Product Overview
The Philips EasySense SNS212 MC is a fixture-mount wireless node sensor designed for advanced lighting control applications. It utilizes passive infrared (PIR) technology for occupancy detection and is compatible with Xitanium SR drivers.
Electrical Specifications
Parameter | Value |
---|---|
Input Voltage | Powered by SR driver low-voltage interface |
Current Consumption | 13mA |
Nominal Power Consumption | 200mW |
Standby Power | < 1 W on luminaire level, including driver standby power |
Occupancy Sensing Type | Passive infrared (PIR) |
Occupancy Based Control | Default enabled and active for SNS211 MC. Activated upon commissioning for SNS210 MC. |
Occupancy Mode | Default Auto on/off. Other options: Manual on/off, Manual on/auto off. |
Eco On Level | 1-100% |
Hold Time | 5-100 minutes |
Viewing Angle | X = 62°, Y = 84° (See detection pattern) |
Prolong Time | 1-100 minutes + infinite |
Background Light Level | 1- 25 sec |
Grace Fading | 1 sec |
Response Time/Fading to Switch On/Off | Default enabled |
Daylight Sensing Viewing Angle | 40° (half value sensitivity); 2% cut-off point at 75° |
Task Tuning Field Task Level | 1%-100% |
Environmental and Approbation Specifications
Parameter | Value |
---|---|
Operating Ambient Temperature Range | 0°C to 55°C |
Operating Humidity | 20%-85% non condensing |
Storage Temperature | -25 °C - 85 °C |
Storage Humidity | 0-95% non condensing |
Max Case Temperature (Tcase) | 55°C |
Agency Approbations | UL, FCC; Tested and approved for use in plenums |
Limited Warranty | 5 years |
Digital Interface | Xitanium SR |
Status Indicators
After commissioning: Red LED on indicates motion is detected; Yellow LED on indicates vacancy detected & sensor is functional.
Configuration
No. Drivers per Sensor: Four (max)
Field Configuration: Via BLE, parameters set via Philips MasterConnect App.
Operation and Configuration via Mobile App
The SNS212 MC requires commissioning to operate. The node can be commissioned and configured via the Philips MasterConnect app through Bluetooth LE. For a complete description of the features and default settings, as well as details on the app, refer to www.philips.com/easysense.
Wiring Diagram
The EasySense SNS212 MC sensors are compatible with Xitanium SR drivers. To find the SR driver that fits your application needs and for product specifications, please visit www.Signify.com/xitaniumsr.
Wiring Description:
The diagram illustrates connections between the Xitanium SR LED Driver and the EasySense sensor. Use 18AWG solid copper wire, rated >=600V/90C. Strip wire to 3/8".
- Xitanium SR LED Driver Terminals: LINE, NEUTRAL, GROUND, DA+, DA-, LED+, LED-.
- EasySense Sensor Terminals: DA+, DA-, LED+, LED-.
- Connections:
- EasySense DA+ connects to Xitanium SR DA+.
- EasySense DA- connects to Xitanium SR DA-.
- EasySense LED+ connects to Xitanium SR LED+.
- EasySense LED- connects to Xitanium SR LED-.
- Xitanium SR LINE connects to Black wire.
- Xitanium SR NEUTRAL connects to White wire.
- Xitanium SR GROUND connects to Green wire.
Note: The provided wiring diagram is for a 40W driver. Consult the specific driver datasheet for applicable wiring diagrams.
Dimensions
Sensor Dimensions
The sensor features a compact design suitable for fixture integration. Key dimensions are:
- Length: Approximately 1.72 inches (43.8 mm) MAX.
- Width: Approximately 0.96 inches (24.3 mm) MAX.
- Height: Approximately 1.97 inches (50.0 mm) MAX.
- Other dimensions include 0.66 inches (16.8 mm) MAX, 0.30 inches (7.5 mm) MAX, and 0.75 inches (19.0 mm) MAX.
Mounting Dimensions
The sensor can be mounted in different ways:
- Mounting in U-shaped slot in sheet metal (max thickness 1 mm): Requires a slot of approximately 1.71 inches (43.5 mm) by 0.63 inches (16.0 mm).
- Mounting in cut-out in sheet metal (thickness 0.7 mm to 1.0 mm): Requires a cut-out of approximately 1.73 inches (44.0 mm) by 0.67 inches (17.0 mm). A mounting ring is used to secure the sensor to the cut-out.
Installation Methods
The sensor can be installed in a fixture:
- Mounting in a slot: The sensor is inserted into a pre-cut slot within the fixture.
- Mounting in a cut-out with mounting ring: The sensor is placed into a cut-out and secured using an accessory mounting ring.
Accessories
- Accessory Mounting Ring: Part Number SMR-50 / Set of 50. Ordered separately, not included.
- Accessory Mounting Bracket: Part Number SMB-50 / Set of 50. Ordered separately, not included.
Compliance Information
FCC and IC Statement
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules for the United States and Industry Canada (IC) license-exempt RSS standard(s). These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment and is intended for commercial use only. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense. Any changes or modifications not expressly approved by Signify could void the user's authority to operate this equipment.
This equipment should be installed and operated with a minimum distance of 20cm between the radiator and your body.
Déclaration De Conformité À La Fcc/Ic
(French translation of the FCC/IC statement is also present in the document.)
Contact Information
Signify North America Corporation
400 Crossing Blvd, Suite 600
Bridgewater, NJ 08807
Tel. 855-486-2216
Signify Canada Ltd.
281 Hillmount Rd,
Markham, ON, Canada L6C 2S3
Tel. 800-668-9008