Philips MR5300 1.5T MRI System: Room Requirements

Introduction

This document provides users and contractors with essential technical requirements for selecting a room and assessing the feasibility of installing the Philips MR5300 1.5T MRI system. It covers critical aspects of site preparation, equipment specifications, and environmental considerations to ensure optimal performance and safety.

Key Room Selection Criteria

  1. A dedicated power line from a transformer (TP / TPS) is required.
  2. Consider proximity to elevators, electrical rooms, roadways, and metro lines.
  3. The floor's load-bearing capacity must be verified, with limitations on metal content in the floor.
  4. Areas with magnetic field induction of 0.5 mT and above, extending beyond the procedural room, must be accounted for.
  5. The total power requirement for the facility is determined by the UPS system, potentially requiring a higher UPS capacity due to peak currents.
  6. The MR5300 BlueSeal system does not require a helium emergency vent pipe.

Recommended Room Dimensions and Layout

Rooms with smaller dimensions may present mechanical limitations and operational challenges.

Equipment Layout and Specifications

The following diagram illustrates a typical equipment configuration. It serves as a general guide for design. Site conditions, customer preferences, and equipment configuration may influence room geometry and layout. Consult Philips for specific site drawings during early design stages.

Diagram Description: A top-down view of an MRI suite layout showing the procedural room, operator room, and technical room. Magnetic field exclusion zones (0.1mT, 0.3mT, 0.5mT, 1mT, 3mT) are indicated around the MRI scanner. Key areas are labeled with numbers corresponding to equipment specifications.

Magnetic Field Exclusion Zones:

Pos. Equipment Dimensions (WxDxH), mm Mass, kg Heat Dissipation, W Noise, dBA Comments
1 Operator console (without table) 562x61x368 10 300 40
2 MRI scanner gantry 2278x1838x2505 3700 2000 90
3 Patient table 2500x560x947 260
4 Distribution board for climate control system ≈100
5 Main MRI disconnect switch 450x170x600 35
6 Cooling system cabinet 609x800x1955 326 10000 75 Heat dissipation is utilized by the supplied climate control system.
7 Data processing cabinet 550x800x1955 265
8 Gradient coil amplifier cabinet 555x800x1955 467
9 Ventilation unit (SACU) 639x639x886 110
10 Uninterruptible Power Supply (UPS) 120 kVA ≈600x980x1400 ≈240 ≈6000 65
11 Battery cabinet ≈610x980x1400 ≈850
12 UPS disconnect switch
13 RF interference filter 950x220x1575 80 100
14 Main system distribution board 135
15 Additional connection panel 135
16 Air cryo-cooler 110
17 Coil storage cabinet 1600x670x2000

Side and Cross-Sectional Views

Side View: Depicts the MRI scanner and its associated magnetic field exclusion zones. It emphasizes the prohibition of individuals with pacemakers within the 0.5 mT magnetic field zone.

Schematic Section A-A: Shows a cross-section of the MRI room, indicating the scanner, Faraday cage, and magnetic field exclusion zones. It highlights the 0.5 mT controlled access area.

Schematic Section B-B: Illustrates another cross-section, detailing the Faraday cage, room boundaries, and the 0.5 mT controlled access area.

Diagram: A schematic for checking ferromagnetic object placement within a 3x3 meter area around the MRI isocenter. It specifies distances and orientations relative to the magnet's axes (Z, X, Y) and provides a graph illustrating minimum distances from the isocenter to moving ferromagnetic objects of varying weights.

Ferromagnetic Object Placement Guidelines:

Placement Recommendations and Comments

  1. Do not locate the MRI procedural room adjacent (horizontally or vertically) to wards for pregnant women, children, cardiac patients, or rooms for round-the-clock patient stays. Individuals with pacemakers must not be in areas with magnetic field strength of 0.5 mT or higher. The isocenter height is 1.004 m.
  2. Avoid installing the scanner directly beneath rooms with potential water leakage through ceilings.
  3. Do not place significant metal masses, transformers, high-power electrical equipment, elevators, or electrical cables near the MRI procedural room. Also, avoid proximity to moving vehicles like cars, trams, etc. Refer to the diagrams on page 3 for verification.
  4. Avoid utilities under the floor or between walls and the Faraday cage, as access will be impossible after installation, and they can affect equipment operation.
  5. Do not locate the MRI suite in areas influenced by utilities such as elevators, power lines, tram lines, or the metro. In such cases, assess the risk of magnetic field impact with a certified organization or the manufacturer.
  6. Ensure transport routes for the MRI are planned. Typically, a temporary transport opening of 2.5m x 2.5m (WxH) is made in the procedural room wall.
  7. Provide a temporary unloading area of 3m x 3m above the procedural room level. The threshold height between the unloading area and the procedural room depends on the Faraday cage floor thickness.
  8. The total weight of the Faraday cage is approximately 5-7 tons, distributed.

Heating, Ventilation, and Air Conditioning (HVAC)

Philips provides a climate control system that ensures the required air exchange and microclimate specifically for the MRI procedural room and technical room. Installation of the external climate control unit (chiller) requires approximately 3.3m x 1.6m x 1.8m (WxDxH) space and weighs around 1000 kg. Recommended chiller placement is near the technical room, outside the building, or on the roof as agreed with Philips. Additional climate control equipment is not required.

Other rooms within the MRI complex (e.g., operator room, preparation room) are not connected to the climate control system. Air exchange in these areas should be provided according to relevant documentation.

Power Supply Requirements

Two separate power feeds are necessary: one for the MRI system and one for the climate control system.

For the MRI, power must be supplied from the transformer substation via a UPS, with cable cross-section sufficient for maximum power consumption, equipment current, and phase-to-phase resistance not exceeding requirements. This dedicated line should only power Philips equipment. Power and grounding cables should be routed to the location specified in the room preparation plan. Allow at least 2 meters of free cable ends. Bottom cable entry is recommended.

The medical device grounding system must comply with local legislation and standards. The grounding loop should connect to the main building grounding bus. Grounding resistance should not exceed 1.5 Ohm.

Lighting within the MRI procedural room is provided by the Faraday cage manufacturer. Ensure adequate lighting in the operator and technical rooms according to current standards. Due to the numerous utilities on the technical room ceiling, wall-mounted lighting is recommended.

Storage and Handling Conditions

The equipment is delivered in large crates (approx. 50 units, total weight ~22 tons). Arrange and agree on a temporary storage location with the Philips Healthcare project manager, close to the installation room. Storage conditions must prevent exposure to atmospheric precipitation, low, and high temperatures.

Uninterruptible Power Supply (UPS)

The UPS is typically supplied in two cabinets. Due to high heat dissipation, it is recommended to place the UPS in the MRI technical room. This allows the climate control system to manage the heat generated by the UPS.

If space in the technical room is insufficient for the UPS, it can be placed in a separate room with forced cooling, adjacent to the electrical room. In this scenario, a climate control system for the UPS heat dissipation will need to be planned. No additional ventilation requirements for this equipment from Philips exist; ventilation should be designed according to current standards.

PDF preview unavailable. Download the PDF instead.

65f4ed0409084a249fecb30d0080ecea pdfplot16.hdi 16.03.061.00000 AutoCAD 2024 - English 2024 (24.3)

Related Documents

Preview Philips MR7700 3.0T MRI System: Room Requirements and Layout Guide
This document outlines the essential room requirements, layout considerations, and technical specifications for installing the Philips MR7700 3.0T MRI system. It covers electrical, environmental, and spatial needs to ensure optimal performance and safety.
Preview MPT Ingenia 1.5T Omega / OmegaHP: Room Requirements and Technical Specifications
This document outlines the essential technical requirements for selecting and preparing a suitable room for the MPT Ingenia 1.5T Omega and OmegaHP MRI systems. It covers room dimensions, environmental criteria, power supply, and layout considerations for optimal installation and operation.
Preview MPT Ingenia Ambition 1.5T S/X: Room Requirements and Technical Specifications
This document outlines the essential technical requirements for selecting and preparing a room for the MPT Ingenia Ambition 1.5T S/X MRI system. It details room dimensions, power, ventilation, and magnetic field considerations for optimal installation and operation.
Preview Philips Ingenia Elition 3.0T S/X MRI System: Room Requirements and Layout
This document outlines the essential technical requirements and considerations for selecting and preparing a suitable room for the Philips Ingenia Elition 3.0T S/X MRI system. It covers room dimensions, power supply, ventilation, magnetic field safety zones, and equipment placement.
Preview Philips MR 5300: Revolutionizing MRI Operations
Discover the Philips MR 5300, a 1.5T MRI system featuring BlueSeal magnet technology for helium-free operations. Enhance patient throughput with faster scans, automated workflows, and high-quality diagnostic imaging.
Preview Philips MRI Innovations: Enhancing Patient Experience and Image Quality
Explore how Philips' advanced MRI innovations, driven by AI and automation, significantly improve patient comfort, image quality, and workflow efficiency, featuring insights from medical professionals.
Preview Cardiac MR Functional Imaging Guide
An application tip providing information on Cardiac MR functional imaging using a 1.5T Philips MRI system, including cine scans for wall motion analysis and workflow guides.
Preview North Star's Blueprint for Scaling Imaging with Remote Scanning Using Philips ROCC
A customer story detailing how North Star Diagnostic Imaging improved imaging efficiency, consistency, and staff satisfaction by implementing Philips Radiology Operations Command Center (ROCC) for remote scanning operations.