Grundfos MGE 71, MGE 80, MGE 90

Installation and Operating Instructions

Declaration of Conformity

GB: EC declaration of conformity
Grundfos declares under its sole responsibility that the products MGE 71, MGE 80, and MGE 90 conform to Council directives on the approximation of laws for EC member states: Low Voltage Directive (2006/95/EC) (Standard: EN 61800-5-1:2007), EMC Directive (2004/108/EC) (Standard: EN 61800-3:2005), and R&TTE Directive (1999/5/EC) (Standard: ETSI EN 300 328 V1.7.1 (2006-10)). This declaration is valid when published as part of the Grundfos installation and operating instructions (publication number 98418360 0813).

CN: EC 产品合格声明书
We, Grundfos, declare under our sole responsibility that the products MGE 71, MGE 80, and MGE 90 conform to the following EU Council directives: Low Voltage Directive (2006/95/EC), EMC Directive (2004/108/EC), and R&TTE Directive (1999/5/EC). This EC declaration of conformity is only valid when published as part of the Grundfos installation and operating instructions (publication number 98418360 0813).

Bjerringbro, 6th March 2013
Jan Strandgaard
Technical Director
Grundfos Holding A/S
Poul Due Jensens Vej 7
8850 Bjerringbro, Denmark

Person authorised to compile technical file and empowered to sign the EC declaration of conformity.

1. Symbols used in this document

2. Abbreviations and definitions

Abbreviation Definition
AI Analog input.
AL Alarm, out of range at lower limit.
AO Analog output.
AU Alarm, out of range at upper limit.
CIM Communication interface module.
Current sinking The ability to draw current into the terminal and guide it towards GND in the internal circuitry.
Current sourcing The ability to push current out of the terminal and into an external load which must return it to GND.
DI Digital input.
DO Digital output.
ELCB Earth leakage circuit breaker.
FM Functional module.
GDS Grundfos Digital Sensor. Factory-fitted sensor in some Grundfos pumps.
GENIbus Proprietary Grundfos fieldbus standard.
GFCI Ground fault circuit interrupter.
GND Ground.
Grundfos Eye Status indicator light.
LIVE Low voltage with the risk of electric shock if the terminals are touched.
OC Open collector: Configurable open-collector output.
PE Protective earth.
PELV Protective extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, except earth faults in other circuits.
SELV Safety extra-low voltage. A voltage that cannot exceed ELV under normal conditions and under single-fault conditions, including earth faults in other circuits.

3. General description

Grundfos MGE 71, MGE 80, and MGE 90 are frequency-controlled permanent-magnet motors for single-phase or three-phase mains connection, incorporating a PI controller. They can be connected to an external sensor and setpoint signal for closed-loop control, or used in an open-loop system where the setpoint signal acts as a speed control signal. These motors are intended for machines with a square torque characteristic, such as ventilators and centrifugal pumps.

The motors feature a control panel available in various versions (see section 8. User interfaces). Detailed motor settings are made using the wireless Grundfos R100 remote control or Grundfos GO Remote. Important operating parameters can also be read via these devices.

The motors include a functional module, available in various versions with different inputs and outputs (see section 6.5 Functional modules). An optional Grundfos CIM module can be fitted for data transmission to external systems (e.g., BMS or SCADA) via fieldbus protocols.

3.1 Radio communication

This product features a class 1 radio module for remote control, usable in all EU member states without restrictions. For use in the USA and Canada, refer to page 35. Some product variants, particularly those sold in China and Korea, may not include a radio module.

The motor can communicate with the Grundfos GO Remote and other MGE motors of the same type via the built-in radio module. An external antenna may be required in some cases, and only Grundfos-approved antennas should be used, installed by an approved technician.

3.2 Battery

The FM 300 functional module contains a Li-ion battery compliant with the Battery Directive (2006/66/EC), free from mercury, lead, and cadmium.

4. Identification

The motor is identified by its nameplate, located on the side of the terminal box (see Fig. 1, pos. A). Figure 2 illustrates the nameplate layout, with numbered positions corresponding to the table below, detailing components such as type designation, product number, supply voltage, rated power, and manufacturer information.

Fig. 1 Nameplate location: Shows the physical location of the nameplate on the motor's terminal box.

Fig. 2 Nameplate, MGE motors: Depicts the nameplate with numbered fields indicating various motor specifications.

Pos. Description Pos. Description
1 Type designation 15 Grundfos company address
2 Product number 16 Country of manufacture
3 Drive-end bearing 17 Human Machine Interface type
4 Version number 18 CIM module type
5 Environmental type 19 Motor efficiency
6 Production code (year and week) 20 Maximum motor speed [min⁻¹]
7 Serial number 21 Maximum input current [A]
8 Supply voltage [V] 22 Mains frequency [Hz]
9 Rated power output [kW] 23 Enclosure class according to IEC 60034-5
10 Power board 24 Insulation class according to IEC 62114
11 Functional module type 25 Maximum ambient temperature [°C]
12 CE mark and approvals 26 Power factor
13 Part number of nameplate 27 Weight [kg]
14 Grundfos logo 28 Non-drive-end bearing

4.2 Type key

The type key provides a coded description of the motor's specifications. It includes codes for the motor unit type (e.g., complete motor, basic unit, kit), control type (MG for Grundfos, E for electronic control), frame size (71, 80, 90), foot size (S, M, L), stator core length (A, B, C, D), rated motor power (in kW for different speed ranges), maximum speed, shaft end diameter, flange version (foot-mounted, tapped-hole, free-hole), pitch circle diameter, model designation (single/three-phase), and version designation.

5. Mechanical installation

Warning: Installation and operation must comply with local regulations and accepted codes of good practice.

5.1 Handling

Warning: Observe local regulations for manual lifting or handling. Caution: Before lifting, note the motor's weight on the nameplate. Do not lift by the terminal box. Always use eyebolts if fitted, or lift with both hands.

5.2 Mounting

Secure the motor to a solid foundation using bolts through the flange or base plate holes. Note: Additional installation procedures may be required to maintain UL approval (see page 35).

5.3 Cable entries

The motor is equipped with four M20 screwed cable entries with blind plugs. Various cable glands are available as accessory kits from Grundfos.

5.4 Ensuring motor cooling

Note: To ensure sufficient cooling, maintain a minimum distance (D) of 50 mm between the fan cover end and any wall or fixed object, regardless of motor size (see Fig. 3).

Fig. 3 Minimum distance (D) from the motor to a wall or other fixed objects: Illustrates the required clearance for cooling.

5.5 Outdoor installation

For outdoor installations, a suitable cover is required to prevent condensation on electronic components (see Fig. 4). Ensure the cover does not expose the motor to direct sunlight, rain, or snow. Grundfos does not supply covers; custom-built covers are recommended. In high humidity areas, enable the built-in standstill heating function (see page 27).

Fig. 4 Examples of covers (not supplied by Grundfos): Shows types of protective covers.

5.6 Drain holes

In moist environments or high humidity, open the bottom drain hole to allow self-venting and escape of water/humid air, which lowers the enclosure class. A plugged drain hole is located on the drive side; the flange can be rotated 90° or 180°.

Fig. 5 Drain holes: Shows different drain hole configurations (B3, B14, B5).

6. Electrical installation

Perform electrical connections according to local regulations. Verify supply voltage and frequency against the nameplate. Warning: Ensure the power supply is switched off for at least 5 minutes before making connections in the terminal box and prevent accidental power-on. The motor must be earthed and protected against indirect contact as per local regulations. Damaged power supply cables must be replaced by the manufacturer, service partner, or qualified personnel. Note: The user or installer is responsible for correct earthing and protection according to local regulations; all operations must be performed by a qualified electrician.

6.1 Protection against electric shock, indirect contact

Warning: The motor must be earthed and protected against indirect contact according to local regulations. Protective-earth conductors must be marked yellow/green (PE) or yellow/green/blue (PEN).

6.1.1 Protection against mains voltage transients

The motor is protected against mains voltage transients per EN 61800-3.

6.1.2 Motor protection

No external motor protection is required. The motor has built-in thermal protection against slow overloading and blocking.

6.2 Cable requirements

6.2.1 Cable size
6.2.2 Conductors

6.3 Mains supply

6.3.1 Single-phase supply voltage

Available voltages: 1 x 200-240 V (-10%/+10%, 50/60 Hz, PE) or 1 x 90-240 V (-10%/+10%, 50/60 Hz, PE or 30-300 VDC from renewable sources). Check nameplate for correct voltage and frequency. Note: For IT networks, use a dedicated IT network motor. Contact Grundfos. Terminal box wires should be short, with the earth conductor being the last to disconnect if the cable is pulled. Refer to section 15.1 for maximum backup fuse size.

Fig. 6 Example of a mains-connected motor with mains switch, backup fuse and additional protection: Illustrates single-phase mains connection for MGE 71 and MGE 80.

Fig. 7 Mains connection, single-phase motors: Shows the wiring diagram for single-phase motors.

6.3.2 Three-phase supply voltage

Available voltage: 3 x 380-500 V (-10%/+10%, 50/60 Hz, PE). Caution: Ensure terminal blocks L1, L2, L3 are seated correctly. Note: Corner grounding is not allowed for supply voltages above 3 x 480 V, 50/60 Hz. Check nameplate for correct voltage and frequency. Note: For IT networks, use a dedicated IT network motor. Contact Grundfos. Terminal box wires should be short, with the earth conductor being the last to disconnect. Refer to section 16.1 for maximum backup fuse size.

Fig. 8 Example of a mains-connected motor with mains switch, backup fuses and additional protection: Illustrates three-phase mains connection for MGE 90.

Fig. 9 Mains connection, three-phase motors: Shows the wiring diagram for three-phase motors.

6.4 Additional protection

6.4.1 Single-phase motors

If an ELCB or GFCI is used, it must be marked with the ELCB (GFCI) symbol. Note: Consider total leakage current of all equipment. Motor leakage current is in section 15.2.

6.4.2 Motors supplied from a renewable-energy source

Applies to motors designed for renewable energy sources (1 x 90-240 V or 30-300 VDC). The motor has overvoltage and undervoltage protection, with automatic restart when voltage is within range. It is protected against transients per EN 61800-3. External lightning protection is recommended in high lightning intensity areas.

6.4.3 Three-phase motors

If an ELCB or GFCI is used, it must be Type B, suitable for leakage and DC fault currents. The circuit breaker or interrupter must be marked with the ELCB (GFCI) symbol. Note: Consider total leakage current. Motor leakage current is in section 16.2.

Protection against phase unbalance: Requires power supply quality per IEC 60146-1-1, class C.

6.5 Functional modules

Various functional modules are available (FM 100, FM 200, FM 300) depending on application needs for inputs and outputs.

6.6 Connection terminals on functional modules

Descriptions and terminal overviews apply to both single- and three-phase motors. Tightening torques are in section 'Torques' (page 33).

6.6.1 Basic functional module (FM 100)

The FM 100 provides essential inputs for closed/open-loop operation and GENIbus communication. It features analog voltage input, digital inputs (or one digital input/one open-collector output), and GENIbus connection (see Fig. 10). Note: Digital input 1 is factory-set for start/stop; a jumper between terminals 2 and 6 can be removed for other functions. Note: Wires for connection groups must be separated by reinforced insulation.

Inputs and outputs are internally separated and supplied by SELV for electric shock protection. Mains supply terminals (N, PE, L/L1, L2, L3, PE) require galvanically safe separation per EN 61800-5-1.

Fig. 10 Connection terminals, FM 100: Diagram showing terminal layout and connections for the FM 100 module.

Terminal Type Function
10 DI3/OC1 Digital input/output, configurable. Open collector: Max. 24 V resistive or inductive.
4 AI1 Analog input: 0.5-3.5 V / 0-5 V / 0-10 V
2 DI1 Digital input, configurable
5 +5 V Supply to potentiometer and sensor
6 GND Ground
A GENIbus, A GENIbus, A (+)
Y GENIbus, Y GENIbus, GND
B GENIbus, B GENIbus, B (-)
6.6.2 Standard functional module (FM 200)

The FM 200 offers more inputs/outputs for demanding applications. Connections include analog inputs, digital inputs/outputs, Grundfos Digital Sensor, signal relay outputs, and GENIbus (see Fig. 11). Note: Digital input 1 function and wire separation notes apply as for FM 100. Inputs/outputs are separated and SELV-protected. Signal relays provide LIVE or SELV outputs. Mains supply terminals require galvanically safe separation.

Fig. 11 Connection terminals, FM 200: Diagram showing terminal layout and connections for the FM 200 module.

6.6.3 Advanced functional module (FM 300)

The FM 300 provides extensive inputs/outputs for advanced applications. Connections include three analog inputs, one analog output, two dedicated digital inputs, two configurable digital inputs/open-collector outputs, Grundfos Digital Sensor input/output, two Pt100/1000 inputs, LiqTec sensor inputs, two signal relay outputs, and GENIbus (see Fig. 12). Note: Digital input 1 function and wire separation notes apply as for FM 100. Inputs/outputs are separated and SELV-protected. Signal relays provide LIVE or SELV outputs. Mains supply terminals require galvanically safe separation.

Fig. 12 Connection terminals, FM 300: Diagram showing terminal layout and connections for the FM 300 module.

6.7 Signal cables

Use screened cables (min. 0.5 mm², max. 1.5 mm²) for external switches, digital inputs, setpoint, and sensor signals. Connect screens to the frame at both ends, close to terminals. Ensure frame connection screws are tightened. Keep terminal box wires short.

6.8 Bus connection cable

6.8.1 New installations

Use a screened 3-core cable (min. 0.5 mm², max. 1.5 mm²) for bus connection. Connect the screen to the cable clamp if present; otherwise, leave it unconnected.

Fig. 14 Connection with screened 3-core cable: Illustrates connecting a screened 3-core cable.

6.8.2 Replacing an existing motor

For existing 2-core screened cables, connect as shown in Fig. 15. For 3-core screened cables, follow new installation instructions.

Fig. 15 Connection with screened 2-core cable: Illustrates connecting a screened 2-core cable.

7. Operating conditions

7.1 Maximum number of starts and stops

Maximum four starts/stops per hour via power supply. Motor starts approx. 5 seconds after power-on. For higher rates, use external start/stop input. External on/off switch provides immediate start.

7.2 Ambient temperature

7.3 Installation altitude

Caution: Maximum installation altitude is 2000 metres above sea level. Motors installed up to 1000 m can be loaded 100%. Above 1000 m, output (P2) must be derated due to lower air density and cooling effect (see Fig. 16).

Fig. 16 Derating of motor output (P2) in relation to altitude above sea level: Graph showing output reduction versus altitude.

7.4 Air humidity

Maximum air humidity is 95%. In high humidity (>85%), open drain holes (see section 5.6).

7.5 Motor cooling

Ensure adequate cooling by positioning the motor correctly (see section 5.4). Cooling air temperature must not exceed 50 °C. Keep cooling fins and fan blades clean.

8. User interfaces

Warning: Product surfaces may be hot; touch buttons only to avoid burns.

Motor settings are made via control panels (Basic, Standard) or remote controls (R100, GO Remote). Settings are stored when power is off.

8.1 Basic control panel

Features the Grundfos Eye (status indicator) and enables radio communication. Settings are made via R100 or GO Remote. Resetting alarms can be done via digital input, power cycle, external input, R100, or GO Remote.

Fig. 17 Basic control panel: Shows the basic control panel with Grundfos Eye and radio communication indicator.

8.2 Standard control panel

Includes Grundfos Eye, light fields for setpoint indication, setpoint adjustment buttons, radio communication enablement, and Start/Stop buttons. The Start button initiates operation if no higher priority functions are active. The Stop button halts the motor.

Fig. 18 Standard control panel: Shows the standard control panel with Grundfos Eye, setpoint controls, radio communication, and Start/Stop buttons.

8.2.1 Setpoint setting

Set desired setpoint using +/- buttons. Green light fields indicate the setpoint. In controlled-operation mode, setpoint corresponds to sensor range (e.g., 3 bar from 0-6 bar range, as shown in Fig. 19). In uncontrolled-operation mode, output is between min/max speed (Fig. 20).

Fig. 19 Setpoint set to 3 bar, pressure-control mode: Illustrates setpoint indication on the control panel.

Fig. 20 Motor in uncontrolled-operation mode: Shows the speed range in uncontrolled mode.

Setting to max. speed: Press to cycle to max speed (top light flashes), then press for 3 seconds. Press to return to desired setpoint (Fig. 21).

Fig. 21 Max. speed duty: Indicates max speed setting.

Setting to min. speed: Press to cycle to min speed (bottom light flashes), then press for 3 seconds. Press to return to desired setpoint (Fig. 22).

Fig. 22 Min. speed duty: Indicates min speed setting.

8.2.2 Start/stop of motor

Use the Stop button (text illuminates when stopped) or continuous press. Start using the Start button or continuous press. Motor can also be stopped via R100, GO Remote, or 'External stop' digital input.

8.2.3 Resetting of alarms and warnings

Fault indications can be reset via digital input, pressing the motor buttons (if not locked), power cycling, or using R100/GO Remote.

8.3 Changing the position of the control panel

The control panel can be rotated 180°. Follow these steps: 1. Loosen four screws (TX25) on the terminal box cover. 2. Remove the terminal box cover. 3. Press and hold locking tabs (A) while lifting the plastic cover (B). 4. Turn the plastic cover 180° (do not twist cable more than 90°). 5. Re-position the plastic cover on pins (C), ensuring tabs (A) align. 6. Fit the terminal box cover, rotated 180°, aligning buttons. Tighten screws to 5 Nm.

Fig. 23 Loosening the screws: Shows screw removal.

Fig. 24 Removing the terminal box cover: Shows cover removal.

Fig. 25 Lifting the plastic cover: Illustrates lifting the cover.

Fig. 26 Turning the plastic cover: Shows the 180° rotation.

Fig. 27 Re-positioning the plastic cover: Details correct placement of the cover.

Fig. 28 Fitting the terminal box cover: Shows refitting the cover.

8.4 R100 remote control

The motor supports wireless communication with the Grundfos R100 remote control. Point the R100 at the control panel; a green flashing light on the Grundfos Eye indicates communication. The R100 offers extended setting and status display capabilities through four menus: GENERAL, OPERATION, STATUS, and INSTALLATION.

Fig. 29 R100 communicating with the motor via infrared light: Depicts the remote control interaction.

8.4.1 R100 menu structure

Outlines the structure of the R100 menus, including options for GENERAL settings, OPERATION parameters (Setpoint, Mode, Speed, Alarms), STATUS displays (Setpoint, Mode, Controlled Value, Inputs, Speed, Power, etc.), and INSTALLATION settings (Control Mode, Controller, Relays, Inputs, etc.).

8.4.2 OPERATION menu

Displays include Setpoint, Operating mode, Manual speed, and Alarm status. Various symbols indicate motor operating conditions like acceleration, deceleration, and stop. Open-loop operation sets speed as a percentage of maximum. Closed-loop operation uses sensor values. Figures illustrate setpoint relations and examples.

Alarm: Lists possible alarms with fault codes (e.g., Blocked pump, Overload, High temperature). Faults can be reset if the cause is resolved.

8.4.3 STATUS menu

This menu displays status information without allowing changes. Values reflect the last communication. Updating requires pressing [OK]. Displays include Actual setpoint/external setpoint, Operating mode, and Actual controlled value. Tolerances are provided for displayed values.

8.4.4 INSTALLATION menu

Allows setting Control mode (Closed loop, Open loop) and PI controller parameters (gain Kp, integral-action time Ti). Instructions are provided for setting the PI controller for optimal performance. Inverse control is also supported.

Signal relay 1 and 2: Can be configured for various incidents (Ready, Operation, Alarm, Warning, Limit exceeded, Running, Not active). Compatibility depends on the functional module.

Buttons on motor: Can be set to Active or Not active.

Number: A number (1-64) can be allocated to the motor for bus communication.

Radio communication

Wireless radio communication can be enabled or disabled. Digital input 1 and 2 can be set to various functions, including External stop, External fault, Alarm resetting, Reversing, Max/Min speed. Digital input/output 3 and 4 can function as digital input or output.

Analog input 1, 2 and 3, Function

Analog inputs can be set to functions like Not active, Feedback sensor, External setpoint influence, or Other function. Compatibility depends on the functional module.

Analog input 1, 2 and 3, Measured parameter

Analog inputs can measure various parameters (Pressure, Flow rate, Temperature, etc.) with selectable units and sensor ranges. Compatibility depends on the functional module.

Pt100/1000 input 1 and 2, Function

Pt100/1000 inputs can be set to functions like Not active, Feedback sensor, External setpoint influence, or Other function. Compatibility depends on the functional module.

Operating range

Sets the minimum and maximum speed within a defined range. The operating range is between user-set min and max speeds (see Fig. 30).

Fig. 30 Example of min. and max. settings: Illustrates operating range settings.

Ramps

Determines acceleration and deceleration times (0.1 to 300 s) for open-loop operation. Short deceleration times may be affected by load and inertia.

Direction of rotation

Selectable as Clockwise or Anti-clockwise. Applies when the reversing digital input is not active.

Skip band 1 & 2

Allows skipping specific speed bands to avoid noise or vibrations. Select '-' if no skip band is required.

Motor bearing monitoring

Monitors bearing mileage and provides a warning when replacement is due. The counter continues even if the function is set to 'Not active'.

Standstill heating

Can be set to Active or Not active. When Active, AC voltage is applied to motor windings to prevent condensation.

8.5 Grundfos GO Remote

The motor supports wireless radio or infrared communication with the Grundfos GO Remote app. The app allows function setting, status overview, technical information, and parameter access. It offers three mobile interfaces (MI) for iPod, iPhone, and Android/iOS devices.

Fig. 31 Grundfos GO Remote communicating with the motor via radio or infrared light: Shows the remote communication setup.

8.5.1 Communication

Communication is established via radio (up to 30m, requires enabling on panel) or infrared (point at control panel). The Grundfos Eye indicator light flashes green during communication.

8.5.2 Navigation

Navigation is done via the dashboard. The dashboard displays connection status, alarms, product information, control source, setpoint, and operating mode. The Tool bar provides access to Help, Documentation, Report, and Update functions.

Fig. 32 Example of dashboard: Illustrates the GO Remote dashboard interface.

9. External setpoint signal

Allows remote setpoint adjustment via an analog signal transmitter. Signal type (voltage/current) must be selected via R100 or GO Remote. In open-loop, any controller can be used. In closed-loop, the setpoint is within the sensor's measuring range or set on the motor/remote (see Fig. 33).

Fig. 33 Relation between the actual setpoint and the external setpoint signal in controlled-operation mode: Explains how external signals affect the setpoint.

Fig. 34 Relation between the actual setpoint and the external setpoint signal in uncontrolled-operation mode: Explains setpoint relations in uncontrolled mode.

10. Bus signal

Enables serial communication via RS-485 using the Grundfos GENIbus protocol for connection to building management systems or external control systems. Allows remote parameter setting and provides status information. Note: Using a bus signal may reduce available settings on R100/GO Remote.

11. Priority of settings

The motor operates based on the highest priority setting. A priority table lists the order for Stop, Manual, Max speed, Min speed, and Start commands from different sources (buttons, R100/GO Remote, digital input, bus). Bus commands can overrule others; if bus communication is interrupted, the motor reverts to the previous setting.

12. Grundfos Eye

Indicates motor operating condition via lights on the control panel. The table describes various light patterns (no lights, green rotating/steady, yellow rotating/steady, red flashing) and their meanings (Power off, Motor running/stopped, Warning, Alarm, Remote control status).

13. Signal relays

Two potential-free signal outputs can be set for Operation, Running, Ready, Alarm, or Warning. The table shows contact positions (Common, Normally Open, Normally Closed) for different Grundfos Eye indications and operating modes.

14. Megging

Caution: Megging is not allowed for installations with MGE motors as it may damage the built-in electronics.

15. Technical data, single-phase motors

15.1 Supply voltage

Available voltages: 1 x 200-240 V or 1 x 90-240 V (also 30-300 VDC from renewable sources). Recommended fuse sizes are provided based on motor size (kW).

15.2 Leakage current

Earth leakage current is < 3.5 mA (AC supply) or < 10 mA (DC supply), measured per EN 61800-5-1:2007.

16. Technical data, three-phase motors

16.1 Supply voltage

Available voltage: 3 x 380-500 V. Recommended fuse sizes are provided based on motor size (kW).

16.2 Leakage current

Leakage current is < 3.5 mA (for supply voltage < 400 V) or < 5 mA (for supply voltage > 400 V), measured per EN 61800-5-1:2007.

17. Inputs/outputs

Ground reference (GND): All voltages and currents refer to GND.

Absolute maximum voltage and current limits: Exceeding these limits can reduce reliability and motor life.

18. Other technical data

EMC (electromagnetic compatibility)

Complies with EN 61800-3 for residential (CISPR 11, class B, group 1) and industrial areas (CISPR 11, class A, group 1). Contact Grundfos for details.

Enclosure class

Standard: IP55 (IEC 34-5). Optional: IP66 (IEC 34-5).

Insulation class

F (IEC 85).

Torques

Table lists maximum tightening torques for various terminals based on thread size.

18.1 Sound pressure level

Table provides sound pressure levels (ISO 3743, dB(A)) for 1-phase and 3-phase motors across different motor sizes (kW), speeds (min⁻¹), and stated speeds.

19. Disposal

Dispose of the product and its parts in an environmentally sound manner using public or private waste collection services. If not possible, contact the nearest Grundfos company or service workshop. Dispose of waste batteries through national collective schemes. Contact local Grundfos company if in doubt.

Appendix

1. Installation in the USA and Canada

Note: Follow additional installation instructions to maintain cURus approval. UL approval is according to UL 1004-1.

1.1 Electrical codes

Complies with Canadian Electrical Code and US National Electrical Code. Tested according to national standards for Electronically Protected Motors (CSA 22.2 100.04:2009 for Canada, UL 1004-1:2011 for USA).

1.2 Radio communication

For USA: Complies with FCC Part 15 and IC RSS210. Subject to two conditions: no harmful interference caused, and acceptance of any interference. For Canada: Similar compliance statements.

1.3 Identification numbers

Provides FCC ID (OG3-RADIOM01-2G4) for USA and IC numbers (10447A-RA2G4M01) for Canada.

Location of identification numbers: Figures 1 and 2 show where identification numbers are located.

1.4 Electrical connection
1.4.1 Conductors

Use 140/167 °F (60/75 °C) copper conductors only.

1.4.2 Torques

Maximum tightening torques are listed in section 'Torques' (page 33).

1.4.3 Line reactors

Maximum line reactor size must not exceed 1.5 mH.

1.4.4 Fuse size/circuit breaker

For short circuits, the supply must not exceed 5000 RMS symmetrical amperes, 600 V maximum. Fuse sizes and circuit breaker types are specified for motor sizes 0.25 to 2.2 kW. Motors up to 2.2 kW require class K5 UR fuses. Circuit breakers must be 'inverse time' type, rated for 480 V, with appropriate interrupting rating.

1.4.5 Overload protection

Internal overload protection is 102% of full-load current.

Grundfos Companies

Lists Grundfos company contact information for various countries worldwide.

PDF preview unavailable. Download the PDF instead.

Grundfosliterature-5235403 FrameMaker 10.0.2 Acrobat Distiller 10.1.12 (Windows)

Related Documents

Preview Grundfos MG Electric Motors: Installation and Operating Instructions
Comprehensive guide for the installation, operation, and maintenance of Grundfos MG series electric motors. Covers technical specifications, safety precautions, electrical and mechanical installation, troubleshooting, and disposal.
Preview Grundfos MG Motor Installation and Operating Instructions
Comprehensive guide for the installation and operation of Grundfos MG motors, covering safety, technical specifications, maintenance, and troubleshooting.
Preview Grundfos MS, MMS Submersible Motors: Installation and Operating Instructions
Comprehensive installation and operating instructions for Grundfos MS and MMS submersible motors, covering delivery, storage, general description, preparation, electrical connection, installation, maintenance, fault finding, and cable sizing.
Preview Grundfos SCALA2 3-45 A Pressure Boosting Pump Specifications and Features
Detailed specifications and features of the Grundfos SCALA2 3-45 A, a fully integrated, self-priming, compact waterworks for pressure boosting in domestic applications. Includes installation steps, technical data, and material information.
Preview Grundfos LiqTec 200-240 V Installation and Operating Manual
Comprehensive guide for installing and operating the Grundfos LiqTec 200-240 V pump protection unit, covering features, electrical connections, calibration, and technical specifications.
Preview Grundfos MG Motors: Installation and Operating Instructions
Comprehensive guide for the installation, operation, and maintenance of Grundfos MG series electric motors, covering technical specifications, safety, and troubleshooting.
Preview Grundfos TP, TPD, TPE, TPE2, TPE2 D, TPE3, TPE3 D Series In-line Circulator Pumps Data Booklet
Comprehensive data booklet for Grundfos TP, TPD, TPE, TPE2, TPE2 D, TPE3, TPE3 D in-line circulator pumps. Details performance, applications, installation, controls, and technical specifications for HVAC and industrial fluid handling.
Preview Grundfos SQ/SQE Data Book: Features, Applications, and Technical Specifications
Comprehensive data book for Grundfos SQ/SQE submersible pumps, detailing features, benefits, applications, communication systems (CU300, R100), performance data, technical specifications, dimensions, weights, and materials of construction.