Komfovent SVK Hot Water Air Heater
Construction
- Galvanized steel housing
- Copper tubes for transferring heating medium (water)
- Standard distance between aluminum plates is 3 mm
- Default location for anti-freeze temperature sensor
- Not insulated
Limitations
- Maximum working pressure is 21 bar
- Maximum water temperature is +130°C
- Maximum air velocity through the heater is 3 m/s
Technical Specifications (Water Temperature 80/60°C)
Model | Air flow, m³/h | Heating power consumption, kW | Air temperature to / from, °C | Differential pressure, Pa | Internal volume of heat exchanger, dm³ | Hydraulic pressure loss, kPa |
---|---|---|---|---|---|---|
SVK-400×200-2 | 850 | 6,3 | 0/22 | 33 | 0,8 | 25 |
SVK-400×200-4 | 850 | 12,8 | -23/22 | 65 | 1,3 | 26 |
SVK-500×250-2 | 1500 | 11,1 | 0/22 | 62 | 0,9 | 11 |
SVK-500×250-4 | 1500 | 22,6 | -23/22 | 132 | 1,5 | 13 |
SVK-500×300-2 | 1800 | 13,4 | 0/22 | 57 | 1,1 | 19 |
SVK-500×300-4 | 1800 | 27,2 | -23/22 | 122 | 2,1 | 21 |
SVK-600×300-2 | 2300 | 17,1 | 0/22 | 64 | 1,2 | 34 |
SVK-600×300-4 | 2300 | 34,7 | -23/22 | 138 | 2,3 | 20 |
SVK-600×350-2 | 2600 | 19,3 | 0/22 | 58 | 1,5 | 16 |
SVK-600×350-4 | 2600 | 39,2 | -23/22 | 123 | 2,8 | 17 |
SVK-700×400-2 | 4000 | 29,7 | 0/22 | 113 | 3,1 | 45 |
SVK-700×400-4 | 4000 | 60,4 | -23/22 | 235 | 6,4 | 46 |
SVK-800×500-2 | 4500 | 33,4 | 0/22 | 84 | 4,1 | 10 |
SVK-800×500-4 | 4500 | 67,9 | -23/22 | 177 | 8,5 | 14 |
SVK-1000×500-2 | 5700 | 42,3 | 0/22 | 86 | 4,9 | 17 |
SVK-1000×500-4 | 5700 | 86,0 | -23/22 | 182 | 10,1 | 24 |
Dimensions and Connections
Model | Dimensions, mm b x h |
B | H | L | Connection diameter, mm (″) | Code | Weight, kg |
---|---|---|---|---|---|---|---|
SVK-400×200-2 | 400×200 | 480 | 320 | 100 | 15 (½″) | 761020001 | 5,0 |
SVK-400×200-4 | 400×200 | 517 | 320 | 130 | 15 (½″) | 761020003 | 7,0 |
SVK-500×250-2 | 500×250 | 617 | 320 | 100 | 15 (½″) | 761020005 | 6,0 |
SVK-500×250-4 | 500×250 | 617 | 320 | 130 | 15 (½″) | 761020007 | 9,0 |
SVK-500×300-2 | 500×300 | 617 | 380 | 100 | 15 (½″) | 761020009 | 7,0 |
SVK-500×300-4 | 500×300 | 623 | 380 | 130 | 20 (¾″) | 761020011 | 12,0 |
SVK-600×300-2 | 600×300 | 717 | 380 | 1 | 15 (½″) | 761020013 | 8,0 |
SVK-600×300-4 | 600×300 | 723 | 380 | 130 | 20 (¾″) | 761020015 | 13,0 |
SVK-600×350-2 | 600×350 | 717 | 440 | 100 | 15 (½″) | 761020017 | 9,0 |
SVK-600×350-4 | 600×350 | 723 | 440 | 130 | 20 (¾″) | 761020019 | 15,0 |
SVK-700×400-2 | 700×400 | 817 | 500 | 100 | 15 (½″) | 761020021 | 12,0 |
SVK-700×400-4 | 700×400 | 830 | 500 | 130 | 25 (1″) | 761020023 | 18,0 |
SVK-800×500-2 | 800×500 | 923 | 560 | 100 | 20 (¾″) | 761020025 | 14,0 |
SVK-800×500-4 | 800×500 | 937 | 560 | 130 | 32 (1 ¼″) | 761020027 | 21,0 |
SVK-1000×500-2 | 1000×500 | 1123 | 560 | 100 | 20 (¾″) | 761020029 | 16,0 |
SVK-1000×500-4 | 1000×500 | 1137 | 560 | 130 | 32 (1 ¼″) | 761020031 | 25,0 |
ORDER EXAMPLE: hot water heater SVK-400×200-2.