Product Overview for COLDZONE models including: COLDZONE, Medium Profile Unit Cooler, Evaporator, Walk-in Cooler, Walk-in Freezer, Air Defrost, Electric Defrost, Hot Gas Defrost, EC Motor, AWEF, CZ-RMX-A1-0725, Refrigeration, HVAC, Unit Cooler Specifications, Unit Cooler Dimensions, Defrost Types, Application Ratings, Dual Speed EC Motor, California Title 24

Coldzone - » Legal

Coldzone - Low Air Velocity

Medium Profile

Coldzone - » Installation & Operations Manuals (IOMs)

PDF preview unavailable. Download the PDF instead.

CZ-RMX-A1-0725
MEDIUM PROFILE
UNIT COOLER
Walk-Ins: Medium to Large Cooler and Freezer Applications
Air Defrost 18,200 to 99,000 BTUH Electric Defrost 11,000 to 86,300 BTUH Hot Gas Defrost 11,000 to 64,300 BTUH

2 MEDIUM PROFILE UNIT COOLER
FEATURES
Our Medium Profile Unit Coolers are the perfect evaporator solution for medium to large walk-in coolers and freezers. Designed with efficiency, performance and service in mind, the Medium Profile line truly stands out from the competition. The unit coolers were engineered to meet the Department of Energy's new AWEF* performance regulations and all feature energy-efficient rail-mount Dual Speed EC Motors. For maximum performance, all units are circuited for multiple refrigerants and feature optimized circuit patterns, enhanced surface coil tubing, and new high efficiency fan and venturi designs. The Medium Profile product line has several serviceability features including rail-mount motors, easily removable fan guards and modular fan panels, face mount defrost heaters, hinged drain pans, and shipping pallets designed to facilitate quicker installation.

SIZES
There are a wide array of sizes available with capacities ranging from 11,000 to 99,000 BTUH at a 10° TD. Models are available with air flow spanning a range of 2,090 to 9,580 CFM.
HOUSING
Each unit is constructed with a rust-free, heavy gauge, textured, aluminum housing which is light weight yet extremely durable. Models feature hinged one-piece drain pans to allow for convenient servicing and maintenance. Hanger holes are provided on all units for fast installation.
COIL
Seamless copper tubes are staggered and mechanically expanded into corrugated aluminum fins to assure maximum heat transfer. Die formed fin collars are provided for accurate fin spacing. Top panel is fastened directly to the tube sheets of the coil to provide high structural strength. Low Temp Electric Defrost and Hot Gas Defrost Models are available in both 6 FPI and 4 FPI. Medium Temp Electric Defrost and Air Defrost models are available in 6 FPI.

MOTORS
All models feature highly efficient Dual Speed Electronically Commutated (EC) motors which are compliant with California Title 24 regulations.
FANS & FAN GUARDS
Powerful heavy-duty aluminum fans are individually balanced to provide vibration free operation. Standard heavy-gauge wire fan guards are UL/cUL-approved epoxy coated for corrosion resistance. Air throw for Medium Profile Unit Coolers is 75 ft.
REFRIGERANTS
Medium Profile Unit Coolers are optimized for multiple refrigerants including R404A, R407A, R448A, R449A and R744 DX (CO2). Please specify system refrigerant requirements when ordering. A separate compartment is provided for all refrigerant connections which allows ample room for internal mounting of expansion valves.
AIR DEFROST
Air Defrost models are designed for use in coolers at +35°F room temperature and warmer.

MEDIUM PROFILE UNIT COOLER 3

ELECTRIC DEFROST - MEDIUM TEMP
Medium Temperature Electric Defrost Models are designed for use in coolers between 10°F and 35°F room temperatures. Defrost heaters are mounted on the air intake side of the unit for optimal performance and easy maintenance. Heaters are installed inside the drain pan for fast, reliable drainage. Adjustable defrost termination, fan delay and heater safety controls are factory mounted for optimum performance of each control function.
ELECTRIC DEFROST - LOW TEMP
Low Temperature Electric Defrost Models are designed for use in freezers between +10°F and -30°F room temperatures. Defrost heaters are mounted on the air intake side of the unit for optimal performance and easy maintenance. Heaters are installed inside the drain pan for fast, reliable drainage. Adjustable defrost termination, fan delay and heater safety controls are factory mounted for optimum performance of each control function.
HOT GAS DEFROST
There are two types of Hot Gas Defrost models available: 3-pipe Hot Gas models and 2-pipe Hot Gas Reverse Cycle units. Hot Gas Defrost models are designed for use in coolers and freezers between +35°F and -30°F. Hot Gas Defrost 4 FPI models are designed for use in freezers between +32°F and -30°F. All units include adjustable defrost termination and fan delay controls which are factory mounted for optimum performance of each control function. Hot Gas Defrost models feature electric drain pan heaters making it possible to open the hinged drain pan for easy cleaning and servicing. Refer to the current Technical Bulletin for piping.

ELECTRICAL
Available in 115/12 (Air Defrost only) 208230V/12, 208-230V/32, 460V/1, or 460V/32. A large compartment is supplied for all electrical components and is easily accessible by removing the end panel. All models are UL and cUL listed.
OPTIONAL FEATURES
· EcoNet® Enabled Controller3 (factoryinstalled) (not available on Hot Gas Evaporators)
· EcoNet® Command Center (loose)
· Thermostat - Mechanical or Electric (mounted or loose)
· Thermostatic Expansion Valve (mounted or loose)
· Adjustable Defrost Termination
· Electronic Expansion Valve (mounted or loose)
· Liquid Line Solenoid Valve (mounted or loose)
· Insulated Drain Pan
· Painted Cabinet (White or Black)
· Stainless Steel Cabinet
· Coated Coil (Bronz-Glow, or Electrofin®)
· Suction/Liquid Heat Exchanger (loose)
* AWEF (Annual Walk-in Energy Factor) 1. Single Compressor system without variable capacity. 2. Some limitations apply. For specific electrical offering, consult electrical data tables in this brochure. 3. EcoNet Control Package includes EEV, suction pressure transducer, suction and entering air coil temp. thermistors, local onboard two-row backlit LCD display and push-button adjustments. (Controller replaces TXV, liquid line solenoid valve, room thermostat, defrost termination and fan delay, and time clock.)

4 MEDIUM PROFILE UNIT COOLER
ECONET ENABLED UNIT COOLERS (OPTIONAL)
Developed in conjunction with Rheem Manufacturing specifically for walk-in coolers and freezers -- it builds on the reliability and efficiency of Rheem's EcoNet technology
· Saves energy in refrigeration systems through precise superheat and space temperature control, fan cycling, and controlling how often the system goes into defrost based on compressor runtime
· Eliminates unnecessary defrosts · Maximizes energy efficiency with less compressor runtime · Reduces fan speed to 50% during off cycle for energy savings · Can be used with a condensing unit in single and multiple evaporator
installations as a group Optional EcoNet Command Center with intuitive graphical interface controls up to 32 devices (including the Command Center) through one display, continuous communication between system components, and remote mount display allows for EcoNet Enabled Unit Coolers to be programmed, monitored and troubleshot outside of space being cooled.

MODEL NOMENCLATURE

C
Brand C = Coldzone

M
Style
M = Medium Profile

6

E

Fins per Inch (FPI)

Defrost Type

4 FPI 6 FPI

A = Air
D = Medium Temp Electric
Defrost
E = Low Temp Electric Defrost
H = Hot Gas 3 Pipe Electric
Drain Pan
G = Hot Gas Rev Electric Drain Pan

153
BTUH in Thousands
XXX

D
Unit Voltage1
A =115/1/60 D =208230/1/60 E =208230/3/60
F =460/1/60 G =460/3/60

D
Motor Type
D = Dual Speed EC

A
Vintage A

MEDIUM PROFILE UNIT COOLER 5

APPLICATION RATING AND ELECTRICAL DATA
AIR DEFROST MODELS

Model No.
CM6A182*DA CM6A220*DA CM6A276*DA CM6A370*DA CM6A442*DA CM6A549*DA CM6A658*DA CM6A730*DA CM6A875*DA

BTUH Capacity @ +25°F S.T. & 10°F TD

R404A/ R744 DX (CO2)
18,200 22,000 27,600

R407A/ R448A/R449A^
21,100 25,800 32,300

37,000 44,200

43,100 51,900

54,900 65,800 73,000 87,500

64,200 76,900 85,600 99,000

CFM
3,190 2,950 6,950 6,380 5,900 9,580 8,860 12,770 11,800

No. of Fans
1 1 2 2 2 3 3 4 4

6 FPI

Total Fan Motor AMPS

115V/1
3.2 3.2 6.4 6.4 6.4 9.6 9.6 12.8 12.8

208-230V/1
1.9 1.9 3.8 3.8 3.8 5.7 5.7 7.6 7.6

460V/1
1.2 1.2 2.4 2.4 2.4 3.6 3.6 4.8 4.8

* Asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F.

6 MEDIUM PROFILE UNIT COOLER

APPLICATION RATING & ELECTRICAL DATA
MEDIUM TEMPERATURE ELECTRIC DEFROST

Model No.

BTUH Capacity @ +25°F S.T. & 10°F TD
CFM

404/744 DX

407/448/449

6 FPI

CM6D181*DA CM6D219*DA CM6D275*DA CM6D369*DA CM6D441*DA CM6D548*DA CM6D657*DA CM6D729*DA CM6D874*DA

18,200 22,000 27,600 37,000 44,200 54,900 65,800 72,900 87,400

21,100 25,800 32,300 43,100 51,900 64,200 76,900 85,300 98,800

3,190 2,950 6,950 6,380 5,900 9,580 8,860 12,770 11,800

No. of Fans
1 1 2 2 2 3 3 4 4

Total Fan Motor AMPS Dual Speed EC Motors
Motor Voltage

208-230V/1
1.9 1.9 3.8 3.8 3.8 5.7 5.7 7.6 7.6

460V/1
1.2 1.2 2.4 2.4 2.4 3.6 3.6 4.8 4.8

Model No.
CM6D181DDA CM6D219DDA CM6D275DDA CM6D369DDA CM6D441DDA

MCA

208-230V/1

MOPD

Base Model EcoNet Enabled1 Base Model EcoNet Enabled1

15.0

20.5

20

25

15.0

20.5

20

25

20

40.5

20

45

20

40.5

20

45

20

40.5

20

45

Heater Amps
208-230V/1 19.5 19.5 38.5 38.5 38.5

Heater Watts
4,480 4,480 8,860 8,860 8,860

6 FPI

Model No.
CM6D181EDA CM6D219EDA CM6D275EDA CM6D369EDA CM6D441EDA CM6D548EDA CM6D657EDA CM6D729EDA CM6D874EDA

MCA

208-230V/3

MOPD

Base Model EcoNet Enabled1 Base Model EcoNet Enabled1

15.0

15.0

20

25

15.0

15.0

20

25

15.0

23.2

20

25

15.0

23.2

20

25

15.0

23.2

20

25

15.0

35.5

20

40

15.0

35.5

20

40

15.0

45.7

20

50

15.0

45.7

20

50

Heater Amps
208-230V/3
11.2 11.2 22.2 22.2 22.2 33.5 33.5 44.7 44.7

Heater Watts
4,480 4,480 8,860 8,860 8,860 13,340 13,340 17,920 17,920

6 FPI

1 EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD. Econet Enabled calculations include additional 1 AMP for control voltages. ^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F.  Dual Speed EC motors are compliant with California Title 24 regulations. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings

MEDIUM PROFILE UNIT COOLER 7

APPLICATION RATING & ELECTRICAL DATA
MEDIUM TEMPERATURE ELECTRIC DEFROST

Model No.

MCA

460V/1

MOPD

Base Model EcoNet Enabled1 Base Model EcoNet Enabled1

6 FPI

CM6D181FDA

15.0

15.0

20

25

CM6D219FDA

15.0

15.0

20

25

CM6D275FDA

15.0

20.3

20

25

CM6D369FDA

15.0

20.3

20

25

CM6D441FDA

15.0

20.3

20

25

CM6D548FDA

15.0

30.0

20

35

CM6D657FDA

15.0

30.0

20

35

CM6D729FDA

15.0

39.7

20

40

CM6D874FDA

15.0

39.7

20

40

Heater Amps
460V/1
9.7 9.7 19.3 19.3 19.3 29.0 29.0 38.7 38.7

Heater Watts
4,480 4,480 8,860 8,860 8,860 13,340 13,340 17,920 17,920

Model No.
CM6D181GDA CM6D219GDA CM6D275GDA CM6D369GDA CM6D441GDA CM6D548GDA CM6D657GDA CM6D729GDA CM6D874GDA

MCA

460V/3

MOPD

Base Model EcoNet Enabled1 Base Model EcoNet Enabled1

15.0

15.0

20

20

15.0

15.0

20

20

15.0

15.0

20

20

15.0

15.0

20

20

15.0

15.0

20

20

15.0

17.7

20

20

15.0

17.7

20

20

15.0

23.3

20

25

15.0

23.3

20

25

Heater Amps
460V/1
5.6 5.6 11.1 11.1 11.1 16.7 16.7 22.3 22.3

Heater Watts
4,480 4,480 8,860 8,860 8,860 13,340 13,340 17,920 17,920

6 FPI

1 EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD. Econet Enabled calculations include additional 1 AMP for control voltages. ^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings

8 MEDIUM PROFILE UNIT COOLER

APPLICATION RATING & ELECTRICAL DATA
LOW TEMPERATURE ELECTRIC DEFROST

6 FPI

Model No.
CM6E153*DA CM6E184*DA CM6E311*DA CM6E374*DA CM6E469*DA CM6E564*DA CM6E624*DA CM6E750*DA CM4E110*DA CM4E143*DA CM4E232*DA CM4E288*DA CM4E336*DA CM4E419*DA CM4E447*DA CM4E557*DA

BTUH Capacity @ -20°F S.T. & 10°F TD1

R404A/R744 DX (CO2) 15,300 18,400 31,100 37,400 46,900 56,400 62,400 75,000 11,000 14,300 23,200 28,800 33,600 41,900 44,700 55,700

R407A/R448A/ R449A^ 17,400 21,100 35,700 42,900 53,600 64,300 71,100 86,300 12,400 16,200 26,100 32,700 38,300 47,600 50,800 64,100

CFM
2,250 2,090 4,500 4,180 6,750 6,270 9,000 8,360 2,350 2,210 4,690 4,420 7,040 6,640 9,000 8,360

4 FPI

No. of Fans
1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4

Capacity Correction for Electric Defrost Evaporators

S.S.T. (Dew)

20ºF

0ºF

-10ºF

-20ºF

Multiply Capacity by:

1.15

1.075

1.0375

1

1 Capacity values adjusted using the Correction Table for Electric Defrost Evaporators.

Total Fan Motor AMPS Dual Speed EC Motors
Motor Voltage

208-230V/1
1.9 1.9 3.8 3.8 5.7 5.7 7.6 7.6 1.9 1.9 3.8 3.8 5.7 5.7 7.6 7.6

460V/1
1.2 1.2 2.4 2.4 3.6 3.6 4.8 4.8 1.2 1.2 2.4 2.4 3.6 3.6 4.8 4.8

-30ºF 0.9625

- 40ºF 0.925

^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F.  Dual Speed EC motors are compliant with California Title 24 regulations. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings.

MEDIUM PROFILE UNIT COOLER 9

APPLICATION RATING & ELECTRICAL DATA
LOW TEMPERATURE ELECTRIC DEFROST

208-230V/1

Model No.

MCA Base Model EcoNet Enabled1

MOPD Base Model EcoNet Enabled1

6 FPI

CM6E153DDA

15.0

20.5

20

25

CM6E184DDA

15.0

20.5

20

25

CM6E311DDA

15.0

40.5

20

45

CM6E374DDA

15.0

40.5

20

45

CM4E110DDA

15.0

20.5

20

25

CM4E143DDA

15.0

20.5

20

25

CM4E232DDA

15.0

40.5

20

45

CM4E288DDA

15.0

40.5

20

45

4 FPI

Heater Amps
208-230V/1 19.5 19.5 38.5 38.5 19.5 19.5 38.5 38.5

Heater Watts
4,480 4,480 8,860 8,860 4,480 4,480 8,860 8,860

6 FPI

Model No.
CM6E153EDA CM6E184EDA CM6E311EDA CM6E374EDA CM6E469EDA CM6E564EDA CM6E624EDA CM6E750EDA CM4E110EDA CM4E143EDA CM4E232EDA CM4E288EDA CM4E336EDA CM4E419EDA CM4E447EDA CM4E557EDA

MCA

208-230V/3

MOPD

Heater Amps

Base Model
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0

EcoNet Enabled1
15.0 15.0 23.2 23.2 35.5 35.5 45.7 45.7 15.0 15.0 23.2 23.2 35.5 35.5 45.7 45.7

Base Model
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

EcoNet Enabled1
25 25 25 25 40 40 50 50 25 25 25 25 40 40 50 50

208-230V/3
11.2 11.2 22.2 22.2 35.5 35.5 44.7 44.7 11.2 11.2 22.2 22.2 35.5 35.5 44.7 44.7

Heater Watts
4,480 4,480 8,860 8,860 13,340 13,340 17,920 17,920 4,480 4,480 8,860 8,860 13,340 13,340 17,920 17,920

4 FPI

1 EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD. Econet Enabled calculations include additional 1 amp for control voltages.

10 MEDIUM PROFILE UNIT COOLER

APPLICATION RATING & ELECTRICAL DATA
LOW TEMPERATURE ELECTRIC DEFROST

Model No.

MCA

460V/1

MOPD

Heater Amps

6 FPI

CM6E153FDA CM6E184FDA CM6E311FDA CM6E374FDA CM6E469FDA CM6E564FDA CM6E624FDA CM6E750FDA CM4E110FDA CM4E143FDA CM4E232FDA CM4E288FDA CM4E336FDA CM4E419FDA CM4E447FDA CM4E557FDA

Base Model
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0

EcoNet Enabled1
15.0 15.0 20.3 20.3 30.0 30.0 39.7 39.7 15.0 15.0 20.3 20.3 30.0 30.0 39.7 39.7

Base Model
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

EcoNet Enabled1
25 25 25 25 35 35 40 40 25 25 25 25 35 35 40 40

460V/1
9.7 9.7 19.3 19.3 29.0 29.0 38.7 38.7 9.7 9.7 19.3 19.3 29.0 29.0 38.7 38.7

4 FPI

Heater Watts
4,480 4,480 8,860 8,860 13,340 13,340 17,920 17,920 4,480 4,480 8,860 8,860 13,340 13,340 17,920 17,920

1 EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD. Econet Enabled calculations include additional 1 AMP for control voltages. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings

MEDIUM PROFILE UNIT COOLER 11

APPLICATION RATING & ELECTRICAL DATA
LOW TEMPERATURE ELECTRIC DEFROST

Model No.

MCA

460V/3

MOPD

Heater Amps

6 FPI

CM6E153GDA CM6E184GDA CM6E311GDA CM6E374GDA CM6E469GDA CM6E564GDA CM6E624GDA CM6E750GDA CM4E110GDA CM4E143GDA CM4E232GDA CM4E288GDA CM4E336GDA CM4E419GDA CM4E447GDA CM4E557GDA

Base Model
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0

EcoNet Enabled1
15.0 15.0 15.0 15.0 17.7 17.7 23.3 23.3 15.0 15.0 15.0 15.0 17.7 17.7 23.3 23.3

Base Model
20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20

EcoNet Enabled1
20 20 20 20 20 20 25 25 20 20 20 20 20 20 25 25

460V/3
5.6 5.6 11.1 11.1 16.7 16.7 22.3 22.3 5.6 5.6 11.1 11.1 16.7 16.7 22.3 22.3

4 FPI

Heater Watts
4,480 4,480 8,860 8,860 13,340 13,340 17,920 17,920 4,480 4,480 8,860 8,860 13,340 13,340 17,920 17,920

1 EcoNet Enabled Units are not powered by Condensing Unit so Defrost Heaters are incorporated into shown MCA/MOPD. Econet Enabled calculations include additional 1 AMP for control voltages. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings

12 MEDIUM PROFILE UNIT COOLER

APPLICATION RATING & ELECTRICAL DATA
HOT GAS 3-PIPE DEFROST

6 FPI

Hot Gas 3-Pipe Model No.+
CM6H153*DA CM6H184*DA CM6H311*DA CM6H374*DA CM6H469*DA CM6H564*DA CM4H110*DA CM4H143*DA CM4H232*DA CM4H288*DA CM4H336*DA CM4H419*DA

BTUH Capacity @ -20°F S.T. & 10°F TD1

R404A
15,300 18,400 31,100 37,400 46,900 56,400 11,000 14,300 23,200 28,800 33,600 41,900

R407A/ R448A/R449A^
17,400 21,100 35,700 42,900 53,600 64,300 12,400 16,200 26,100 32,700 38,300 47,600

CFM
2,250 2,090 4,500 4,180 6,750 6,270 2,350 2,210 4,690 4,420 7,040 6,640

No. of Fans

Total Fan Motor AMPS Dual Speed EC Motors
Motor Voltage

208-230V/1 460V/1

1

1.9

1.2

1

1.9

1.2

2

3.8

2.4

2

3.8

2.4

3

5.7

3.6

3

5.7

3.6

1

1.9

1.2

1

1.9

1.2

2

3.8

2.4

2

3.8

2.4

3

5.7

3.6

3

5.7

3.6

4 FPI

MCA MOPD

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

6 FPI

Hot Gas 3-Pipe Model No.+
CM6H153*DA CM6H184*DA CM6H311*DA CM6H374*DA CM6H469*DA CM6H564*DA CM4H110*DA CM4H143*DA CM4H232*DA CM4H288*DA CM4H336*DA CM4H419*DA

Drain Pan Heater Amps

208-230V/1
15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300

460V/1
15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300 15,300

Drain Pan Heater Watts
1,480 1,480 2,960 2,960 4,440 4,440 1,480 1,480 2,960 2,960 4,440 4,440

HOT GAS 3-PIPE MODEL
The system uses 3 pipes -- 1 for liquid line, 1 for suction line and 1 for hot gas. The hot gas is taken from the discharge line, between the compressor and the condenser, through a hot-gas solenoid valve to the distributor tee then through the coil.

4 FPI

Capacity Correction for Hot Gas Defrost Evaporators

S.S.T. (Dew)

20ºF

0ºF

-10ºF

-20ºF

Multiply Capacity by:

1.15

1.075

1.0375

1

1 Capacity values adjusted using the Correction Table for Hot Gas Defrost Evaporators

-30ºF 0.9625

-40ºF 0.925

* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. + Hot Gas models include an electric drain pan.  Dual Speed EC motors are compliant with California Title 24 regulations. ^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings.

MEDIUM PROFILE UNIT COOLER 13

APPLICATION RATING & ELECTRICAL DATA
HOT GAS REVERSE CYCLE

4 FPI

6 FPI

Hot Gas Reverse Cycle Model No.+
CM6G153*DA CM6G184*DA CM6G311*DA CM6G374*DA CM6G469*DA CM6G564*DA CM4G110*DA CM4G143*DA CM4G232*DA CM4G288*DA CM4G336*DA CM4G419*DA

BTUH Capacity @ -20°F S.T. & 10°F TD1

R404A
15,300 18,400 31,100 37,400 46,900 56,400 11,000 14,300 23,200 28,800 33,600 41,900

R407A/ R448A/R449A^
17,400 21,100 35,700 42,900 53,600 64,300 12,400 16,200 26,100 32,700 38,300 47,600

CFM
2,250 2,090 4,500 4,180 6,750 6,270 2,350 2,210 4,690 4,420 7,040 6,640

No. of Fans

Total Fan Motor AMPS Dual Speed EC Motors
Motor Voltage
208-230V/1 460V/1

1

1.9

1.2

1

1.9

1.2

2

3.8

2.4

2

3.8

2.4

3

5.7

3.6

3

5.7

3.6

1

1.9

1.2

1

1.9

1.2

2

3.8

2.4

2

3.8

2.4

3

5.7

3.6

3

5.7

3.6

MCA MOPD

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

15.0

20

Hot Gas Reverse Cycle Model No.+

Drain Pan Heater Amps 208-230V/1 460V/1

6 FPI

CM6G153*DA

6.4

3.2

CM6G184*DA

6.4

3.2

CM6G311*DA

12.9

6.4

CM6G374*DA

12.9

6.4

CM6G469*DA

19.3

9.7

CM6G564*DA

19.3

9.7

CM4G110*DA

6.4

3.2

CM4G143*DA

6.4

3.2

CM4G232*DA

12.9

6.4

CM4G288*DA

12.9

6.4

CM4G336*DA

19.3

9.7

CM4G419*DA

19.3

9.7

4 FPI

Drain Pan Heater Watts
1,480 1,480 2,960 2,960 4,440 4,440 1,480 1,480 2,960 2,960 4,440 4,440

HOT GAS REVERSE CYCLE 2-PIPE MODEL
A changeover valve is located in the discharge suction line of the compressor, so that when defrost is required, the valve changes over from the normal refrigeration flow so that the discharged gas flows into the suction connection and bypasses TX valve.

Capacity Correction for Hot Gas Defrost Evaporators

S.S.T. (Dew)

20ºF

0ºF

-10ºF

-20ºF

Multiply Capacity by:

1.15

1.075

1.0375

1

1 Capacity values adjusted using the Correction Table for Hot Gas Defrost Evaporators

-30ºF 0.9625

-40ºF 0.925

* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. + Hot Gas models include an electric drain pan.  Dual Speed EC motors are compliant with California Title 24 regulations. ^ R407A, R448A and R449A are rated at dew point temperature. Use R407A capacity ratings for R407C and R407F. Models were designed in anticipation of the July 2020 Department of Energy Annual Walk-in Energy Factor (AWEF) regulations for evaporators for Walk-in Coolers and Freezers in boxes less than 3,000 sq. ft. See page 26 for AWEF compliance ratings.

14 MEDIUM PROFILE UNIT COOLER

DISTRIBUTOR NOZZLES & EXPANSION VALVES
AIR DEFROST

Part Numbers

Model No.

Nozzle @ Liq. Temp.

TXV^ @ Liq. Temp.

6 FPI - R404A

6 FPI - R407A, R407C

CM6A182*DA CM6A220*DA CM6A276*DA CM6A370*DA CM6A442*DA CM6A549*DA CM6A658*DA CM6A730*DA CM6A875*DA CM6A182*DA CM6A220*DA CM6A276*DA CM6A370*DA CM6A442*DA CM6A549*DA CM6A658*DA CM6A730*DA CM6A875*DA CM6A182*DA CM6A220*DA CM6A276*DA CM6A370*DA CM6A442*DA CM6A549*DA CM6A658*DA CM6A730*DA CM6A875*DA

50°F L-3/4 L-3/4
L-1 L-1-1/2 G-1-1/2
G-2 G-2-1/2
G-3 F-3 L-3/4 L-3/4 L-1 L-1-1/2 G-1-1/2 G-2 G-2-1/2 G-3 G-4 L-3/4 L-3/4 L-1 L-1-1/2 G-1-1/2 G-2 G-2-1/2 G-3 G-4

100°F L-2
L-2-1/2 L-3 L-4 G-5 G-6 G-8 G-10 G-12 L-2
L-2-1/2 L-3 L-4 G-5 G-6 G-8 G-10 G-12 L-2
L-2-1/2 L-3 L-4 G-5 G-6 G-8 G-10 G-12

50°F SBFSE-B-C SBFSE-B-C SBFSE-B-C SBFSE-C-C EBSSE-6-C EBSSE-6-C EBSSE-6-C EBSSE-6-C EBSSE-6-C SBFDE-B-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-7-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-7-C

100°F SBFSE-B-C SBFSE-B-C SBFSE-B-C SBFSE-C-C EBSSE-6-C EBSSE-6-C EBSSE-6-C EBSSE-7.5-C EBSSE-10-C SBFDE-B-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-10-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-10-C

6 FPI - R448A, R449A

EEV @ Liq. Temp.

50°F

100°F

SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-DS SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-D SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-D

SER-B SER-B SER-C SER-C SER-C SER-C SER-D SER-DS SER-DS SER-B SER-B SER-C SER-C SER-C SER-C SER-D SER-D SER-D SER-B SER-B SER-C SER-C SER-C SER-C SER-D SER-D SER-D

No. of Circuits
4 6 8 9 12 12 16 18 24 4 6 8 9 12 12 16 18 24 4 6 8 9 12 12 16 18 24

The distributor lines are 3/16" tube & 21" long. * Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ TXV selections are based on +25°F suction temp., 8°F to 12°F evaporator TD. Contact factory for operating conditions outside of this range.  SBFDE expansion valves are compatible with R407A, R448A and R449A/B. For other valves, follow manufacturers selection guidelines. Base models (no factory-mounted components) include nozzles sized for 100°F liquid shipped loose.

MEDIUM PROFILE UNIT COOLER 15

DISTRIBUTOR NOZZLES & EXPANSION VALVES
MEDIUM TEMPERATURE ELECTRIC DEFROST

Part Numbers

Model No.

Nozzle @ Liq. Temp.

TXV @ Liq. Temp.

6 FPI - R404A

6 FPI -R407A, R407C

CM6D181*DA CM6D219*DA CM6D275*DA CM6D369*DA CM6D441*DA CM6D548*DA CM6D657*DA CM6D729*DA CM6D874*DA CM6D181*DA CM6D219*DA CM6D275*DA CM6D369*DA CM6D441*DA CM6D548*DA CM6D657*DA CM6D729*DA CM6D874*DA CM6D181*DA CM6D219*DA CM6D275*DA CM6D369*DA CM6D441*DA CM6D548*DA CM6D657*DA CM6D729*DA CM6D874*DA

50°F L-3/4 L-3/4
L-1 L-1-1/2 G-1-1/2
G-2 G-2-1/2
G-3 G-3 L-3/4 L-3/4 L-1 L-1-1/2 G-1-1/2 G-2 G-2-1/2 G-3 G-4 L-3/4 L-3/4 L-1 L-1-1/2 G-1-1/2 G-2 G-2-1/2 F-3 G-4

105°F L-2
L-2-1/2 L-3 L-4 G-5 G-6 G-8 G-10 G-12 L-2
L-2-1/2 L-3 L-4 G-5 G-6 G-8 G-10 G-12 L-2
L-2-1/2 L-3 L-4 G-5 G-6 G-8 G-10 F-12

50°F SBFSE-B-C SBFSE-B-C SBFSE-B-C SBFSE-C-C EBSSE-6-C EBSSE-6-C EBSSE-6-C EBSSE-6-C EBSSE-6-C SBFDE-B-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-7-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-7-C

105°F SBFSE-B-C SBFSE-B-C SBFSE-C-C SBFSE-C-C EBSSE-6-C EBSSE-6-C EBSSE-6-C EBSSE-7.5-C EBSSE-10-C SBFDE-B-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-10-C SBFDE-B-C SBFDE-B-C SBFDE-C-C SBFDE-C-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-7-C EBSDE-10-C

6 FPI - R448A, R449A

EEV @ Liq. Temp.

50°F

105°F

SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-DS SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-D SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-D

SER-B SER-B SER-C SER-C SER-C SER-C SER-D SER-DS SER-DS SER-B SER-B SER-C SER-C SER-C SER-C SER-D SER-D SER-D SER-B SER-B SER-C SER-C SER-C SER-C SER-D SER-D SER-D

No. of Circuits
4 6 8 9 12 12 16 18 24 4 6 8 9 12 12 16 18 24 4 6 8 9 12 12 16 18 24

The distributor lines are 3/16" tube & 21" long. * Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ TXV selections are based on +25°F suction temp., 8°F to 12°F evaporator TD. Contact factory for operating conditions outside of this range.  SBFDE expansion valves are compatible with R407A, R448A and R449A/B. For other valves, follow manufacturers selection guidelines. Base models (no factory-mounted components) include nozzles sized for 100°F liquid shipped loose.

16 MEDIUM PROFILE UNIT COOLER

DISTRIBUTOR NOZZLES AND EXPANSION VALVES
LOW TEMPERATURE ELECTRIC DEFROST

Part Numbers

Model No.

Nozzle @ Liq. Temp.

TXV^ @ Liq. Temp.

EEV @ Liq. Temp.

6 FPI - R404A

6 FPI - R407A/ R407C

CM6E153*DA CM6E184*DA CM6E311*DA CM6E374*DA CM6E469*DA CM6E564*DA CM6E624*DA CM6E750*DA CM6E153*DA CM6E184*DA CM6E311*DA CM6E374*DA CM6E469*DA CM6E564*DA CM6E624*DA CM6E750*DA CM6E153*DA CM6E184*DA CM6E311*DA CM6E374*DA CM6E469*DA CM6E564*DA CM6E624*DA CM6E750*DA

50°F
L-1-1/2 L-1-1/2 G-2-1/2
G-3 G-4 G-5 5
6 L-1-1/2 L-1-1/2 G-2-1/2
G-3 G-4 G-5 G-5 G-6 L-1-1/2 L-1-1/2 G-2-1/2 G-3 G-4 G-5 G-5 G-6

100°F
L-2-1/2 L-3 G-5 G-6 G-10 G-12 15 17
L-2-1/2 L-3 G-5 G-6 G-10 G-12 G-15 G-17
L-2-1/2 L-3 G-5 G-6 G-10 G-12 G-15 G-17

50°F

100°F

SBFSE-B-Z

SBFSE-B-Z

SBFSE-B-Z

SBFSE-C-Z

SBFSE-C-Z

EBSSE-6-Z

EBSSE-6-Z

EBSSE-6-Z

EBSSE-6-Z EBSSE-7-1/2-Z

EBSSE-7-1/2-Z EBSSE-10-Z

EBSSE-7.5-Z EBSSE-10-Z

EBSSE-10-Z EBSSE-13-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-C-Z

SBFDE-C-Z

SBFDE-C-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z EBSDE-10-Z

EBSDE-10-Z EBSDE-12-Z

EBSDE-10-Z

EBS-12-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-C-Z

SBFDE-C-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-10-Z EBSDE-10-Z

EBSDE-10-Z EBSDE-12-Z

EBSDE-10-Z

EBS-12-Z

50°F
SER-B SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C SER-C SER-C

100°F
SER-B SER-B SER-C SER-C SER-C SER-C SER-DS SER-DS SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-D SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-D

6 FPI - R448A, R449A

No. of Circuits
6 8 12 16 18 24 18 24 6 8 12 16 18 24 18 24 6 8 12 16 18 24 18 24

The distributor lines are 3/16" tube & 21" long. * Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ TXV selections are based on -20°F suction temp., 8°F to 12°F evaporator TD. Contact factory for operating conditions outside of this range.  SBFDE expansion valves are compatible with R407A, R448A and R449A/B. For other valves, follow manufacturers selection guidelines. Base models (no factory-mounted components) include nozzles sized for 100°F liquid shipped loose.

MEDIUM PROFILE UNIT COOLER 17

DISTRIBUTOR NOZZLES AND EXPANSION VALVES
LOW TEMPERATURE ELECTRIC DEFROST

Part Numbers

Model No.

Nozzle @ Liq. Temp.

TXV^ @ Liq. Temp.

EEV @ Liq. Temp.

4 FPI - R404A

4 FPI - R407A, R407C

CM4E110*DA CM4E143*DA CM4E232*DA CM4E288*DA CM4E336*DA CM4E419*DA CM4E447*DA CM4E557*DA CM4E110*DA CM4E143*DA CM4E232*DA CM4E288*DA CM4E336*DA CM4E419*DA CM4E447*DA CM4E557*DA CM4E110*DA CM4E143*DA CM4E232*DA CM4E288*DA CM4E336*DA CM4E419*DA CM4E447*DA CM4E557*DA

50°F
L-1 L-1-1/2
L-2 G-2-1/2
G-3 G-4 4 5 L-1 L-1-1/2 L-2 G-2-1/2 G-3 G-4 G-4 G-5 L-1 L-1-1/2 L-2 G-2-1/2 G-3 G-4 G-4 G-5

100°F
L-2 L-2-1/2
L-4 G-5 G-6 G-8 10 12 L-2 L-2-1/2 L-4 G-5 G-6 G-8 G-10 G-12 L-2 L-2-1/2 L-4 G-5 G-6 G-8 G-10 G-12

50°F
SBFSE-A-Z SBFSE-A-Z SBFSE-B-Z SBFSE-C-Z SBFSE-C-Z EBSSE-6-Z EBSSE-6-Z EBSSE-6-Z SBFDE-A-Z SBFDE-B-Z SBFDE-C-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z EBSDE-7-Z EBSDE-7-Z SBFDE-A-Z SBFDE-A-Z SBFDE-B-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z EBSDE-7-Z EBSDE-7-Z

100°F
SBFSE-A-Z SBFSE-B-Z SBFSE-C-Z EBSSE-6-Z EBSSE-6-Z EBSSE-6-Z EBSSE-7.5-Z EBSSE-10-Z SBFDE-A-Z SBFDE-B-Z SBFDE-C-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z EBSDE-7-Z EBSDE-10-Z SBFDE-A-Z SBFDE-A-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z EBSDE-7-Z EBSDE-7-Z EBSDE-10-Z

50°F
SER-A SER-A SER-B SER-B SER-C SER-C SER-C SER-C SER-A SER-A SER-B SER-B SER-B SER-C SER-C SER-C SER-A SER-A SER-B SER-B SER-B SER-C SER-C SER-C

100°F
SER-A SER-B SER-B SER-C SER-C SER-C SER-C SER-DS SER-A SER-B SER-B SER-C SER-C SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C SER-C SER-C

4 FPI - R448A, R449A

No. of Circuits
4 6 9 12 12 16 18 24 4 6 9 12 12 16 18 24 4 6 9 12 12 16 18 24

The distributor lines are 3/16" tube & 21" long. * Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ TXV selections are based on -20°F suction temp., 8°F to 12°F evaporator TD. Contact factory for operating conditions outside of this range.  SBFDE expansion valves are compatible with R407A, R448A and R449A/B. For other valves, follow manufacturers selection guidelines. Base models (no factory-mounted components) include nozzles sized for 100°F liquid shipped loose.

18 MEDIUM PROFILE UNIT COOLER

DISTRIBUTOR NOZZLES AND EXPANSION VALVES
HOT GAS DEFROST

Part Numbers

Model No.

Nozzle @ Liq. Temp.

TXV^ @ Liq. Temp.

EEV @ Liq. Temp.

6 FPI - R404A

6 FPI - R407A, R407C

CM6*153*DA CM6*184*DA CM6*311*DA CM6*374*DA CM6*469*DA CM6*564*DA CM6*153*DA CM6*184*DA CM6*311*DA CM6*374*DA CM6*469*DA CM6*564*DA CM6*153*DA CM6*184*DA CM6*311*DA CM6*374*DA CM6*469*DA CM6*564*DA

50°F
L-1-1/2 G-1-1/2 G-2-1/2
G-3 G-4 G-5 L-1-1/2 G-1-1/2 G-2-1/2 G-3 G-4 G-5 L-1-1/2 G-1-1/2 G-2-1/2 G-3 G-4 G-5

105°F
L-2-1/2 G-3 G-5 G-6 G-10 G-12
L-2-1/2 G-3 G-5 G-6 G-10 G-12
L-2-1/2 G-3 G-5 G-6 G-10 G-12

50°F

105°F

SBFSE-B-Z

SBFSE-B-Z

SBFSE-B-Z

SBFSE-C-Z

SBFSE-C-Z

EBSSE-6-Z

EBSSE-6-Z

EBSSE-6-Z

EBSSE-6-Z EBSSE-7-1/2-Z

EBSSE-7-1/2-Z EBSSE-10-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-C-Z

SBFDE-C-Z

SBFDE-C-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z EBSDE-10-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-B-Z

SBFDE-C-Z

SBFDE-C-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-7-Z

EBSDE-10-Z EBSDE-10-Z

50°F
SER-B SER-B SER-B SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C

105°F
SER-B SER-B SER-C SER-C SER-C SER-C SER-B SER-B SER-C SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C

6 FPI - R448A/ R449A

No. of Circuits
6 8 12 16 18 24 6 8 12 16 18 24 6 8 12 16 18 24

The distributor lines are 3/16" tube & 21" long. * Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ TXV selections are based on -20°F suction temp., 8°F to 12°F evaporator TD. Contact factory for operating conditions outside of this range.  SBFDE expansion valves are compatible with R407A, R448A and R449A/B. For other valves, follow manufacturers selection guidelines. Base models (no factory-mounted components) include nozzles sized for 100°F liquid shipped loose.

MEDIUM PROFILE UNIT COOLER 19

DISTRIBUTOR NOZZLES AND EXPANSION VALVES
HOT GAS DEFROST

Part Numbers

Model No.

Nozzle @ Liq. Temp.

TXV^ @ Liq. Temp.

EEV @ Liq. Temp.

4 FPI - R404A

4 FPI - R407A/ R407C

CM4*110*DA CM4*143*DA CM4*232*DA CM4*288*DA CM4*336*DA CM4*419*DA CM4*110*DA CM4*143*DA CM4*232*DA CM4*288*DA CM4*336*DA CM4*419*DA CM4*110*DA CM4*143*DA CM4*232*DA CM4*288*DA CM4*336*DA CM4*419*DA

50°F
L-1 L-1-1/2
G-2 G-2-1/2
G-3 G-4 L-1 L-1-1/2 G-2 G-2-1/2 G-3 G-4 L-1 L-1-1/2 G-2 G-2-1/2 G-3 G-4

105°F
L-2 L-2-1/2
G-4 G-5 G-6 G-8 L-2 L-2-1/2 G-4 G-5 G-6 G-8 L-2 L-2-1/2 G-4 G-5 G-6 G-8

50°F
SBFSE-A-Z SBFSE-A-Z SBFSE-B-Z SBFSE-C-Z SBFSE-C-Z EBSSE-6-Z SBFDE-A-Z SBFDE-B-Z SBFDE-C-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z SBFDE-A-Z SBFDE-A-Z SBFDE-B-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z

105°F
SBFSE-A-Z SBFSE-B-Z SBFSE-C-Z EBSSE-6-Z EBSSE-6-Z EBSSE-6-Z SBFDE-A-Z SBFDE-B-Z SBFDE-C-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z SBFDE-A-Z SBFDE-A-Z SBFDE-C-Z SBFDE-C-Z EBSDE-7-Z EBSDE-7-Z

50°F
SER-A SER-A SER-B SER-B SER-C SER-C SER-A SER-A SER-B SER-B SER-B SER-C SER-A SER-A SER-B SER-B SER-B SER-C

105°F
SER-A SER-B SER-B SER-C SER-C SER-C SER-A SER-B SER-B SER-C SER-C SER-C SER-A SER-A SER-B SER-B SER-B SER-C

4 FPI - R448A R449A

No. of Circuits
4 6 9 12 12 16 4 6 9 12 12 16 4 6 9 12 12 16

The distributor lines are 3/16" tube & 21" long. * Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ TXV selections are based on -20°F suction temp., 8°F to 12°F evaporator TD. Contact factory for operating conditions outside of this range.  SBFDE expansion valves are compatible with R407A, R448A and R449A/B. For other valves, follow manufacturers selection guidelines. Base models (no factory-mounted components) include nozzles sized for 100°F liquid shipped loose.

20 MEDIUM PROFILE UNIT COOLER

SPECIFICATIONS

AIR DEFROST MODELS

Model No.

Fan Diam. (In.)

Motor Data

Motor Qty.

HP

RPM

Refrigerant Connections

No. of Hangers

Liquid Line^

Suction

Slot Location

Fig.

Unit Dimensions (In.)

L

W

H

Approx. Unit Wt.
(Lbs.)

6 FPI

CM6A182*DA 24 CM6A220*DA 24 CM6A276* DA 24 CM6A370*DA 24 CM6A442*DA 24 CM6A549*DA 24 CM6A658*DA 24 CM6A730*DA 24 CM6A875*DA 24

1

1/3

850

3/8

7/8

4

1

1/3

850

3/8

7/8

4

2

1/3

850

1/2

1-1/8

6

2

1/3

850

1/2

1-1/8

6

2

1/3

850

5/8 1-1/8

6

3

1/3

850 5/8 1-3/8

8

3

1/3

850 5/8 1-3/8

8

4

1/3

850

7/8 1-5/8

10

4

1/3

850

7/8 1-5/8

10

1 47-1/2 21-5/16 33-7/8 120 1 47-1/2 21-5/16 33-7/8 120 2 80-1/2 21-5/16 33-7/8 220 2 80-1/2 21-5/16 33-7/8 220 2 80-1/2 21-5/16 33-7/8 220 3 113-9/16 21-5/16 33-7/8 316 3 113-9/16 21-5/16 33-7/8 316 4 146-9/16 21-5/16 33-7/8 416 4 146-9/16 21-5/16 33-7/8 416

SPECIFICATIONS // MEDIUM TEMPERATURE ELECTRIC DEFROST MODELS

Model No.
CM6D181*DA CM6D219*DA CM6D275*DA CM6D369*DA CM6D441*DA CM6D548*DA CM6D657*DA CM6D729*DA CM6D874*DA

Fan Diam. (In.)
24 24 24 24 24 24 24 24 24

Motor Data

Motor Qty

HP

RPM

1

1/3

850

1

1/3

850

2

1/3

850

2

1/3

850

2

1/3

850

3

1/3

850

3

1/3

850

4

1/3

850

4

1/3

850

Refrigerant Connections

No. of Hangers

Liquid Line^

Suction

Slot Location

3/8

7/8

4

3/8

7/8

4

1/2 1-1/8

6

1/2 1-1/8

6

5/8 1-1/8

6

5/8 1-3/8

8

5/8 1-3/8

8

7/8 1-5/8 10

7/8 1-5/8 10

Unit Dimensions (In.) Approx.

Fig.

Unit Wt.

L

W

H

(Lbs.)

1 47-1/2 21-5/16 33-7/8 120 1 47-1/2 21-5/16 33-7/8 120 2 80-1/2 21-5/16 33-7/8 220 2 80-1/2 21-5/16 33-7/8 220 2 80-1/2 21-5/16 33-7/8 220 3 113-9/16 21-5/16 33-7/8 316 3 113-9/16 21-5/16 33-7/8 316 4 146-9/16 21-5/16 33-7/8 416 4 146-9/16 21-5/16 33-7/8 416

6 FPI

* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ For units with mounted TXV components. See Nozzle/TXV table for distributor connection size when TXV is field installed. For dimensional distance between hanger slots, consult model's corresponding dimension drawing. Hanger slots are 3/8" deep x 1" wide. Drain is 1-1/4" NPT for all models.

MEDIUM PROFILE UNIT COOLER 21

SPECIFICATIONS
LOW TEMPERATURE ELECTRIC DEFROST MODELS

Model No.

Fan Diam. (In.)

Motor Data

Motor Qty.

HP

RPM

Refrigerant Connections

Liquid Line^

Suction

No. of Hanger
Slot Loc.

Fig.

6 FPI - RM*E/G/H

CM6E153EDA 24 CM6E184EDA 24 CM6E311EDA 24 CM6E374EDA 24 CM6E469EDA 24 CM6E564EDA 24 CM6E624EDA 24 CM6E750EDA 24 CM4E110*DA 24 CM4E143*DA 24 CM4E232*DA 24 CM4E288*DA 24 CM4E336*DA 24 CM4E419*DA 24 CM4E447*DA 24 CM4E557*DA 24

1

1/3 850 3/8 1-1/8

4

1

1

1/3 850 3/8 1-1/8

4

1

2

1/3 850 1/2 1-5/8 6

2

2

1/3 850 5/8 1-5/8 6

2

3

1/3 850 5/8 2-1/8

8

3

3

1/3 850 5/8 2-1/8

8

3

4

1/3 850 7/8 2-1/8" 10 4

4

1/3 850 7/8 2-1/8" 10 4

1

1/3 850 3/8 1-1/8

4

1

1

1/3 850 3/8 1-1/8

4

1

2

1/3 850 1/2 1-3/8 6

2

2

1/3 850 1/2 1-3/8 6

2

3

1/3 850 1/2 1-5/8

8

3

3

1/3 850 5/8 1-5/8

8

3

4

1/3 850 5/8" 2-1/8" 10 4

4

1/3 850 5/8" 2-1/8" 10 4

4 FPI - RM*E/G/H

Unit Dimensions (In.)

L
47-1/2 47-1/2 80-1/2 80-1/2 113-9/16 113-9/16 146-9/16 146-9/16 47-1/2 47-1/2 80-1/2 80-1/2 113-9/16 113-9/16 146-9/16 146-9/16

W
21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16 21-5/16

H
33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8 33-7/8

App.Unit Wt. (Lbs.)
120 120 220 220 320 320 420 420 120 120 220 220 320 320 420 420

* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature. ^ For units with mounted TXV components. See Nozzle/TXV table for distributor connection size when TXV is field installed. For dimensional distance between hanger slots, consult model's corresponding dimension drawing. Hanger slots are 3/8" deep x 1" wide. Drain is 1-1/4" NPT for all models.

22 MEDIUM PROFILE UNIT COOLER

DIMENSIONAL DRAWINGS

Front View

LIQUID (BACK SIDE)

Figure 1: Single Fan
47-1/2

Side View

31-13/16

7/8 KNOCKOUT (BACKSIDE)

SUCTION (BACKSIDE)

POWER AND CONTROL PANEL
1-1/4 - 11.5 NPT DRAIN FITTING

Top View

FIGURE 1: SHIPPING INFORMATION

No. of Fans L

1

60

All mounting holes are 3/8" diameter. All dimensions are in inches.

Shipping Dimensions (Inches) W
43-1/4

H 48-1/2

Shipping Weight (Lbs) 346

MEDIUM PROFILE UNIT COOLER 23

DIMENSIONAL DRAWINGS

Front View

Figure 2: Two Fan

LIQUID (BACK SIDE)

80-1/2

31-13/16

7/8 KNOCKOUT (BACKSIDE)

Side View

SUCTION (BACKSIDE)

1-1/4 - 11.5 NPT DRAIN FITTING

POWER AND CONTROL PANEL

Top View

17-13/16

35-15/16

35-15/16

FIGURE 2: SHIPPING INFORMATION

No. of Fans L

2

93

All mounting holes are 3/8" diameter. All dimensions are in inches.

Shipping Dimensions (Inches) W
43-1/4

H 48-1/2

3/8 X 1 MOUNTING HOLES (6)
Shipping Weight (Lbs) 510

24 MEDIUM PROFILE UNIT COOLER

DIMENSIONAL DRAWINGS

Front View

Figure 3: Three Fan

LIQUID (BACK SIDE)

113-9/16

31-13/16

Side View

SUCTION (BACKSIDE)

1-1/4 - 11.5 NPT DRAIN FITTING

7/8 KNOCKOUT (BACKSIDE)
POWER AND CONTROL PANEL

Top View

17-13/16

36

FIGURE 3: SHIPPING INFORMATION

No. of Fans L

3

120

All mounting holes are 3/8" diameter. All dimensions are in inches.

33

36

Shipping Dimensions (Inches) W
43-1/4

H 48-1/2

3/8 X 1 MOUNTING HOLES (8)
Shipping Weight (Lbs) 673

MEDIUM PROFILE UNIT COOLER 25

DIMENSIONAL DRAWINGS

Front View

Figure 4: Four Fan

Side View

Top View

FIGURE 4: SHIPPING INFORMATION

No. of Fans L

4

160

All mounting holes are 3/8" diameter. All dimensions are in inches.

Shipping Dimensions (Inches) W
43-1/4

H 48-1/2

Shipping Weight (Lbs) 843

26 MEDIUM PROFILE UNIT COOLER

EVAPORATOR APPLICATION RATINGS
Multiple conditions combine to determine the application capacity of an evaporator. Walk-in space temperature, relative humidity, saturated suction temperature difference, and outdoor ambient temperature. All of the factors are considered when calculating an evaporator application rating. These ratings are considerably higher than the net capacity value used for DOE ratings (AWEF).
The AWEF of an evaporator is calculated using the dry coil capacity and the daily evaporator power consumption. Power consumption included fan and defrost power. Evaporator net capacity reported to the DOE database is dry coil capacity less the full power fan watts. DOE test conditions are at 10°F evaporator/SST temperature difference and less than 50% relative humidity and 96°F liquid temperature. These conditions create a uniform test method, but should not be used for equipment selection. The equipment selected would be too large for the application.
Published application ratings are a guideline for proper equipment selection. They account for true operating conditions experienced by equipment.

AWEF RATINGS // COOLER AND FREEZER MODELS

Department of Energy Annual Walk-In Energy Factor (AWEF) Ratings

Base Model No.

Defrost Type

FPI

COOLER MODELS1

CM6A182*DA

Air Defrost

6

CM6A220*DA

Air Defrost

6

CM6A276*DA

Air Defrost

6

CM6A370*DA

Air Defrost

6

CM6A442*DA

Air Defrost

6

CM6A549*DA

Air Defrost

6

CM6A658*DA

Air Defrost

6

CM6A730*DA

Air Defrost

6

CM6A875*DA

Air Defrost

6

CM6D181*DA Med Temp Electric Defrost 6

CM6D219*DA Med Temp Electric Defrost 6

CM6D275*DA Med Temp Electric Defrost 6

CM6D369*DA Med Temp Electric Defrost 6

CM6D441*DA Med Temp Electric Defrost 6

CM6D548*DA Med Temp Electric Defrost 6

CM6D657*DA Med Temp Electric Defrost 6

CM6D729*DA Med Temp Electric Defrost 6

CM6D874*DA Med Temp Electric Defrost

6

CM6*153*DA Med Temp Hot Gas Defrost 6

CM6*184*DA Med Temp Hot Gas Defrost 6

CM6*311*DA Med Temp Hot Gas Defrost 6

CM6*374*DA Med Temp Hot Gas Defrost 6

CM6*469*DA Med Temp Hot Gas Defrost 6

CM6*564*DA Med Temp Hot Gas Defrost 6

AWEF
9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9

* Each asterisk represents a variable character based on voltage ordered. See page 4 for nomenclature.
1 If the model has a numerical value in the table above, the following statement applies:"The evaporator is designed and certified for use in walk-in cooler applications.
2 If the model has a numerical value in the table above, the following statement applies: "The evaporator is designed and certified for use in walk-in freezer applications."

Department of Energy Annual Walk-In Energy Factor (AWEF) Ratings

Base Model No.

Defrost Type

FPI

FREEZER MODELS2
CM6E153*DA Low Temp Electric Defrost 6 CM6E184*DA Low Temp Electric Defrost 6 CM6E311*DA Low Temp Electric Defrost 6 CM6E374*DA Low Temp Electric Defrost 6 CM6E469*DA Low Temp Electric Defrost 6 CM6E564*DA Low Temp Electric Defrost 6 CM6E624*DA Low Temp Electric Defrost 6 CM6E750*DA Low Temp Electric Defrost 6 CM4E110*DA Low Temp Electric Defrost 4 CM4E143*DA Low Temp Electric Defrost 4 CM4E232*DA Low Temp Electric Defrost 4 CM4E288*DA Low Temp Electric Defrost 4 CM4E336*DA Low Temp Electric Defrost 4 CM4E419*DA Low Temp Electric Defrost 4 CM4E447*DA Low Temp Electric Defrost 4 CM4E557*DA Low Temp Electric Defrost 4 CM6*153*DA Low Temp Hot Gas Defrost 6 CM6*184*DA Low Temp Hot Gas Defrost 6 CM6*311*DA Low Temp Hot Gas Defrost 6 CM6*374*DA Low Temp Hot Gas Defrost 6 CM6*469*DA Low Temp Hot Gas Defrost 6 CM6*564*DA Low Temp Hot Gas Defrost 6 CM4*110*DA Low Temp Hot Gas Defrost 4 CM4*143*DA Low Temp Hot Gas Defrost 4 CM4*232*DA Low Temp Hot Gas Defrost 4 CM4*288*DA Low Temp Hot Gas Defrost 4 CM4*336*DA Low Temp Hot Gas Defrost 4 CM4*419*DA Low Temp Hot Gas Defrost 4

AWEF
4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15 4.15

MEDIUM PROFILE UNIT COOLER 27

©2025 Heat Transfer Products Group Published July 2025 CZ-RMX-A1-0725 coldzone.htpg.com
This information is the most current and accurate information available and is subject to change without notice. HTPG makes no warranty or guarantee of any kind, express or implied, regarding the information set forth herein, including without limitation warranty regarding its currency, accuracy or completeness or any warranty of merchantability or fitness for a particular purpose.


Adobe PDF Library 17.0 Adobe InDesign 20.4 (Windows)

Related Documents

Preview Coldzone A2L Heavy Duty Unit Cooler Specifications and Data
Comprehensive technical specifications, features, application ratings, and dimensional data for the Coldzone A2L Heavy Duty Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Includes details on air defrost, electric defrost (medium and low temperature), refrigerants, electrical specifications, and optional features.
Preview COLDZONE A2L Medium Profile Unit Cooler: Specifications & Applications
Discover the COLDZONE A2L Medium Profile Unit Cooler, an efficient evaporator solution for walk-in coolers and freezers. This document details technical specifications, application ratings, electrical data, and dimensional drawings for various defrost types and refrigerants.
Preview Coldzone A2L Medium Profile Unit Cooler: Features, Specifications, and Ratings
Detailed technical specifications, application ratings, and dimensional data for Coldzone's A2L Medium Profile Unit Coolers, designed for walk-in cooler and freezer applications. Includes information on defrost types, capacities, electrical data, and model nomenclature.
Preview COLDZONE A2L Center Mount Unit Cooler for Walk-Ins
Detailed specifications, features, and application data for COLDZONE A2L Center Mount Unit Coolers, designed for small to medium walk-in cooler and freezer applications. Includes information on air and electric defrost models, refrigerants, electrical specifications, and model nomenclature.
Preview COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler Specifications
The COLDZONE A2L Next Gen All-Temp Low Profile Unit Cooler is designed for small to medium walk-in cooler and freezer applications, featuring advanced performance, air and electric defrost options, high-efficiency motors, and compatibility with A2L refrigerants.
Preview COLDZONE Low Velocity Center Mount Unit Cooler Specifications
Detailed specifications and features for the COLDZONE Low Velocity Center Mount Unit Cooler, designed for walk-in coolers and freezers. Includes BTUH capacities, defrost options, motor details, and application suitability.
Preview Coldzone A2L Next Gen All-Temp Low Profile Unit Cooler
Detailed specifications, features, and application ratings for Coldzone's A2L Next Gen All-Temp Low Profile Unit Coolers, designed for walk-in coolers and freezers. Includes information on air and electric defrost models, refrigerant compatibility, and dimensional data.
Preview Coldzone A2L Warehouse Unit Coolers: Specifications and Applications
Explore the Coldzone A2L Warehouse Unit Cooler series, designed for medium to large walk-in cooler and freezer applications. Features include air and electric defrost options, various BTUH capacities, and compatibility with refrigerants R454A, R454C, and R455A.