Philips Ingenia Elition 3.0T S/X: Room Requirements and Layout

This document provides users and contractors with the essential technical requirements for selecting a room and assessing the feasibility of installing the Philips Ingenia Elition 3.0T S/X MRI equipment.

General Room Requirements

Please note the following:

  1. A dedicated power line from a transformer (TP / TRS) is required.
  2. Consider the proximity to elevators, electrical rooms, traffic routes, and the metro.
  3. Verify the floor's load-bearing capacity; there are also limitations on the amount of metal in the floor.
  4. Identify areas with magnetic field induction of 0.5 mT and higher outside the procedure room.
  5. The total power requirement for the medical facility is determined by the UPS system, which may allow for a higher UPS capacity due to peak currents.
  6. Consider the route for the quench pipe and the helium exhaust zone.

Recommended Room Dimensions and Layout

Procedure Room: 7300 x 6500 mm

Operator Room: 3000 x 6500 mm

Technical Room: 3000 x 6500 mm

Recommended ceiling height: 3200 mm from floor to ceiling slab.

Rooms with smaller dimensions may present mechanical limitations and operational or maintenance difficulties.

Layout Diagram and Equipment Specifications

The diagram below is based on a typical equipment configuration and serves as a general guide for design. Site conditions, customer preferences, and/or equipment configuration may significantly influence room geometry and equipment placement. It is recommended to request drawings for a specific site from a Philips representative during the early stages of design.

Schematic layout of the MRI suite, including procedure room, operator room, technical room, and safety zones.
Side view illustrating magnetic field zones and room boundaries.
Cross-sectional view A-A showing magnetic field zones and room boundaries.
Cross-sectional view B-B showing magnetic field zones and room boundaries.
Diagram for checking the placement of ferromagnetic objects within a 3x3 meter area around the MRI isocenter.
Graph showing the minimum distance from the MRI isocenter to moving ferromagnetic objects of a certain weight.
Item No.EquipmentDimensions (WxDxH), mmWeight, kgHeat Dissipation, WNoise Level, dBAComments
1Operator console (without table)609x885x762174300--
2MRI scanner gantry1868x2278x23206300200040-
3Patient table-260---
4Distribution board for climate control system450x170x600100---
5Main MRI disconnect switch-35---
6Cooling system cabinet595x801x1955320600075Heat dissipation is utilized by the supplied climate control system.
7Data processing cabinet595x801x1955333---
8Gradient cabinet800x787x1950562---
9Uninterruptible Power Supply (UPS) unit≈707x845x1930≈470≈900065Heat dissipation is utilized by the supplied climate control system.
10Battery cabinet≈1000x845x1930≈1626---
11UPS disconnect switch-----
12RF interference filter-80---
13Air cooling unit----72
14Coil accessory cabinet-----

Additional Placement Recommendations and Comments

  1. Do not place the MRI procedure room adjacent (horizontally or vertically) to wards for pregnant women, children, or cardiac patients, or to rooms for round-the-clock patient stays (as per SN 2.1.2678-20). Also, do not allow individuals with pacemakers in the zone with magnetic field strength of 0.5 mT or higher. The height of the MRI isocenter is 1.004 m.
  2. It is not recommended to install the scanner under rooms from which water leakage through ceilings is possible.
  3. Do not place significant masses of metal, transformers, high-power electrical equipment, elevators, or electrical cables near the MRI procedure room. Additionally, vehicles, trams, etc., moving in close proximity to the MRI suite can have an undesirable influence. For verification, it is recommended to use the diagrams and graphs on page 3.
  4. Communications under the room floors, as well as between walls and the Faraday cage, are highly undesirable. Besides their influence on the equipment's operation, access to them after installation will be impossible.
  5. It is not recommended to locate the MRI suite in the influence zone of communications (elevators, power lines, tram tracks, metro, etc.). In such cases, the risk of impact on the magnetic field should be assessed by an accredited organization or the equipment manufacturer.
  6. A helium emergency exhaust pipe exits through the wall to the outside. Under normal conditions, a minimal amount of helium gas exits through it, but in an emergency, a large amount of helium at a very low temperature is released in a short period. Therefore, the area within a 3 m radius of the pipe outlet must be secured, and access for people restricted. Open windows and air intake systems should be excluded.
  7. Provision must be made for MRI transport routes. Typically, a temporary transport opening in the procedure room wall of 2.5 m x 2.5 m (W x H) is made for equipment transport.
  8. A temporary unloading area of 3 m x 3 m above the procedure room level must be provided. The height of the threshold between the unloading area and the procedure room depends on the thickness of the Faraday cage floor.
  9. The total weight of the Faraday cage is approximately 5-7 tons, with distributed weight.

Heating, Ventilation, and Air Conditioning

Philips provides a climate control system for the operation of the equipment, ensuring the required air exchange and microclimate only in the MRI procedure room and technical room. For the installation of the external climate control unit (chiller), a space of approximately 3.3 m x 1.6 m x 1.8 m (W x D x H) with a weight of ~1000 kg must be reserved. It is recommended to install the chiller near the technical room, outside the building, or on the roof in agreement with Philips. No additional climate control equipment installation is required.

Other rooms within the MRI suite (e.g., control room, preparation room, etc.) are not connected to the climate control system. Air exchange in these rooms should be provided in accordance with regulatory documentation.

Power Supply Requirements

  1. Power supply scheme: Star connection, 5-wire, TN-C-S: 3 phases, neutral, protective conductor.
    • Permissible voltage fluctuations: +10% / -10%.
    • Supply voltage: 380/400 V.
    • Mains frequency: (50±3) Hz.
    • Phase-to-phase impedance of the network: no more than 0.15 Ohm (parameter to be checked at the MRI disconnect switch in the technical room before installation).
    • Total power for the MPT Elition system: 86 kVA, Nominal current: 124 A.
    • Peak current: 400A (for no more than 5 ms), 500A (for no more than 1 ms), Power factor = 0.9.
    • Climate control system power: approximately 60 kVA, Nominal current: approximately 90 A.
  2. Two separate power feeds must be provided (one for the MRI system, the other for the climate control system). For the MRI system, the feed should be from the transformer substation, through the UPS, with a cross-section ensuring the maximum power consumption, equipment current, and phase-to-phase network impedance not exceeding the required level. Only Philips equipment should be connected to this separate line. Power and grounding cables should be brought to the location indicated on the room preparation plan for installation. Free cable ends should be at least 2 m long. Cable entry from below is recommended.
  3. The grounding system for the medical device must comply with local legislation and regulatory requirements. The grounding loop should be connected to the main grounding bus of the building. The grounding resistance should not exceed 1.5 Ohm.
  4. Lighting inside the MRI procedure room is provided by the Faraday cage manufacturer. Lighting in the control room and technical room should be provided in accordance with current standards. Due to the numerous communications present on the technical room ceiling, wall-mounted lighting is recommended.

Storage and Storage Conditions

The equipment is supplied in large crates (approximately 50 units, totaling about 22 tons). A temporary storage location for the equipment must be prepared and agreed upon with the Philips Healthcare project manager, adhering to the storage conditions below. The temporary storage location should be in close proximity to the equipment installation room.

The equipment must be stored in conditions that exclude exposure to atmospheric precipitation, low and high temperatures.

Uninterruptible Power Supply (UPS)

The UPS is typically supplied in two cabinets. Due to high heat dissipation, it is recommended to locate the UPS in the MRI technical room. In this case, the climate control system will dissipate the excess heat from the UPS.

If there is insufficient space in the technical room for the UPS, it can be located in a separate room with forced cooling, adjacent to the electrical room. In this case, a climate control system will be needed to remove excess heat from the UPS.

There are no additional ventilation requirements for this Philips equipment. Ventilation should be designed according to current standards.

PDF preview unavailable. Download the PDF instead.

a11f12dafda640ff9cd5b30d0080e1f5 pdfplot16.hdi 16.03.061.00000 AutoCAD 2024 - English 2024 (24.3)

Related Documents

Preview Philips MR7700 3.0T MRI System: Room Requirements and Layout Guide
This document outlines the essential room requirements, layout considerations, and technical specifications for installing the Philips MR7700 3.0T MRI system. It covers electrical, environmental, and spatial needs to ensure optimal performance and safety.
Preview MPT Ingenia Ambition 1.5T S/X: Room Requirements and Technical Specifications
This document outlines the essential technical requirements for selecting and preparing a room for the MPT Ingenia Ambition 1.5T S/X MRI system. It details room dimensions, power, ventilation, and magnetic field considerations for optimal installation and operation.
Preview MPT Ingenia 1.5T Omega / OmegaHP: Room Requirements and Technical Specifications
This document outlines the essential technical requirements for selecting and preparing a suitable room for the MPT Ingenia 1.5T Omega and OmegaHP MRI systems. It covers room dimensions, environmental criteria, power supply, and layout considerations for optimal installation and operation.
Preview Philips BlueSeal: Helium-Free 1.5T MRI System - Innovation, Performance, and Patient Experience
Explore the Philips BlueSeal, a revolutionary helium-free 1.5T MRI system designed for enhanced clinical performance, operational efficiency, and patient comfort. Discover its innovative features, AI capabilities, and environmental benefits.
Preview Philips MRI Innovations: Enhancing Patient Experience and Image Quality
Explore how Philips' advanced MRI innovations, driven by AI and automation, significantly improve patient comfort, image quality, and workflow efficiency, featuring insights from medical professionals.
Preview Philips MR 5300: Revolutionizing MRI Operations
Discover the Philips MR 5300, a 1.5T MRI system featuring BlueSeal magnet technology for helium-free operations. Enhance patient throughput with faster scans, automated workflows, and high-quality diagnostic imaging.
Preview Philips MR5300 1.5T MRI System: Room Requirements and Technical Specifications
This document outlines the essential room requirements and technical specifications for the Philips MR5300 1.5T MRI system, covering site selection criteria, room dimensions, equipment layout, and electrical and environmental considerations.
Preview Philips BlueSeal Magnet: Helium-Free MR Operations
Discover the Philips BlueSeal magnet, a revolutionary, fully sealed MRI system designed for helium-free operations. Enhance productivity, reduce costs, and improve patient safety with its advanced micro-cooling technology and EasySwitch solutions.