inVENTer aV100 ALD Installation Instructions
Ventilation device without heat recovery
Trademarks, Copyrights, and Industrial Property Rights
inVENTer® is a protected trademark of inVENTer GmbH. The copyright to this document remains with the manufacturer. Rights to all content and images: © inVENTer GmbH 2022. All trademarks used are the property of their respective owners.
Disclaimer
This documentation is a translation of the original German installation instructions and must be passed on to the user after installation. While efforts have been made to ensure conformity with the described hardware and software, deviations may occur. This documentation covers the standard product range and may not include all detailed information for every product type or conceivable scenario. Illustrations may differ slightly from the purchased product but function remains the same. The latest version is available at www.inventer.eu/downloads.
Company Information
Publisher: inVENTer GmbH
Ortsstraße 4a
D-07751 Löberschütz
Germany
Telefon: +49 (0) 36427 211-0
Fax: +49 (0) 36427 211-113
E-Mail: info@inventer.de
Web: www.inventer.eu
CEO: Annett Wettig
VAT ID number: DE 815494982
Jena District Court: HRB 510380
User and Safety Instructions
Thank you for purchasing this high-quality product from inVENTer. This section provides essential safety precautions for the safe and proper operation of your ventilation system.
User Information
Safety and warning instructions are structured uniformly and marked with a symbol on the left. Signal words indicate the hazard level:
- DANGER: Imminent danger of serious injury or death.
- WARNING: Possible danger of serious injury or death.
- CAUTION: Direct danger or minor/significant injury.
- NOTICE: Direct or possible risk of property damage.
Follow the described measures to avoid hazards and damage.
Other Symbols Used
- TIP: Practical and useful tips.
- [Tool icon]: Additional tools and aids required.
- [Red arrow pointing left]: Illustration shows the outer wall.
- [Blue arrow pointing left]: Illustration shows the outer wall.
- [Checkmark icon]: Action required.
- [Magnifying glass icon]: Check results.
- [Target icon]: Action focus.
Safety Instructions
Operating instructions are part of the device and must be available at all times. Read carefully before performing any work and observe all instructions. Failure to do so may result in personal injury and/or property damage.
Intended Use
The external wall air diffuser aV100 ALD is used for fresh air supply in residential spaces, supplementing extract air devices, in accordance with DIN 18017-3 or DIN 1946-6. Use contrary to the intended purpose voids all liability claims.
General Information
- Observe applicable standards, regulations, and directives, including building regulations, fire protection ordinances, and accident prevention regulations.
- Only use components as described. Modifications are not permitted.
- The device is designed for ambient temperatures between -20 °C and 50 °C.
- Proper transport, storage, assembly, and maintenance are crucial for faultless and safe operation.
Installation and Assembly
CAUTION: The system may only be installed by qualified personnel.
A project plan showing the number and location of ventilation devices and the ventilation principle is recommended. Exact positioning should be checked and adjusted on-site with the planner or user. Installation in the upper wall area is recommended for optimal function.
WARNING: For joint operation with fireplaces, measures must be taken to prevent negative pressure in the building. Consult your chimney sweep and/or building planner.
NOTICE: The device is not suitable for drying buildings. Do not operate until construction work is complete. Seal ventilation device/air outlets dust-tight during construction. Do not remove thread locks until final assembly.
NOTICE: Do not install near room air thermostats, sensitive furniture, or pictures. Observe minimum distances (1.2 m between adjacent air openings) to ensure proper function and access. The wall sleeve must be installed airtightly according to the "RAL installation" standard. Store components upright and do not throw them. To prevent algae, follow installation instructions precisely and consider biocide pre-treatment of the facade. Use insulation anchors for walls with insulation. Use permanently elastic sealing compound for outdoor joints. Avoid touching components with oily/dirty hands or sharp objects.
If your device has a defect, contact the factory representative or technical service.
Improper Use
Improper use includes installation/operation in environments with high oil/grease content, flammable gases/liquids/vapors, extreme dust exposure, temperatures outside -20 – 50 °C, or where components are inaccessible. The unit is not to be used as an opening for smoke discharge/extraction in windowless basements.
Qualified Personnel
Qualified personnel are authorized to install, commission, and label devices, systems, and circuits according to safety engineering standards.
System Overview Ventilation Device aV100 ALD
The aV100 ALD is an external wall air diffuser for fresh air supply, complementing extract air devices. It features an insert with an adjustable inner panel, integrated wind protection and filter, a wall sleeve, and an external cover. The air volume is regulated via the inner panel. The filter cartridge ensures clean air intake.
The standard wall sleeve is 495 mm, with longer options available. Both can be shortened on-site.
Components
- Inner panel (insulated / lockable)
- Filter cartridge incl. filter ISO Coarse (G1)
- External closure
- Pollen filter (optional)
- Wall sleeve
Models
The aV100 ALD series differs in external terminations:
- Basic variant: Equipped with a square weather protection grille aV100.
- Plus variant: Equipped with a rain-proof weather protection hood Flex aV100 (available in white/grey/anthracite/special colors).
- Corner variant: For integration into window reveals.
- Nordic variant: For integration into masonry brick walls.
Refer to separate installation instructions for details on external closure variants.
Construction
The aV100 ALD Plus consists of:
- External closure (Base plate, Drip edge, Cover, Weather protection grille)
- Wall sleeve
- Filter cartridge with wind protection
- Filter ISO Coarse (G1)
- Inner panel base plate ALD100
- Inner panel cover ALD 100
Functions
ALD units are installed in supply air rooms connected to extract air devices. Negative pressure from the extract air device draws outside air in. Fresh air outlets have filters and wind protection. Air volume is regulated at the inner panel by adjusting the opening angle.
Installation Example: Aventus extract air system with aV100 ALD for fresh air supply.
Preparing for Installation
Installation Position
Installation location should follow ventilation planning. Exact positioning requires on-site checks and adjustments with the planner/user. Installation near the ceiling (e.g., 1.80 m above finished floor) is recommended for optimal function. Avoid placing the unit above radiators, thermostats, sensitive furniture, or pictures.
Minimum Distances for Wall Opening
Observe minimum distances to components and building elements on both internal and external walls. A minimum distance of 1.2 m is required between adjacent air openings. Ensure the aV100 ALD is not covered and has free airflow. Maintain a minimum circumferential clearance of 250 mm. Installation close to the ceiling improves air distribution.
Recommendation: Install the wall opening above a radiator to pre-heat incoming air. Position the device so air does not flow directly into the occupied zone (maintain 1-1.2 m distance). Each device must be in its own wall sleeve. Minimize inflow air velocity to avoid drafts.
Component closure | Distance from centre of hole at the | ||
---|---|---|---|
Outer wall [mm] | Inner wall [mm] | frontal [mm] | |
Weather protection grille ALD100 | 250 | – | 60 |
Weather protection hood Flex aV100 | 250 | – | 250 |
External closure Corner | 250… 385 to soffit 250 (above, below, sideways) |
– | – |
External closure Nordic | 250 circumferential | ||
Insert unit ALD100 | – | 250 | 250 |
A Horizontal or vertical on the same wall: 1.2 m |
B Installation over corner: 1.0 m, 1.4 m |
C Installation with height offset: 1.2 m - 0.75 m (y) |
Position of the Wall Opening
Refer to specific installation instructions for other variants. Diagrams illustrate positioning for Basic and Plus variants, including dimensions for the wall opening and the Simplex wall mounting system.
Sectional Drawings
Detailed sectional drawings are provided for the Basic variant (with weather protection grille aV100) and the Plus variant (with weather protection hood Flex aV100), illustrating the assembly of components within the wall structure.
Dimensional Drawings of Components
Dimensional drawings are provided for:
- Weather protection grille aV100 (Frame, Slats, Fixing holes)
- Weather protection hood Flex aV100 (Base plate, Air volume flow guide, Drip edge, Protective grid, Wall sleeve opening, Fixing holes, Cover)
- Inner panel (Base plate, Connecting element, Snap-in hook, Cover, Insert unit, Fixing holes, Fastening cover)
Dimensions
Designation | Depth/Length [mm] | Wide [mm] | High [mm] |
---|---|---|---|
Opening wall sleeve | Wall thickness¹ | Ø115 | |
Wall sleeve R-D103x495 | 495 | Ø103 | |
Weather protection grille aV100 | 55 | 150 | |
Weather protection hood Flex aV100 | 20 – 88 | 181 | 198 |
Inner panel ALD 100 | 180² | 160 | 160 |
¹ with exterior rendering, insulation, masonry and interior rendering.
² open, incl. socket
Installation and Assembly
Read this chapter carefully before installation to avoid errors. Installation must be performed by qualified personnel.
Check the Scope of Supply
Check delivery for completeness and transport damage upon receipt. Report missing items immediately. These instructions cover the standard version; refer to separate instructions for external closure variants.
Components Overview
- External closure: 1a) WPH Flex aV100, 1b) WSG aV100, 1c) Mounting elements, 1d) Sealing strip guide. The Flex aV100 is available in various colors.
- Wall sleeve R-D103: 2a) Styrofoam discs, 2b) Mounting wedges set.
- Inner panel ALD 100: 3a) Inner panel base plate with insert unit (pre-assembled), 3b) Inner panel cover, 3c) Filter cartridge, 3d) Dust filter ISO Coarse (G1).
Create Wall Opening
CAUTION: Falling masonry can cause injury or damage. Install protection against falling masonry and clear the area.
For new constructions, consider the optional Simplex D103 wall mounting system, D120 wall block, or Woodplex for timber construction. Observe minimum distances and installation positions. Consult your planner if unsure.
Create Wall Opening via Core Drilling
Drill a hole with a core drill attachment or milling drill of Ø 115 mm. Ensure the masonry is dry and load-bearing, and that no load-bearing elements are in the drill hole path. The wall opening must have a slope of 1-2° towards the exterior wall.
Installing the Wall Sleeve
Tools required: Measuring tape, angle grinder, spirit level, non-pressing 2K polyurethane foam, cutter, mounting wedge set, styrofoam discs.
Requirements: Wall opening Ø 115 mm is complete. Determine exact wall thickness X and protrusion Y based on exterior rendering (D), insulation (C), masonry (B), and interior plaster (A). Refer to the table for specific calculations based on external closure and inner cover type.
Steps:
- Cut the wall sleeve to the determined dimension X + Y. File edges.
- Remove styrofoam discs. Insert the wall sleeve into the opening, flush with the interior wall, ensuring a 1-2° slope towards the exterior wall using mounting wedges and checking with a spirit level.
- Insert styrofoam discs from inside and outside to prevent contamination.
- Foam-seal the gap between the wall sleeve and masonry with 2K polyurethane foam.
- After hardening (approx. 24 hours), cut off excess foam and protruding mounting wedges flush with the inner or outer wall as needed.
NOTICE: Improper slope can lead to condensation water accumulation and damage. Ensure proper sealing to prevent contamination.
Installing the External Closure
Weather Protection Grille aV100
Tools required: Spirit level, pencil, power drill with Ø 6mm bit, cordless screwdriver, anchors.
Requirements: Exterior wall completed and even, wall sleeve installed.
Steps:
- Insert the weather protection grille into the wall sleeve from outside. Level it with a spirit level.
- Mark the four drill holes, remove the grille, and drill holes (Ø 6 mm, min 50 mm deep). Insert anchors.
- Apply permanently elastic external sealing compound to the spigot and base plate.
- Slide the grille onto the wall sleeve, ensuring the condensate drain slopes towards the floor and away from the wall.
- Screw the grille to the exterior wall.
NOTICE: Misaligned condensate drain can damage the masonry/exterior wall.
Installing the Weather Protection Hood Flex aV100
Tools required: Spirit level, pen, cordless screwdriver, dowel, stop tape, sealing tape 10 mm, screws, saw.
Requirements: Exterior wall completed and even. Wall sleeve with Ø 100 mm installed, with a maximum projection of 10 mm on the outer wall. Remove styrofoam disc from the outer wall side of the sleeve.
Steps:
- Slide the base plate onto the projecting wall sleeve. Ensure the protective grille faces the floor.
- Level the base plate inner panel. Mark the four drill holes.
- Drill holes (Ø 8 mm, min 50 mm deep).
- Apply sealing tape (10 mm) to the outside wall side and circumferentially on the base plate, flush with the sleeve opening and along the outer edge guide. Do not seal fixing holes.
- Insert wall anchors and screw the base plate to the wall anchors with 4 screws. Use insulation plugs/anchors for insulated walls or Simplex systems if needed (optional).
- Seal only the upper joint between the base plate and the outer wall with permanently elastic exterior sealant.
- Place the cover onto the base plate from above and pull it down until it hooks behind the base plate.
NOTICE: Improper sealing of the joint between the base plate and outer wall prevents cover fitting.
Installing Inner Panel ALD100
Requirements: Exterior wall completed and even, wall sleeve installed.
Steps:
- Slide the pre-assembled inner panel into the wall sleeve, ensuring the inVENTer logo is at the bottom right. Level the base plate inner panel.
- (Optional) Screw the inner panel to the inner wall using the 4 corner holes if it does not fit tightly.
- Pull the top edge of the cover forward to unhook it. The inner panel is fitted.
Technical Data
General Specifications
Feature | Value |
---|---|
Operating range [°C] | -20 – 50 |
Extract air/outdoor air | Without aggressive gases, dust and oils |
Reference air flow [m³/h] | 7 – 15 [Basic variant] 7 – 15 [Plus variant] |
Reference air flow [m³/h] | 14 – 22 [Basic variant] 14 – 22 [Plus variant] |
Standard sound level difference [dB] | 33 – 49 [Basic variant] 34 – 48 [Plus variant] |
Standard filter class ISO 16890 / EN 779:2012 | ISO Coarse / G1 |
Conformity |
Scope of Supply
Standard components are also available as spare parts. Contact your local distributor for accessories and spare parts. Refer to the separate accessories overview for more details.
Standard Components
Component | Product Number |
---|---|
aV100 ALD | 1002-0029 |
aV100 ALD Plus incl. WPH white, RAL 9016 | 1002-0030 |
aV100 ALD Plus incl. WPH grey, RAL 9006 | 1002-0031 |
aV100 ALD Plus incl. WPH anthracite, RAL 7016 | 1002-0045 |
aV100 ALD Plus incl. WPH special colours | 1002-0033 |
aV100 ALD Corner | 1002-0034 |
aV100 ALD Nordic | 1002-0046 |
External closure Basic variant / Plus: Weather protection hood incl. sealing tapes | |
Weather protection grille aV100, white - RAL 9010 | 1508-0096 |
Weather protection hood Flex aV100, white - RAL 9016 | 1508-0207 |
Weather protection hood Flex aV100, grey - RAL 9006 | 1508-0208 |
Weather protection hood Flex aV100, anthracite - RAL 7016 | 1508-0209 |
Weather protection hood Flex aV100, special colours | 1508-0210 |
Wall sleeve with Styrofoam discs and mounting wedges | |
Wall sleeve R-D103x495 | 1506-0099 |
Wall sleeve R-D103xdesired length | 1506-0131 |
Inner cover | |
Inner panel ALD 100, white | 3008-0085 |
Accessories
Component | Product Number |
---|---|
aV100 Wall mounting set | 1001-0159 |
Flimmer filter aV100 ALD | 1004-0165 |
Pollen filter aV100 ALD | 1004-0163 |
Dust filter aV100 ALD | 1004-0164 |
Simplex incl. WEH R-D103x495 | 1506-0107 |
Wall mounting block WEB D120 | 3008-0080 |
Troubleshooting
Fault | Possible Cause | Remedy |
---|---|---|
Air flow / volume | Air volume flow too low | Move the cover to a larger opening. |
Air volume flow too strong | Move the cover to a smaller opening for a short time. The inner panel must not be permanently closed. | |
Noises | Foreign body in the ventilation device | Remove the foreign body from the ventilation device. |
Warranty and Guarantee
Warranty
The warranty covers defects present at the time of purchase. Observe intended use to maintain warranty claims. Outside Germany, national warranty regulations apply. Contact your local dealer.
Guarantee
inVENTer GmbH provides a 5-year guarantee for the wall sleeve, covering premature product wear. For guarantee provisions, visit www.inventer.de/garantie. In case of claims, contact the dealer or factory representative. Send the complete unit back to the manufacturer. The warranty claim is an additional offer and does not affect applicable law.
Service
Complaints
Check delivery for completeness and damage upon receipt. Report missing items within 14 days to your supplier, dealer, or factory representative.
Accessories and Spare Parts
To order components, contact your dealer or factory representative.
Technical Customer Service
For technical advice, contact:
- Phone: +49(0)36427211-333
- Email: service@inventer.de
inVENTer GmbH
Ortsstraße 4a
D-07751 Löberschütz
www.inventer.eu
Subject to modifications. No liability for printing errors.
Product Number: 5012-0015
Version: 1.0 – 09/2022