [dB (A)]40,8Sound power at extract side at Min speed LWA [dB (A)]63,9
Breakout sound pressure at 3m at Min speed Lp [dB (A)]35,5Sound power at supply side at Max speed LWA [dB (A)]74,9
Max airflow at Max speed (l/s)408,3Sound power at supply side at Mid speed LWA [dB (A)]72,3
Max airflow at Max speed (m³/h)1470Sound pressure at extract side at 3m at Max speed Lp [dB (A)]58,0
Max airflow at Max speed at 60 Hz (l/s)452,8Sound pressure at extract side at 3m at Mid speed Lp [dB (A)]54,1
Max airflow at Max speed at 60 Hz (m³/h)1630Sound pressure at extract side at 3m at Min speed Lp [dB (A)]46,4
Max airflow at Mid speed (m³/h)1240Sound pressure at suply side at 3m at Max speed Lp [dB (A)]57,4
Max airflow at Mid speed at 60 Hz (l/s)294,4Sound pressure at suply side at 3m at Mid speed Lp [dB (A)]54,8
Max airflow at Mid speed at 60 Hz (m³/h)1060Sound pressure at suply side at 3m at Min speed Lp [dB (A)]47,1

Dimensions

Diagrams show different views of the fan with labeled dimensions:

  • Front view (A, B, G, H, ØM)
  • Side view (C, D, E, F, L)
  • Bottom view (H, L, M, N)
DimensionValue
Size A (mm)300
Size B (mm)378
Size C (mm)322
Size D (mm)Ø 243
Size E (mm)190
Size F (mm)329
Size G (mm)200
Size H (mm)70
Size L (mm)170
Size M (mm)Ø 6,5
Size N (mm)174,5

Curves

A graph displays performance curves, plotting air pressure (p) in Pascals (Pa) against airflow (q) in cubic meters per hour (m³/h) and liters per second (l/s). Multiple lines represent different operating speeds and conditions, showing the relationship between airflow and pressure for each speed.

Accessories

The following accessories are available:

  • TRIO-LINEΟ 503
    Code 12891
  • C 2.5 (COMANDO EL. 2.5 A)
    Code 12967
  • C TEMP
    Code 12992
  • C SMOKE
    Code 12993
  • C HCS
    Code 12994
  • C PIR
    Code 12998
  • C TIMER
    Code 12999

Other Products

KIT SCB (TRASF.E.C.)
Code 22481

Contact Information / Per Informazioni

ITALY

Pre Sales: prevendita@vortice-italy.com

After Sales: postvendita@vortice-italy.com

UNITED KINGDOM & REP. OF IRELAND

Sales Dept: sales@vortice.ltd.uk

Technical Dept: technical@vortice.ltd.uk

OTHER COUNTRIES

Sales Dept: export@vortice-italy.com

After Sales: after-sales@vortice-italy.com

PDF preview unavailable. Download the PDF instead.

FANS70304 ExpertPdf v17.0.0

Related Documents

Preview Vortice LINEO 150 Mixed Flow Extractor Fan Technical Data Sheet
Technical specifications, performance data, dimensions, and accessories for the Vortice LINEO 150 mixed flow extractor fan.
Preview Vortice LINEO 100 ES Technical Data Sheet - Energy Saving Extractor Fan
Detailed technical specifications, performance data, dimensions, and certifications for the Vortice LINEO 100 ES energy-saving mixed flow extractor fan.
Preview Vortice LINEO 250 Ducted Centrifugal Fan Technical Data Sheet
Comprehensive technical specifications, performance data, dimensions, and contact information for the Vortice LINEO 250 ducted centrifugal fan.
Preview VORTICE LINEO 150 ES Technical Data Sheet - Energy Saving Extractor Fan
Detailed technical specifications, performance data, dimensions, and accessory information for the VORTICE LINEO 150 ES energy-saving mixed flow extractor fan.
Preview Vortice LINEO 200 ES Technical Data Sheet and Specifications
Detailed technical specifications, performance data, dimensions, and features of the Vortice LINEO 200 ES energy-saving mixed flow extractor fan.
Preview Vortice LINEO 250 Q Ducted Centrifugal Fan Technical Data Sheet
Detailed technical specifications, performance curves, dimensions, and accessories for the Vortice LINEO 250 Q ducted centrifugal fan, designed for efficient air extraction.
Preview VORTICE LINEO Serie Aspiratori: Manuale di Istruzioni
Manuale di istruzioni completo per gli aspiratori centrifughi assiali VORTICE LINEO. Include dettagli su installazione, funzionamento, sicurezza, manutenzione e specifiche tecniche per i modelli LINEO 100, 125, 150, 160, 200 Q e 250 Q.
Preview Vortice Nordik Evolution R Ceiling Fan - Installation and User Manual
This comprehensive manual provides detailed instructions for the installation, operation, cleaning, and disposal of the Vortice Nordik Evolution R reversible ceiling fan. Includes safety warnings, technical specifications, and EC Declaration of Conformity.