MPT Ingenia 1.5T Omega / OmegaHP: Room Requirements and Technical Specifications

This document provides users and contractors with the essential technical requirements for selecting a room and assessing the feasibility of installing the MPT Ingenia 1.5T Omega / OmegaHP equipment.

Room Selection Criteria

Key considerations for room selection include:

Recommended Room Dimensions and Components

Recommended Dimensions:

Rooms with smaller dimensions may present mechanical limitations and operational or maintenance challenges.

Equipment Layout and Specifications

The following diagrams illustrate a typical equipment configuration and serve as a general guide for design. Site conditions, customer preferences, and equipment configuration may influence room geometry and layout. It is recommended to request specific site drawings from a Philips representative during the early stages of design.

Side View
People with pacemakers are not permitted in areas with magnetic field strength of 0.5 mT or higher.

Diagram showing magnetic field exclusion zones around the MRI scanner.

Schematic Section A-A

Diagram illustrating magnetic field exclusion zones and room boundaries.

Schematic Section B-B

Diagram illustrating magnetic field exclusion zones, Faraday cage, and room boundaries.

Diagram for checking ferromagnetic object placement within a 3x3 meter area around the MPT isocenter

Diagram showing distances from the MPT isocenter to moving ferromagnetic objects of varying weights, with different requirements for Z-axis and X/Y-axis placement, and floor loading specifications.

Characteristics of Mounted Equipment

Pos.EquipmentDimensions (WxDxH), mmMass, kgHeat Dissipation, WNoise, dBAComments
1Operator console (without table)562x61x3681030040
2Scanner gantry2278x1838x25053700200090
3Patient table2500x560x947260
4Distribution board for climate control system≈100
5Main MRI disconnect switch450x170x60035
6Cooling system cabinet609x800x1955326450075Heat dissipation is utilized by the climate control system.
7Data processing cabinet550x800x1955265
8Gradient coil amplifier cabinet555x800x1955467
9Ventilation unit (SACU)639x639x886110
10Uninterruptible Power Supply (UPS) 120 kVA≈600x980x1400≈240≈600065Heat dissipation is utilized by the climate control system.
11Battery cabinet≈610x980x1400≈850
12UPS disconnect switch
13RF interference filter950x220x157580100
14Main system distribution board135
15Additional connection panel135
16Air cryo-cooler110
17Coil accessory cabinet1600x670x2000

Additional Recommendations and Comments

  1. The MPT procedure room should not be adjacent (horizontally or vertically) to wards for pregnant women, children, or cardiac patients, nor to rooms for overnight patient stays (according to SP 2.1.2678-20). People with pacemakers are also not permitted in areas with magnetic field strength of 0.5 mT or higher. The height of the tomograph's isocenter is 1.004 m.
  2. It is not recommended to install the tomograph beneath rooms from which water leakage through ceilings is possible.
  3. Avoid placing significant masses of metal, transformers, high-power electrical equipment, elevators, and electrical cables near the MPT procedure room. Vehicles, trams, etc., moving in close proximity to the MRI suite can also have an undesirable effect. Refer to the diagram and graph on page 3 for verification.
  4. Communications under the floor of the rooms, and between walls and the Faraday cage, are highly undesirable. Besides affecting the equipment's operation, access to them after installation will be impossible.
  5. It is not recommended to locate the MRI suite in areas affected by communications (elevators, power lines, tram lines, metro lines, etc.). In such cases, assess the risk of magnetic field impact by a certified organization or the equipment manufacturer.
  6. A helium emergency exhaust pipe exits through the wall to the outside. Under normal conditions, a minimal amount of gaseous helium is released through it. However, in an emergency, a large amount of helium at very low temperatures is released in a short period. Therefore, it is necessary to fence off an area within a 3 m radius of the pipe outlet, restrict access for people, and prohibit the placement of equipment requiring maintenance, opening windows, and air intake systems.
  7. Consider the MRI transport path. Typically, a temporary transport opening in the procedure room wall measuring 2.5 m x 2.5 m (W x H) is made for equipment transport.
  8. A temporary unloading area measuring 3 m x 3 m, located above the procedure room level, must be provided. The threshold height between the unloading area and the procedure room depends on the thickness of the Faraday cage floor.
  9. The total mass of the Faraday cage is approximately 5-7 tons, with distributed weight.

Heating, Ventilation, and Air Conditioning

Philips provides a climate control system for the equipment's operation, ensuring the required air exchange and microclimate only in the MPT procedure room and technical room. A space of approximately 3.3 m x 1.6 m x 1.8 m (W x D x H), weighing ~1000 kg, must be reserved for the installation of the external climate system unit (chiller). It is recommended to install the chiller unit near the technical room, outside the building, or on the roof in agreement with Philips. Additional climate control equipment is not required.

Other rooms within the MRI suite (e.g., operator room, preparation room, etc.) are not connected to the climate control system. Air exchange in these rooms should be provided in accordance with applicable regulations.

Power Supply Requirements

  1. Power supply scheme: Star, 5-wire, TN-C-S: 3 phases, neutral, protective conductor.
    • Supply voltage: 380/400 V.
    • Permissible voltage fluctuations: +10% / -10%.
    • Mains frequency: (50±3) Hz.
    • Phase-to-phase resistance of the network: no more than 0.20 Ohm for Ingenia 1.5 Omega and no more than 0.15 Ohm for Ingenia 1.5 OmegaHP (parameter to be checked at the MRI disconnect switch in the technical room before installation).
    • Total power for Omega gradient: 60 kVA, Nominal current - 90 A; and for OmegaHP: 80 kVA, Nominal current - 116 A.
    • Peak current: 400A (for no more than 5 ms), 500A (for no more than 1 ms), Power factor = 0.9.
    • Climate control system power: approximately 60 kVA, Nominal current approximately 90 A.
  2. Two separate power supplies must be installed (one for the MRI system, the other for the climate control system). For the MRI, power should be supplied from the transformer substation, through the UPS, with a cross-section that ensures maximum power consumption, equipment current, and phase-to-phase network resistance not exceeding the required level. Only Philips equipment should be connected to this separate line. Power and grounding cables should be routed to the location indicated on the room preparation plan for installation. Free cable ends should be at least 2 m long. Cable routing from below is recommended.
  3. The grounding of the medical device must comply with local legislation and regulatory requirements. The grounding loop should be connected to the main grounding bus of the building. The resistance of the grounding device should not exceed 1.5 Ohm.
  4. MRI procedure room lighting is provided by the Faraday cage manufacturer. Lighting in the operator room and technical room should be provided according to current standards. Due to the presence of many communications on the technical room ceiling, wall-mounted lighting is recommended.

Storage and Handling Conditions

The equipment is delivered in large-sized boxes (approx. 50 units, total weight approx. 22 tons). A temporary storage location for the equipment must be prepared and agreed upon with the Philips Healthcare project manager, adhering to the following storage conditions. The temporary storage location should be in close proximity to the equipment installation room.

The equipment must be stored in conditions that exclude exposure to atmospheric precipitation, low and high temperatures.

Uninterruptible Power Supply (UPS)

The UPS is typically supplied in two cabinets. Due to high heat dissipation, it is recommended to locate the UPS in the MRI technical room. In this case, the climate control system will dissipate the excess heat from the UPS. If there is insufficient space in the technical room for the UPS, it may be located in a separate room with forced cooling, adjacent to the electrical room. In this scenario, a climate control system will be needed to manage the excess heat from the UPS.

Philips has no additional ventilation requirements for this equipment. Ventilation should be designed according to applicable standards.

PDF preview unavailable. Download the PDF instead.

080b8cf968fb4c42afecb30d0080e3dc pdfplot16.hdi 16.03.061.00000 AutoCAD 2024 - English 2024 (24.3)

Related Documents

Preview Philips BlueSeal: Helium-Free 1.5T MRI System - Innovation, Performance, and Patient Experience
Explore the Philips BlueSeal, a revolutionary helium-free 1.5T MRI system designed for enhanced clinical performance, operational efficiency, and patient comfort. Discover its innovative features, AI capabilities, and environmental benefits.
Preview MPT Ingenia Ambition 1.5T S/X: Room Requirements and Technical Specifications
This document outlines the essential technical requirements for selecting and preparing a room for the MPT Ingenia Ambition 1.5T S/X MRI system. It details room dimensions, power, ventilation, and magnetic field considerations for optimal installation and operation.
Preview Philips Ingenia Elition 3.0T S/X MRI System: Room Requirements and Layout
This document outlines the essential technical requirements and considerations for selecting and preparing a suitable room for the Philips Ingenia Elition 3.0T S/X MRI system. It covers room dimensions, power supply, ventilation, magnetic field safety zones, and equipment placement.
Preview Philips BlueSeal Magnet: Helium-Free MR Operations
Discover the Philips BlueSeal magnet, a revolutionary, fully sealed MRI system designed for helium-free operations. Enhance productivity, reduce costs, and improve patient safety with its advanced micro-cooling technology and EasySwitch solutions.
Preview Philips MR 5300: Revolutionizing MRI Operations
Discover the Philips MR 5300, a 1.5T MRI system featuring BlueSeal magnet technology for helium-free operations. Enhance patient throughput with faster scans, automated workflows, and high-quality diagnostic imaging.
Preview Philips MR5300 1.5T MRI System: Room Requirements and Technical Specifications
This document outlines the essential room requirements and technical specifications for the Philips MR5300 1.5T MRI system, covering site selection criteria, room dimensions, equipment layout, and electrical and environmental considerations.
Preview Philips MR7700 3.0T MRI System: Room Requirements and Layout Guide
This document outlines the essential room requirements, layout considerations, and technical specifications for installing the Philips MR7700 3.0T MRI system. It covers electrical, environmental, and spatial needs to ensure optimal performance and safety.
Preview Philips MRI Innovations: Enhancing Patient Experience and Image Quality
Explore how Philips' advanced MRI innovations, driven by AI and automation, significantly improve patient comfort, image quality, and workflow efficiency, featuring insights from medical professionals.