MPT Ingenia Ambition 1.5T S/X: Room Requirements and Technical Specifications

Room Selection Criteria

This document provides users and contractors with the essential technical requirements for selecting a room and assessing the feasibility of installing the equipment.

Important Considerations:

Recommended Room Dimensions and Layout

Procedure Room: 7000 x 4800 mm

Operator Room: 3000 x 4800 mm

Technical Room: 3000 x 5100 mm

Recommended Ceiling Height: 3000 mm (floor to ceiling slab)

Rooms with smaller dimensions may present mechanical limitations and operational or maintenance difficulties.

Equipment Layout and Specifications

The diagram below illustrates a typical equipment configuration and serves as a general design guide. Site conditions, customer preferences, and/or equipment configuration may significantly influence room geometry and equipment placement. It is recommended to request specific site drawings from a Philips representative during the early stages of design.

[Diagram showing MRI room layout with dimensions and zones: Procedure Room (38 m²), Technical Room (16 m²), Control Room (16 m²). Key zones indicated: A (ferromagnetic object restriction), B (minimum installation/service space), C (0.5 mT magnetic field induction zone), D (water supply, sewage, floor drain), E (recommended unloading area). Dimensions provided for various components and distances.]
Pos.EquipmentDimensions (WxDxH), mmMass, kgHeat Dissipation, WNoise, dBAComments
1Operator Console (without table)562x61x36810300
2Tomograph Gantry2278x1838x2505370020005590
3Patient Table2500x560x947260
4Climate System Distribution Unit≈100
5Main MRI Disconnect Switch450x170x60035
6Cooling System Cabinet609x800x1955326800075Heat dissipation is utilized by the climate system.
7Data Processing Cabinet550x800x1955265
8Gradient Coil Amplifier Cabinet555x800x1955467
9Ventilation Unit (SACU)639x639x886110
10Uninterruptible Power Supply (UPS) 120 kVA≈600x980x1400≈240≈600065Heat dissipation is utilized by the climate system.
11Battery Cabinet≈610x980x1400≈850
12UPS Disconnect Switch
13RF Interference Filter950x220x157580100
14Main System Distribution Board135
15Additional Connection Panel135
16Air Cryo-Cooler110
17Coil Storage Cabinet1600x670x2000

Side View and Cross-Sections

Side View

People with pacemakers should not be in areas with magnetic field strength of 0.5 mT or higher.

[Diagram showing side view of MRI scanner with magnetic field contours (0.1 mT, 0.3 mT, 0.5 mT, 1 mT, 3 mT) and room boundaries.]

Schematic Section A-A

[Diagram showing schematic section A-A of MRI scanner with magnetic field contours and room boundaries.]

Schematic Section B-B

[Diagram showing schematic section B-B of MRI scanner with magnetic field contours and room boundaries.]

Ferromagnetic Object Placement Check

The diagram below is for checking the placement of ferromagnetic objects within a 3x3 meter area around the MRI isocenter.

[Diagram illustrating zones for checking ferromagnetic object placement relative to the MRI isocenter, with distances specified for Z-axis and X/Y axes. Includes graphs for minimum distance from isocenter to moving ferromagnetic objects by weight and floor loading capacity.]

General Recommendations and Comments:

Heating, Ventilation, and Air Conditioning (HVAC)

Philips provides a climate control system that ensures the required air exchange and microclimate only in the MRI procedure room and technical room. A location for the external climate control unit (chiller) of approximately 3.3 m x 1.6 m x 1.8 m (W x D x H) with a weight of ~1000 kg needs to be reserved. The recommended installation area for the chiller is near the technical room, outside the building, or on the roof in agreement with Philips. Additional climate control equipment is not required.

Other rooms within the MRI complex (e.g., control room, preparation room, etc.) are not connected to the climate control system. Air exchange in these rooms should be provided in accordance with applicable regulations.

Power Supply Requirements

Two separate power supplies are required (one for the MRI system, one for the climate system).

For the MRI: from the transformer substation, through the UPS, with a cross-section ensuring maximum power consumption, equipment current, and mains phase resistance not exceeding the required level. Only Philips equipment should be connected to this separate line. Power and grounding cables should be routed to the location indicated on the room preparation plan for installation. Free ends of cables should be at least 2 m long. Bottom cable routing is recommended.

The grounding system for the medical device must comply with local legislation and regulatory requirements. The grounding loop should be connected to the main grounding bus of the building. The grounding resistance should not exceed 1.5 Ohm.

Lighting within the MRI procedure room is provided by the Faraday cage manufacturer. Lighting in the control room and technical room should be provided according to current standards. Due to the numerous communications on the technical room ceiling, wall-mounted lighting is recommended.

Storage and Handling Conditions

The equipment is delivered in large crates (approx. 50 units, total weight ~22 tons). A temporary storage area for the equipment must be prepared and agreed upon with the Philips Healthcare project manager, adhering to the storage conditions below. The temporary storage location should be in close proximity to the equipment installation room.

Equipment must be stored in conditions that exclude exposure to atmospheric precipitation, low, and high temperatures.

Uninterruptible Power Supply (UPS)

The UPS is typically supplied in two cabinets. Due to high heat dissipation, it is recommended to place the UPS in the MRI technical room. In this case, the climate control system will dissipate the excess heat from the UPS.

If there is insufficient space in the technical room for the UPS, it can be placed in a separate room with forced cooling, adjacent to the electrical room. In this scenario, a climate control system will need to be planned to dissipate the excess heat from the UPS.

No additional ventilation requirements for this Philips equipment are specified. Ventilation should be designed according to applicable standards.

PDF preview unavailable. Download the PDF instead.

f7d106f233a84ac5bc20b30d0080e03c pdfplot16.hdi 16.03.061.00000 AutoCAD 2024 - English 2024 (24.3)

Related Documents

Preview MPT Ingenia 1.5T Omega / OmegaHP: Room Requirements and Technical Specifications
This document outlines the essential technical requirements for selecting and preparing a suitable room for the MPT Ingenia 1.5T Omega and OmegaHP MRI systems. It covers room dimensions, environmental criteria, power supply, and layout considerations for optimal installation and operation.
Preview Philips Ingenia Elition 3.0T S/X MRI System: Room Requirements and Layout
This document outlines the essential technical requirements and considerations for selecting and preparing a suitable room for the Philips Ingenia Elition 3.0T S/X MRI system. It covers room dimensions, power supply, ventilation, magnetic field safety zones, and equipment placement.
Preview Philips BlueSeal Magnet: Helium-Free MR Operations
Discover the Philips BlueSeal magnet, a revolutionary, fully sealed MRI system designed for helium-free operations. Enhance productivity, reduce costs, and improve patient safety with its advanced micro-cooling technology and EasySwitch solutions.
Preview Philips MR5300 1.5T MRI System: Room Requirements and Technical Specifications
This document outlines the essential room requirements and technical specifications for the Philips MR5300 1.5T MRI system, covering site selection criteria, room dimensions, equipment layout, and electrical and environmental considerations.
Preview Philips MR7700 3.0T MRI System: Room Requirements and Layout Guide
This document outlines the essential room requirements, layout considerations, and technical specifications for installing the Philips MR7700 3.0T MRI system. It covers electrical, environmental, and spatial needs to ensure optimal performance and safety.
Preview Philips MR 5300: Revolutionizing MRI Operations
Discover the Philips MR 5300, a 1.5T MRI system featuring BlueSeal magnet technology for helium-free operations. Enhance patient throughput with faster scans, automated workflows, and high-quality diagnostic imaging.
Preview Philips MRI Innovations: Enhancing Patient Experience and Image Quality
Explore how Philips' advanced MRI innovations, driven by AI and automation, significantly improve patient comfort, image quality, and workflow efficiency, featuring insights from medical professionals.
Preview Philips SPK7207WL 2000 Series Wired Mouse User Manual
Comprehensive user manual for the Philips SPK7207WL 2000 Series wired mouse. Includes function overview, connection guide, system requirements, technical specifications, and troubleshooting tips.