KMC BAC-9000A Series BACnet VAV Controller-Actuators (B-BC)
Description
KMC Conquest™ BAC-9000A series controller-actuators are designed to operate VAV (Variable Air Volume) terminal units. The integrated alarming, scheduling, and trending enable these BACnet Building Controllers to be powerful edge devices for the modern smart building ecosystem.
With integrated actuators, internal air pressure sensors, and other powerful features, they are ideal for new installations and upgrades of less-efficient equipment. They easily mount to terminal boxes by securing a “V” clamp on the shaft and securing a single-screw anti-rotation bracket.
The factory-supplied programming covers common VAV applications. The controllers feature simple, menu-driven setup choices using an STE-9000 series digital sensor, which can be installed permanently as the room sensor or used temporarily as a technician's service tool.
Alternately, quick configuration of controller properties can be done using NFC (Near Field Communication) from a smart phone, tablet, or computer (using KMC Connect Lite™ app) while the controller is unpowered. For demanding building automation custom requirements, these controllers are also fully programmable. Custom configuration and programming, with wizards for application programming selection/configuration, are enabled by KMC Connect™ software and the KMC Converge™ module for Niagara Workbench.
KMC Converge and TotalControl™ software additionally provide the capability of creating custom graphical web pages (hosted on a remote web server) to use as a custom user-interface for the controllers.
Applications
Application options include:
- Pressure independent or dependent VAV
- Cooling only and with changeover
- Staged, modulated, floating, or time-proportional reheat
- Series or parallel fan control
- Dual duct (with TSP-8003 actuators)
- CAV (Constant Air Volume)
For installations with a BACnet building automation system, these easily integrated controllers signal demands for higher static duct pressure, cooler or warmer supply air, and other diagnostics for AHU optimization. (See Sample Installation on page 6.)
Models and Features
APPLICATIONS | INPUTS | OUTPUTS | Air Pressure Sensor | Real Time Clock | MS/TP | Ethernet | MODEL |
---|---|---|---|---|---|---|---|
Pressure-independent VAV, cooling/heating with fan and reheat; CAV | 8 total:
| 9 total:
| ✔️ | ✔️ | ✔️ | ✔️ | BAC-9001A |
Pressure-dependent VAV | ✔️ | ✔️ | ✔️ | ✔️ | BAC-9001ACE | ||
✔️ | BAC-9021A |
Specifications
Dimensions
A | 7.605 inches (193 mm) |
B | 4.374 inches (111 mm) |
C | 0.830 inches (21 mm) |
D | 2.150 inches (55 mm) |
E | 5.891 inches (150 mm) |
Terminal Color Code
Black | 24 VAC Power |
Gray | MS/TP Communications |
Green | Inputs and Outputs |
Inputs, Universal (4 on Terminal Blocks)
- Configurable as: analog, binary, or accumulator objects
- Termination: 1K and 10K ohm sensors, 0-12 VDC, or 0-20 mA (without need for an external resistor)
- Resolution: 16-bit analog-to-digital conversion
- Protection: Overvoltage protection (24 VAC, continuous)
- Wire size: 12-24 AWG, copper, in removable screw terminal blocks
Input, Integrated Air Pressure Sensor (optional)
- Pressure range: 0 to 2" wc (0 to 500 Pa)
- Sensor accuracy: ±4.5% of the reading or (when near zero) 0.0008" wc (0.2 Pa), whichever is greater (@ 25° C); internally linearized and temperature compensated
- Connections: Barbed for 1/4 inch FR (Flame Retardant) tubing
Input, Dedicated Room Sensor Port
- Connector: Modular connector for STE-9xx1 series digital wall sensors or STE-6010/6014/6017 analog temperature sensors
- Cable: Uses standard Ethernet patch cable up to 150 feet (45 meters)
Outputs, Universal (3 on Terminal Blocks)
- Universal outputs: Configurable as an analog (0 to 12 VDC) or binary object (0 or 12 VDC, on/off)
- Power/protection: Each short-circuit protected universal output capable of driving up to 100 mA (at 0-12 VDC) or 100 mA total for all outputs
- Resolution: 12-bit digital-to-analog conversion
- Wire size: 12-24 AWG, copper, in removable screw terminal blocks
Outputs, Triac (4 Binary)
- Triac outputs: Optically isolated zero-crossing triac output configured as a binary object
- Power: Maximum switching 24 VAC at 1.0 A for each output; maximum total for controller is 3.0 A
- Wire size: 12-24 AWG, copper, in removable screw terminal blocks
Output, Integrated Actuator
- Torque: 40 in-lb. (4.5 N•m)
- Angular rotation: 0 to 95°; adjustable end stops at 45 and 60° rotation
- Motor timing: 90 sec. for 90° at 60 Hz; 108 sec. for 90° at 50 Hz
- Shaft type/size: Mounts on round or square damper shafts. See Enclosure and Mounting on page 4.
- Noise level: <35 db(A) @ 1 meter (3.3 feet)
Communication Ports
- MS/TP (optional): One EIA-485 port (removable terminal block) for BACnet MS/TP, operating at 9.6, 19.2, 38.4, 57.6, 76.8, or 115.2 kilobaud; max. length of up to 4,000 feet (1,200 meters) of 18 AWG shielded twisted-pair, no more than 51 pf/ft (167 pf/m); use repeaters for longer distances
- Ethernet (optional): On "E" model only, two 10/100BaseT Ethernet connectors for BACnet IP, Foreign Device, and Ethernet 802.3 (ISO 8802-3); segmentation supported; up to 328 ft (100 m) between controllers (using T568B Category 5 or better cable)
- NFC: NFC (Near Field Communication) up to 1 inch (2.54 cm) from the top of the enclosure
- Room sensor: Modular STE connection jack for STE-9000A series digital sensors and STE-6010/6014/6017 analog sensors
- Auxiliary: One serial port with mini Type B connector (reserved for future use)
Configurability
OBJECTS* | MAXIMUM # |
---|---|
Inputs and Outputs | |
Analog, binary, or accumulator input | 8 |
Analog or binary output | 9 |
Values | |
Analog value | 120 |
Binary value | 80 |
Multi-state value | 40 |
Program and Control | |
Program (Control Basic) | 10 |
PID loop | 10 |
Schedules | |
Schedule | 2 |
Calendar | 1 |
Logs | |
Trend log | 20 |
Trend log multiple (must be created) | 4 (default 0) |
Alarms and Events | |
Notification class | 5 |
Event enrollment | 40 |
*Configuration allows creation and deletion of objects (maximum number of objects shown). The number and configuration of default objects depends on the selected application. For lists of default objects, see the KMC Conquest Controller Application Guide. See also the PIC statement for all supported BACnet objects.
Indicators and Isolation
- LED indicators: Power/status, MS/TP communication, and Ethernet status
- MS/TP protection: One network bulb assembly indicates reversed polarity and isolates circuit
- Switch: EOL (end of line) for MS/TP
Installation
Power
- Supply voltage: 24 VAC (−15%, +20%), 50/60 Hz, Class 2 only; non-supervised (all circuits, including supply voltage, are power limited circuits)
- Required power: 8 VA, plus external loads
- Wire size: 12-24 AWG, copper, in a removable screw terminal block
Enclosure and Mounting
- Weight: 1.17 lb. (0.53 kg)
- Case material: Green and black flame retardant plastic
- Mounting: Directly mounts on 3/8 to 5/8 inch (9.5 to 16 mm) round or 3/8 to 7/16 inch (9.5 to 11 mm) square damper shafts with 2 inch (51 mm) minimum shaft length
Environmental Limits
- Operating: 32 to 120° F (0 to 49° C)
- Shipping: -40 to 160° F (-40 to 71° C)
- Humidity: 0 to 95% relative humidity (non-condensing)
Warranty, Protocol, and Approvals
Warranty
KMC Limited Warranty 5 years (from mfg. date code)
BACnet Protocol
- Standard: Meets or exceeds the specifications in ANSI/ASHRAE BACnet Standard 135-2010 for Building Controllers
- Type: BTL-certified as a B-BC controller type
Regulatory
- UL: UL 916 Energy Management Equipment listed
- BTL: BACnet Testing Laboratory listed as Building Controller (B-BC) (pending)
- RoHS 2: RoHS 2 compliant
- FCC: FCC Class A, Part 15, Subpart B and complies with Canadian ICES-003 Class A*
*This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. (NFC operation meets FCC compliance while the controller is in an unpowered state.)
Accessories
DAT Sensor and Dual Duct Actuator
- STE-1405: Discharge air temperature sensor with 10-foot plenum-rated cable
- TSP-8003: Tri-state actuator with pressure sensor for dual-duct applications
Differential Air Pressure Sensors
- SSS-1012: Sensor, 3-5/32 inches (80 mm) length
- SSS-1013: Sensor, 5-13/32 in. (137 mm) length
- SSS-1014: Sensor, 7-21/32 in. (194 mm) length
- SSS-1015: Sensor, 9-29/32 in. (252 mm) length
Miscellaneous Hardware
- HPO-9901: Controller replacement parts kit with terminal blocks (1 gray, 1 black, 2 green 3-terminal, 4 green 4-terminal, 2 green 5-terminal, 2 green 6-terminal) and DIN clips (2 small for router and 1 large for controllers)
- SP-001: Screwdriver (KMC branded) with a hex end (for NetSensor cover screws) and a flat blade end (for controller terminals)
Network Communications
- BAC-5051AE: BACnet router with single MS/TP and IP/Ethernet ports
- HPO-0055: Replacement network bulb assembly (pack of 5)
- HPO-5551: Router technician cable kit
- HPO-9003: NFC Bluetooth/USB module (fob)
- HSO-9001: Ethernet patch cable, 50 feet
- HSO-9011: Ethernet patch cable, 50 feet, plenum rated
- HSO-9012: Ethernet patch cable, 75 feet, plenum rated
- KMD-5567: Network surge suppressor
Room Sensors, Analog
- STE-6010W10: Temperature sensor, white
- STE-6014W10: Sensor with rotary setpoint dial, white
- STE-6017W10: Sensor with rotary setpoint dial and override button, white
- HPO-9005: Room sensor adapter allows the use of other sensors and optional setpoint potentiometers (with wire leads or terminal blocks) to be used instead of STE-601x sensor models with modular jacks
NOTE: Other STE-6000 series sensors are not fully compatible with the dedicated sensor port. However, various other models can be used with an HPO-9005 adapter or with the controller screw terminals. See the STE-6000 series data sheet for more information. For digital sensor information, see the STE-9000 series.
NOTE: To order the STE-601x sensor with light almond color instead of white, drop the W on the end of the model number (e.g., STE-6010W is white and STE-6010 is light almond).
Room Sensors, Digital (LCD Display)
- STE-9000 Series: KMC Conquest NetSensor digital room temperature sensors for viewing, configuring, and optional humidity, occupancy, and CO2 sensing
- HPO-9001: NetSensor distribution module
Transformers, 120 to 24 VAC
- XEE-6111-050: 50 VA, single-hub
- XEE-6112-050: 50 VA, dual-hub
Sample Installation
Communication with Other Network Devices and Remote Monitoring
Configuration via NFC-Enabled Smart Phone
BAC-9001A on VAV Box (with air pressure sensor tubing attached)
Up to 4 Sensors (to terminal blocks)
STE-9xx1 NetSensor (to modular connector)
Up to 7 External Outputs (terminal blocks)
TSP-8003 Actuator (with air pressure sensor tubing attached) on Dual Duct VAV Box (controlled by 2 of the BAC-9001's 7 maximum external outputs)
Quick (temporary) Network Access Through Computer Data Port
For more information about installation and operation, see:
- BAC-9000 Series VAV Controller Installation Guide
- KMC Conquest Controller Application Guide
- KMC Conquest Wiring: BAC-9000 Series Controllers (Video)
Support
Additional resources for installation, configuration, application, operation, programming, upgrading, and much more are available on the web at www.kmccontrols.com. Log-in to see all available files.