KMC BAC-9300A Series BACnet Unitary Controllers (B-BC)
This document provides information on the KMC Conquest™ BAC-9300A series controllers, designed for unitary and terminal equipment operation. These BACnet Building Controllers offer integrated alarming, scheduling, and trending, making them powerful edge devices for modern smart building ecosystems.
Features and Applications
The controllers come with factory-supplied programming for common unitary applications and feature a menu-driven setup using an STE-9000 series digital sensor. Configuration can also be done via NFC using the KMC Connect Lite™ app or through an HTML5-compatible web browser for Ethernet-enabled BAC-93x1ACE models. For advanced customization, KMC Connect™ software and the KMC Converge™ module for Niagara Workbench enable full programmability and custom graphical web page creation.
These controllers are suitable for various unitary equipment, including:
- Air handling units (AHU)
- Chilled beams
- Constant air volume (CAV) with external actuator
- Fan coil units (FCU)
- Heat pump units (HPU)
- Roof top units (RTU)
- Unit ventilators
- Variable air volume (VAV) with external actuator
Note: Some applications may require custom programming.
Models and Specifications
APPLICATIONS | INPUTS | OUTPUTS | FEATURES | MODEL | |||
---|---|---|---|---|---|---|---|
RTU, HPU, FCU, AHU, and unit ventilator | 1 opt. air pressure sensor and 8 (total) standard: 2 analog (temp. sensor port), 6 universal inputs (software configurable as analog, binary, or accumulator on terminals) | 10 total: 6 triacs (binary), 4 universal (software configurable as analog or binary) | Air Pressure Sensor (Input) | Real Time Clock (RTC) | Ethernet Port | MS/TP Port | |
VAV/CAV (with external tri-state actuator), RTU/HPU static pressure monitoring/control | ✔️ | ✔️ | ✔️ | ✔️ | BAC-9301A | ||
✔️ | ✔️ | ✔️ | ✔️ | BAC-9301AC | |||
✔️ | ✔️ | ✔️ | ✔️ | BAC-9301ACE | |||
✔️ | ✔️ | ✔️ | ✔️ | BAC-9311A | |||
✔️ | ✔️ | ✔️ | ✔️ | BAC-9311AC | |||
✔️ | ✔️ | ✔️ | ✔️ | BAC-9311ACE |
Dimensions
Inches | mm | |
---|---|---|
A | 6.744 | 171 |
B | 5.500 | 140 |
C | 5.000 | 127 |
D | 6.000 | 152 |
E | 1.500 | 38 |
F | 6.279 | 159 |
Terminal Color Code
Black | 24 VAC/VDC Power |
Green | Inputs and Outputs |
Inputs and Outputs Details
Inputs, Universal (6 on Terminal Blocks)
- Configurable as analog, binary, or accumulator objects.
- Supports 1K and 10K ohm sensors, 0-12 VDC, or 0-20 mA inputs.
- 16-bit analog-to-digital conversion resolution.
- Overvoltage protection (24 VAC, continuous).
- Uses 12-24 AWG copper wire.
Input, Dedicated Room Sensor Port
- Modular connector for STE-9xx1 series digital wall sensors or STE-6010/6014/6017 analog temperature sensors.
- Uses standard Ethernet patch cable up to 150 feet (45 meters).
Input, Integrated Air Pressure Sensor (BAC-9311ACE)
- Pressure range: 0 to 2" wc (0 to 500 Pa).
- Sensor accuracy: ±4.5% of reading or 0.0008" wc (0.2 Pa) at near zero, whichever is greater. Internally linearized and temperature compensated.
- Connections: Barbed for 1/4 inch FR (Flame Retardant) tubing.
Outputs, Universal (4 on Terminal Blocks)
- Configurable as analog (0 to 12 VDC) or binary object (0 or 12 VDC, on/off).
- Each short-circuit protected output can drive up to 100 mA (at 0-12 VDC) or 100 mA total for all outputs.
- 12-bit digital-to-analog conversion resolution.
- Uses 12-24 AWG copper wire.
Outputs, Triac (6 Binary)
- Optically isolated zero-crossing triac output configured as a binary object.
- Maximum switching 24 VAC at 1.0 A per output; maximum total for controller is 3.0 A.
- Uses 12-24 AWG copper wire.
Communication Ports
- MS/TP (optional): One EIA-485 port, supporting various baud rates up to 115.2 kilobaud. Maximum length up to 4,000 feet (1,200 meters) with 18 AWG shielded, twisted-pair cable. Repeaters can be used for longer distances.
- Ethernet (optional): Two 10/100BaseT Ethernet connectors for BACnet IP, Foreign Device, and Ethernet 802.3. Supports segmentation up to 328 ft (100 m) between controllers using T568B Category 5 or better cable.
- NFC: Near Field Communication up to 1 inch (2.54 cm) from the top of the enclosure.
- Room sensor: Modular STE connection jack for STE-9000 series digital sensors and STE-6010/6014/6017 analog sensors.
Configurability
OBJECTS* | MAXIMUM # |
---|---|
Inputs and Outputs | |
Analog, binary, or accumulator input | 8 for BAC-9301, 9 for BAC-9311 |
Analog or binary output | 10 |
Values | |
Analog value | 120 |
Binary value | 80 |
Multi-state value | 40 |
Program and Control | |
Program (Control Basic) | 10 |
PID loop | 10 |
Schedules | |
Schedule | 2 |
Calendar | 1 |
Logs | |
Trend log | 20 |
Trend log multiple (must be created) | 4 (default 0) |
Alarms and Events | |
Notification class | 5 |
Event enrollment | 40 |
Tables | |
Input tables | 20 |
Control Basic tables | 20 |
*Configuration allows creation and deletion of objects (maximum number of objects shown). The number and configuration of default objects depends on the selected application.
Installation
Power
- Supply voltage: 24 VAC (50/60 Hz) or 24 VDC; –15%, +20%; Class 2 only; non-supervised.
- Required power: 8 VA, plus external loads.
- Wire size: 12-24 AWG, copper, in a removable screw terminal block.
Enclosure and Mounting
- Weight: 14 ounces (0.4 kg).
- Case material: Green and black flame retardant plastic.
- Mounting: Direct mounting to panels or on DIN rails.
Environmental Limits
- Operating: 32 to 120° F (0 to 49° C).
- Shipping: −40 to 160° F (−40 to 71° C).
- Humidity: 0 to 95% relative humidity (non-condensing).
Warranty, Protocol, and Approvals
Warranty
- KMC Limited Warranty: 5 years (from mfg. date code).
BACnet Protocol
- Standard: Meets or exceeds the specifications in ANSI/ASHRAE BACnet Standard 135-2010 for Building Controllers.
- Type: BTL-certified as a B-BC controller type.
Regulatory Approvals
- UL: UL 916 Energy Management Equipment listed.
- BTL: BACnet Testing Laboratory listed as Building Controller (B-BC) (pending).
- RoHS 2: RoHS 2 compliant.
- FCC: FCC Class A, Part 15, Subpart B and complies with Canadian ICES-003 Class A.
Hardware Features
Processor, Memory, and Clock
- Processor: 32-bit ARM® Cortex-M4.
- Memory: Programs and configuration parameters stored in nonvolatile memory; auto restart on power failure.
- RTC: Real time clock with capacitor power backup for 72 hours (“C” model only) for network time synchronization or full stand-alone operation.
Indicators and Isolation
- LED indicators: Power/status and Ethernet status.
Accessories
- Network Communications: BAC-5051AE (BACnet router), HPO-0055 (Replacement network bulb assembly), HPO-5551 (Router technician cable kit), HPO-9003 (NFC Bluetooth/USB module), HSO-9001 (Ethernet patch cable, 50 feet), HSO-9011 (Ethernet patch cable, 50 feet, plenum rated), HSO-9012 (Ethernet patch cable, 75 feet, plenum rated).
- Actuators: MEP-4xxx (25 to 90 in-lb., fail-safe and non-fail-safe), MEP-7xxx (180 and 320 in-lb., fail-safe and non-fail-safe).
- Differential Air Pressure Sensors: SSS-1012, SSS-1013, SSS-1014, SSS-1015 (various lengths).
- Miscellaneous Hardware: HCO-1103, HCO-1035, HCO-1036 (Steel control enclosures), SP-001 (Screwdriver), HPO-9901 (Controller replacement parts kit).
Room Sensors
Room Sensors, Analog
- STE-6010W10 (Temperature sensor, white)
- STE-6014W10 (Sensor with rotary setpoint dial, white)
- STE-6017W10 (Sensor with rotary setpoint dial and override button, white)
- HPO-9005 (Room sensor adapter for using other sensors)
Room Sensors, Digital (LCD Display)
- STE-9000 Series (KMC Conquest NetSensor digital room temperature sensors)
- HPO-9001 (NetSensor distribution module)
Sensors, Miscellaneous
- STE-1405 (DAT sensor)
- STE-1451 (OAT sensor)
Transformers, 120 to 24 VAC
- XEE-6111-050 (50 VA, single-hub)
- XEE-6112-050 (50 VA, dual-hub)
- XEE-6112-100 (96 VA, dual-hub, approved for smoke control applications)
Sample Installation
The diagram illustrates a typical installation connecting the BAC-9311ACE controller with an Air Pressure Sensor, STE-9xx1 NetSensor, and a BAC-5051AE Router. It also shows configuration via NFC-enabled smartphone and communication with other network devices and remote monitoring.
Diagram Description
The diagram shows a KMC BAC-9311ACE controller connected to an Air Pressure Sensor (BAC-9311ACE). The controller has 4 Universal and 6 Triac Outputs. It also connects to an STE-9xx1 NetSensor via a modular connector, supporting up to 6 sensors (to terminal blocks). The setup includes configuration via an NFC-Enabled Smart Phone. A BAC-5051AE Router is shown providing quick, temporary network access through a computer data port, connecting to other network devices and remote monitoring.
Support and Resources
For more information about installation and operation, refer to the following documents:
- BAC-9300 Series Controller Installation Guide
- KMC Conquest Controller Application Guide
- KMC Conquest Wiring: BAC-9300 Series Controllers (Video)
- Smoke Control Manual for KMC Conquest Systems
KMC Controls provides additional resources for installation, configuration, application, operation, programming, and upgrading on their website at www.kmccontrols.com. Users can log in to access available files.
Feedback: KMC values feedback to improve their documents. A link is provided to take a 3-minute survey.