Komfovent Duct Heat Exchangers

Installation and Maintenance Manual

Nomenclature

The nomenclature for Komfovent heat exchangers follows a specific structure:

Additional codes indicate:

Technical Information

Duct heat exchangers are designed for heating or cooling cleaned air in ventilation systems. They are mounted outside the main unit. The coils are typically made of copper tubes and aluminum plates, with housings made of galvanized steel (as shown in Figure 1a).

Figure 1a: Illustration showing the housing of heat exchangers made of galvanized steel.

Coolers with rectangular connections are housed in shield sections (Figure 1b). These sections have a shield thickness of 45 mm and are insulated with mineral stone wool (thermal conductivity λ = 0.037 W/mK). The casing is available in RAL 7035. Cooler sections are equipped with a drop separator and a drain tray (drain tray pipe Ø32 mm). Connecting flanges are L20. Control of heat exchangers is managed by automatic control systems.

Figure 1b: Illustration showing coolers with rectangular connections mounted in shield sections.

Figure 2: Diagram illustrating the dimensions (L, B, H, B1, H1) of an air cooler/heater section with rectangular connections.

Figure 3: Diagrams showing heat exchangers with round connections: (a) heater, (b) cooler, with dimensions (ØD, L, B, H, B1, H1).

Water heat exchangers with round connections are shown in Figure 3. Coolers are supplied with a drain tray (drain tray pipe Ø15 mm).

Key Technical Specifications:

Attention: Earthing must be installed according to EN61557 BS 7671!
Note: It is a must to mount the drainage siphon.

Technical Data Tables

The following tables provide detailed technical data for various heat exchanger models, including capacity, pressure drops, dimensions, and weights.

Table 1. Water and evaporative coolers with rectangular connections

Type Supply air volume, m³/h Air temp. in/out, °C Internal fluid Capacity, kW Air pressure drop*, Pa Hydraulic pressure drop, kPa B×H×L, mm Pipe connection Internal volume, dm³ B1×H1, mm Weight, kg
DCF-0,4-3400R410A2,8160,4600×550×3901/2"/22 mm0,9300×40040
DCW-0,4-3400Water 7/122,63030,7505×550×3901/2"1,6300×40033
DCF-0,5-3500R410A3,5190,6600×550×3901/2"/22 mm0,9400×30040
DCW-0,5-3500Water 7/123,33052,8600×550×3901/2"1,9400×30035
DCF-0,7-5700R410A4,8220,6705×610×3901/2"/22 mm1,8500×40049
DCW-0,7-5700Water 7/124,2226,9705×610×3901/2"2,6500×40042
DCF-0,9-6900R410A6,2290,9705×610×3901/2"/22 mm1,8500×40049
DCW-0,9-6900Water 7/125,5307,9705×610×3903/4"2,8500×40045
DCF-1,2-81200R410A8,3431,5705×610×3901/2"/22 mm1,8500×40049
DCW-1,2-81200Water 7/127,44612,8705×610×3903/4"2,8500×40045
DCF-1,4-101400R410A9,77411,8705×610×3901/2"/22 mm2,3500×40051
DCW-1,4-91400Water 7/128,76116,7705×610×3903/4"2,8500×40045
DCF-1,6-11160030/18R410A11,17816,4755×610×4201/2"/22 mm2,5500×40056
DCW-1,6-11160030/18Water 7/12106522,2755×610×4203/4"3,0500×40046
DCF-2,0-142000R410A13,87130,7920×610×4205/8"/22 mm3,1700×40065
DCW-2,0-132000Water 7/1212,86038920×610×4203/4"3,6700×40057
DCF-2,5-172500R410A16,96714,91080×670×4205/8"/22 mm7,5800×40079
DCW-2,5-172500Water 7/1215,56316,61080×670×4201"8,4800×40065
DCF-3,0-203000R410A20,89222,11080×670×4205/8"/22 mm7,6800×40079
DCW-3,0-203000Water 7/1218,7102231080×670×4201"8,4800×40069
DCF-4,0-274000R410A26,99445,61220×730×4205/8"/22 mm9,8900×50097
DCW-4,0-274000Water 7/1225,210638,41220×730×4201"10,7900×50082
DCF-4,5-314500R410A30,39535,51220×790×4203/4"/22 mm10,9900×600103
DCW-4,5-304500Water 7/1228,8108621220×790×4201"11,9900×60087
DCF-7,0-48-27000R410A2×24,210210,21500×790×4802×3/4"/2×22mm7,71200×600125
DCW-7,0-477000Water 7/1244,510035,51500×790×4201 1/2"10,41200×600105
* with droplet eliminator

Table 2. Evaporative coolers with rectangular connections adapted to external condensers MOU

Type Supply air volume, m³/h Air temper. in/out, °C Internal fluid Capacity, kW Air pressure drop*, Pa Hydraulic pressure drop, kPa B×H×L, mm Pipe connection Internal volume, dm³ B1×H1, mm Weight, kg
DCF-0,4-340030/18,52,6160,4600×550×3901/2"/22 mm0,9300×40040
DCF-0,5-350030/18,73,2200,5600×550×3901/2"/22 mm0,9400×30040
DCF-0,7-570030/16,85,3220,7705×610×3901/2"/22 mm1,8500×40049
DCF-0,9-690030/16,07,4301,2705×610×3901/2" /22 mm1,8500×40049
DCF-1,2-8120030/17,28,9451,7705×610×3901/2"/22 mm1,8500×40049
DCF-1,4-10140030/16,810,77414,3705×610×3901/2"/22 mm2,3500×40051
DCF-1,6-11160030/18,4R410A10,77915,3755×610×4201/2"/22 mm2,5500×40056
DCF-2,0-14200030/17,714,27132,3920×610×4205/8"/22 mm3,1700×40065
DCF-2,5-17250030/18,715,86713,21080×670×4205/8"/22 mm7,5800×40079
DCF-3,0-20-2300030/17,72×10,67912,61080×670×4202×12½"/2×22mm4,5800×40079
DCF-4,0-27-2400030/17,72×14,28024,61220×730×4202×5/8"/2×22mm5,7900×50092
DCF-4,5-31-2450030/17,62×16,18239,11220×790×4202×5/8"/2×22mm6,3900×60098
DCF-7,0-48-3700030/17,93×16,210013,21500×790×4803×5/8" /3×22mm8,01200×600131
* with droplet eliminator

Table 3. Duct water heat exchangers with round connections

Type Supply air volume, m³/h Air temper. in/out, °C Fluid Capacity, kW Air pressure drop, Pa Hydraulic pressure drop, kPa B×H×L, mm Pipe connection Internal volume, dm³ ØD, mm Weight, kg
DH-12545010/22Water 60/401,8442,2335×295×1520,91256,15
DHCW-12545026/18Water 7/121,46911,6335×335×1641,212511,13
DH-16045010/22Water 60/401,8442,2335×295×1520,91606,15
DHCW-16045026/18Water 7/121,46911,6335×335×1641,216011,13
DH-20090010/22Water 60/403,61014,5360×320×1521,12007,04
DHCW-20090026/18Water 7/123,015350,1365×365×1641,520012,40
DH-25090010/22Water 60/403,6495,4420×380×1521/2"1,52509,30
DHCW-25090026/18Water 7/123,17767,6425×425×1642,025015,37
DH-315160010/22Water 60/406,55817,9470×510×1522,131511,75
DHCW-315160026/18Water 7/125,29013,4560×515×1643,031521,60
DH-315M200010/22Water 60/408,1983,6480×520×1322,431514,39
DHCW-315200026/18Water 7/126,513320,1560×515×1643,031521,60
DH-355200010/22Water 60/408,16128,3600×510×1522,435513,34
DHCW-355200026/18Water 7/126,65521,6605×605×1642,435525,43

Table 4. Duct water heat exchangers with rectangular connections

Type Supply air volume, m³/h Air temp. in/out, °C Capacity*, kW Air pressure drop, Pa Hydraulic pressure drop, Pa B×H×L, mm Pipe connection Internal volume, dm³ B1×H1, mm Weight, kg
SVK-400×200-28500/226,33731480×320×1001/2"0,8400×2005,0
SVK-400×200-4850-23/2212,86933517×320×1301/2"1,3400×2007,0
SVK-500×250-215000/2211,17014617×320×1001/2"0,9500×2506,0
SVK-500×250-41500-23/2222,613117617×320×1301/2"1,5500×2509,0
SVK-500×300-218000/2213,36524617×380×1001/2"1,1500×3007,0
SVK-500×300-41800-23/2227,212226623×380×1303/4"2,1500×30012,0
SVK-600×300-223000/22177340717×380×1001/2"1,2600×3008,0
SVK-600×300-42300-23/2234,713725723×380×1303/4"2,3600×30013,0
SVK-600×350-226000/2219,26521717×440×1001/2"1,5600×3509,0
SVK-600×350-42600-23/2239,212325723×440×1303/4"2,8600×35015,0
SVK-700×400-240000/2229,612052817×500×1001/2"3,1700×40012,0
SVK-700×400-44000-23/2260,322653830×500×1301"6,4700×40018,0
SVK-800×500-245000/2233,39214923×560×1003/4"4,1800×50014,0
SVK-800×500-44500-23/2267,917214,2937×560×1301 1/4"8,5800×50021,0
SVK-1000×500-257000/2242,194221123×560×1003/4"4,91000×50016,0
SVK-1000×500-45700-23/2286177231137×560×1301 1/4"10,11000×50025,0
* Internal fluid temperature 80/60 °C.

The technical data presented in tables 1-4 cover capacity, air pressure drop, hydraulic pressure drop at different air flows, and parameters like cooling capacities (calculated at 50% relative humidity). Weights, dimensions, and connection specifications are also provided.

Installation of Heat Exchangers

The unit is intended for indoor use only, within a temperature range of +5°C to +40°C. Coolers must be installed such that the air flow direction is horizontal. For heat exchangers, the water flow direction must always be opposite to the air flow direction.

Figure 4a: Diagram showing fluid flow direction in respect of air flow in coolers with rectangular connections. 'A' indicates water/refrigerant out, 'B' indicates water/refrigerant in.

DH and DHCW heat exchangers are equipped with a return water temperature sensor, mounted according to the fluid flow direction (Figure 4b).

Figure 4b: Diagram showing fluid flow direction in respect of air flow in heat exchangers with round connections. 'A' indicates water out, 'B' indicates water in, 'T' indicates temperature sensor.

Before installation, heat exchangers should be thoroughly flushed with water. DCF heat exchangers are filled with nitrogen gas, which must be released through a valve.

Attention! When screwing fitting pipes onto the system, hold them with a tube wrench, as shown in Figure 5a.

Figure 5a: Illustration depicting a correct heat exchanger fitting pipe connection, emphasizing the use of a tube wrench for proper installation and maintenance access.

Figure 5b: Illustration showing the installation of a return water sensor.

Attention! Fig. 5a shows correct heat exchanger fitting pipe connection. Wherever possible, heat exchanger pipes should be connected in such a way as to ensure free access to pipe work for maintenance. When carrying out installation of heat exchanger pipes, make sure that liquid (evaporative refrigerant) supply is completely disconnected.

The sensor shown in Figure 5b must be thermally insulated and connected to the controller terminals (refer to the automatic control manual for details).

Before starting up the air handling unit, working evaporative refrigerant should be injected into the heat exchangers. The heat exchanger can be filled with water and 30% ethylene glycol liquid.

Consult the technical documentation of the ethylene glycol liquid supplier for specific handling instructions. Never pour glycol down a drain; collect it in a receptacle and take it to a recycling center. Glycol is hazardous if consumed and can cause poisoning or kidney damage. Seek medical attention if ingested. Avoid breathing glycol vapor in confined spaces. If glycol gets into the eyes, flush thoroughly with water for approximately 5 minutes.

Cleaning and Inspection of Heat Exchangers

The plates of heat exchangers and droplet eliminators should be cleaned regularly to ensure efficient heat exchange between the coil surface and the air flow. Cleaning frequency should be determined by air purity and the use of in-line filters.

Always clean the heat exchanger against the regular direction of airflow. Ensure the coils are purged of air. If a droplet eliminator is fitted, remove it and clean it with water. Also, check that the condensate drain is not clogged.

Water Trap Installation

The bend of the water trap can be repositioned to the right or left. The drain line from the water trap must be routed to avoid damaging adjacent unit sections or building elements. If the drain line passes through cold spaces, it should be insulated to prevent freezing, and a heating cable may be required.

Water trap installation for a unit section mounted on the suction side

Since fans in most air handling units are positioned at the end of the functional chain and generate sub-atmospheric pressure inside the unit, correct installation of the water trap is crucial. This prevents condensate from being poorly eliminated, which could lead to condensate accumulation. Height H₁ must be at least equivalent in mm to half of the negative pressure inside the unit (measured in mm water gauge). Height H₂ must be at least equivalent in mm to the negative pressure inside the unit (measured in mm water gauge).

Figure 6: Schematic diagram illustrating the principle of correct drainage siphon installation, showing condensate flow and height requirements (H1, H2).

Precaution: The drainage siphon should be mounted on the outlet fitting pipe of every drip tray for complete condensate drainage from the air handling unit and to prevent the penetration of offensive odors from an effluent into the ventilation system.

Water trap installation for a unit section mounted on the pressure side

When fans are not at the end of the chain and generate over-atmospheric pressure inside the cooling section, condensate can be easily removed from the AHU. In such cases, there are no strict requirements for siphon installation; a drainage siphon with a minimum rake is sufficient.

RECOMMENDATION: The drainage siphon must be installed with a pipe diameter of not less than the specified size.

Service and Support

LITHUANIA: UAB KOMFOVENT, Phone: +370 5 200 8000, service@komfovent.com, www.komfovent.com

FINLAND: Komfovent Oy, Muuntotie 1 C1, FI-01510 Vantaa, Finland, Phone: +358 20 730 6190, toimisto@komfovent.com, www.komfovent.com

GERMANY: Komfovent GmbH, Konrad-Zuse-Str. 2a, 42551 Velbert, Deutschland, Phone: +49 0 2051 6051180, info@komfovent.de, www.komfovent.de

LATVIA: SIA Komfovent, Bukaisu iela 1, LV-1004 Riga, Latvia, Phone: +371 24 66 4433, info.lv@komfovent.com, www.komfovent.com

SWEDEN: Komfovent AB, Älggärdesvägen 12A, 433 30 Partille, Sverige, Phone: +46 31 487 752, info_se@komfovent.com, www.komfovent.se

UNITED KINGDOM: Komfovent Ltd, Unit C1 The Waterfront, Newburn Riverside, Newcastle upon Tyne NE15 8NZ, UK, Phone: +447983 299 165, steve.mulholland@komfovent.com, www.komfovent.com

Partners:

AT: J. PICHLER Gesellschaft m. b. H. www.pichlerluft.at

BE: Ventilair group, ACB Airconditioning, www.ventilairgroup.com, www.acbairco.be

CZ: REKUVENT s.r.o., www.rekuvent.cz

CH: WESCO AG, SUDCLIMATAIR SA, CLIMAIR GmbH, www.wesco.ch, www.sudclimatair.ch, www.climair.ch

DK: Øland A/S, www.oeland.dk

EE: BVT Partners, www.bvtpartners.ee

FR: ATIB, www.atib.fr

HR: Microclima, www.microclima.hr

HU: AIRVENT Lågtechnikai Zrt., Gevent Magyarország Kft., Merkapt, www.airvent.hu, www.gevent.hu, www.merkapt.hu

IE: Lindab, www.lindab.ie

IR: Fantech Ventilation Ltd, www.fantech.ie

IS: Blikk & Tækniþjónustan ehf, Hitataekni ehf, www.bogt.is, www.hitataekni.is

IT: ICARIA, www.icaria.srl

NL: Ventilair group, DECIPOL-Vortvent, CLIMA DIRECT BV, www.ventilairgroup.com, www.vortvent.nl, www.climadirect.com

NO: Ventilution AS, Ventistål AS, Thermo Control AS, www.ventilution.no, www.ventistal.no, www.thermocontrol.no

PL: Ventia Sp. z o.o., www.ventia.pl

SE: Nordisk Ventilator AB, www.nordiskventilator.se

SI: Agregat d.o.o, www.agregat.si

SK: TZB produkt, s.r.o., www.tzbprodukt.sk

UA: TD VECON LLC, www.vecon.ua

For more information, visit: www.komfovent.com

This symbol indicates that this product is not to be disposed of with your household waste, according to the WEEE Directive (2002/96/EC) and your national law. This product should be handed over to a designated collection point, or to an authorised collection site for recycling waste electrical and electronic equipment (EEE). Improper handling of this type of waste could have a possible negative impact on the environment and human health due to potentially hazardous substances that are generally associated with EEE. At the same time, your cooperation in the correct disposal of this product will contribute to the effective usage of natural resources. For more information about where you can drop off your waste equipment for recycling, please contact your local city office, waste authority, approved WEEE scheme or your household waste disposal service.
Models: Duct Heat Exchangers, Heat Exchangers, Exchangers

PDF preview unavailable. Download the PDF instead.

dcf dcw dh dhcw svk manual en .sMHxIsra99uOum7sUpIMREBsyIoPCHTv Adobe PDF Library 17.0 Adobe InDesign 19.0 (Windows)

Related Documents

Preview Komfovent SVK Hot Water Air Heater Specifications and Dimensions
Detailed specifications, dimensions, and performance data for the Komfovent SVK series of hot water air heaters, including air flow, heating power, water temperature, pressure loss, and connection sizes.
Preview Komfovent Verso R 5000 V C5 Air Handling Unit Specifications
Technical specifications and performance data for the Komfovent Verso R 5000 V C5 air handling unit, including airflow, power, temperature performance, and dimensions.
Preview Komfovent Domekt R 200 V C8 Air Handling Unit Specifications
Technical specifications and performance data for the Komfovent Domekt R 200 V C8 air handling unit, including airflow, pressure, efficiency, and dimensions.
Preview Komfovent RHP Pro Installation Manual - Efficient Air Handling
Comprehensive installation manual for the Komfovent RHP Pro air handling unit. Learn about unit types, components, mechanical and electrical installation, commissioning, and maintenance.
Preview Komfovent Domekt R 150 F C8 - Technical Specifications and Performance Data
Detailed technical specifications for the Komfovent Domekt R 150 F C8 heat recovery ventilation unit, including performance data, dimensions, and operational characteristics.
Preview Komfovent Verso Standard User Manual
User manual for the Komfovent Verso Standard ventilation unit, detailing its functions, settings, and maintenance.
Preview Komfovent Kombi A9 Hybrid Heating and Ventilation Unit Technical Specifications
Detailed technical specifications, performance data, and connection details for the Komfovent Kombi A9 hybrid heating and ventilation unit, including AHU and heat pump performance.
Preview Komfovent RHP Pro User Manual: Comprehensive Guide to Air Handling Unit Operation
This user manual provides detailed information on the Komfovent RHP Pro air handling unit, covering its functions, control methods, maintenance, and troubleshooting for optimal indoor air quality and climate control in commercial and industrial spaces.