Product Description: The D9412GV3 Control Panel is a powerful solution for integrated intrusion, access control, and fire alarm system applications.
Key Features and Capabilities
The D9412GV3 Control Panel offers:
- Fully integrated intrusion, fire, and access control, allowing users to interface with one system instead of three.
- Conettix IP-based communication options for high-speed, secure alarm transport and control via up to two wired (DX4020) and/or wireless (ITS-DX4020-G) network interfaces.
- Up to 32 programmable areas with perimeter and interior partitioning.
- 246 points with flexible configuration options to meet multiple installation requirements.
- Commercial Wireless support for up to 238 RF points.
The control panel includes a communicator that sends events to selected public switched telephone network (PSTN), IP network, or general packet radio service (GPRS) destinations through four programmable route groups. It provides up to 246 individually identified points, each capable of accommodating normally-open (NO) and normally-closed (NC) devices with end-of-line (EOL) resistor supervision, and programmable for fire, fire supervisory, or intrusion applications.
With the D9412GV3, users can:
- Monitor alarm points for intruder or fire alarms while operating user keypads and other outputs.
- Program all system functions locally or remotely (attended or unattended) through Remote Programming Software (RPS), or program critical parameters on-site via a keypad.
- Add up to eight doors of access control using the optional D9210BLC Access Control Interface Module.
Functions
Programmable Outputs
- 2 A alarm power at 12 VDC
- 1.4 A auxiliary power at 12 VDC
- Four alarm-output patterns
- Programmable bell test
System Response
- High-performance microcontroller providing industry-leading system response.
- 31 custom point indexes, including fire supervisory.
- Selectable point response time.
- Cross point capability.
- Fire alarm verification.
- Fire inspector's local test.
- Watch mode.
- Scheduled events (skeds) for arming, disarming, bypassing, unbypassing points, controlling relays, authority levels, and door access.
User Interface
- Supervision of up to 16 keypads (up to 32 unsupervised keypads can be used).
- Custom keypad text is fully programmable, including remote programming.
Advanced Features and Configurations
User Authority and Area Management
- Full function command menu including custom functions.
- Authority by area and 16-character name for each user.
- 14 custom authority levels control user's authority to change, add, or delete passcodes or access control credentials; to disarm or bypass points; and to start system tests.
Area Configurations
Area programming offers a wide selection of different system configurations. Each area is assigned an account number to define annunciation, control, and reporting functions. Multiple areas can be linked to a shared area (e.g., hallway or lobby) for automatic control. Area arming can be conditional on other areas (master or associate). Any area can be configured for perimeter and interior arming without requiring a separate area.
Security Protocols
- Two Man Rule: Requires two people present at opening or two unique passcodes on the same keypad to disarm an area, enhancing security.
- Early Ambush: Requires two passcode entries on the same keypad. The first entry disarms the area, and the second entry initiates a timer to send a duress event if not completed within the programmed time. This allows users to inspect premises safely.
- Easy Exit Control: Allows the control panel to change from one armed state to another without disarming, simplifying operation.
- Programmable Passcode-controlled Menu List: Displays menu options based on user authority, simplifying operation.
- Passcode Follows Scope: Restricts passcode arming and disarming to the keypad's local area, even if the keypad can report events from other areas.
- Invisible Walk Test: A menu item allows testing of 24-hour points without sending reports to the central station.
- Door-Activated Custom Function: Activates a custom function when user credentials are presented to a D9210B door controller's reader, mimicking keypad functions.
Passcodes
User passcodes are three to six digits. Each user can be assigned one of 14 customized authority levels per area. Passcodes can be restricted to operate only during certain times. The Two Man Rule and Early Ambush options require two passcodes for enhanced security in financial establishments.
Communications and Connectivity
Communications
The D9412GV3 Control Panel prioritizes and sends reports in Contact ID or Modem IIIa² formats to four programmable route groups, each with primary and backup destinations. It provides flexible communications for most central stations, supporting individual point numbers, opening/closing reports, remote programming attempts, and diagnostic reports.
The panel utilizes the DX4020 Ethernet Network Interface Module and/or the ITS-DX4020-G GPRS/GSM Communicator to connect with Conettix D6600 and D6100i Communications Receiver/Gateways. Conettix IP communication offers a secure path with anti-replay/anti-substitution features and encryption. Both modules support remote programming.
Security and Fire Detection
The D9412GV3 provides eight on-board points and up to 238 additional off-board points (depending on model and expansion interfaces). Individual points can be programmed to monitor various alarm types, including burglar alarms, fire alarms, and supervision devices.
Commercial Wireless
The Commercial Wireless platform, powered by Inovonics wireless mesh network technology, ensures superior range, reliability, and scalability for commercial applications. This proven technology offers flexibility and performance. It sends redundant information on multiple frequency channels within the FCC Part 15 900 MHz band, providing enhanced range and reliability compared to single-frequency systems.
Event Management and Access Control
Event Log
The event log stores up to 1,000 local and transmitted events, including time, date, event, area, point, and user number. Events can be viewed from a keypad or retrieved remotely using RPS. RPS operators can retrieve events periodically via a single phone call. The system can send optional reports when the event log reaches a programmed threshold.
Access Control
The D9412GV3 supports custom door strike, point shunt, and auto disarming response by area. It features 14 panel-wide access levels with manual and scheduled control. Users can store, view, or print access events such as 'Access granted', 'No entry', 'Request-to-enter', and 'Request-to-exit'.
Scheduled Events (Skeds)
The internal clock and calendar manage scheduled events (skeds) to perform functions like arming/disarming, relay control, or point bypassing. The D9412GV3 offers:
- 40 scheduled events with up to 25 different functions.
- Eight opening windows and eight closing windows.
- Eight user windows.
- Day-of-week, date-of-month, or holiday-only schedules.
- Four holiday schedules covering up to 366 days each (leap year).
Fire Test
When Fire Test Mode is activated, the control panel suppresses all reports to the central station. The keypad and annunciator display testing data. An automatic sensor reset feature saves time, eliminating manual sensor resets. At the end of the test, the keypad indicates the number of untested points.
Programming, Diagnostics, and Updates
Programming, Diagnostics, and Controls
Installers can perform limited on-site programming using a keypad for critical parameters (e.g., Account IDs, Central Station and RPS IP addresses, phone numbers, reporting formats). Full programming can be done on-site or remotely (attended or unattended) with RPS. A programmable system passcode prevents unauthorized remote programming.
D9412GV3 Control Panels support up to four separate destinations for primary, alternate, and backup receivers for automatic test reports. User identification (name and number) is logged when resetting alarms or arming/disarming the system.
ROM Updates
An on-site flash update key allows for easy feature enhancements without requiring ROM chip replacement.
Commercial Fire Alarm Support
The system is suitable for Commercial Fire applications compliant with UL 864, 9th Edition.
Certifications and Approvals
Region | Certification | Details |
---|---|---|
USA | UL | AMCX: Central Station Alarm Units (ANSI/UL 1610 and 1635); AMTB: Control Panels, SIA False Alarm Reduction (UL 864 and ANSI/SIA CP-01-2000); AOTX: Local Alarm Units (ANSI/UL 609 and ANSI/UL 464); APAW: Police Station Alarm Units (ANSI/UL 365 and ANSI/UL 464); APOU: Proprietary Alarm Units (ANSI/UL 1076); NBSX: Household Burglar Alarm System Units (ANSI/UL 1023); UOJZ: Control Units, System (ANSI/UL 864); UTOU: Control Units and Accessories, Household System Type (ANSI/UL 985) |
FM | 7167-1615:0239 CONTROL UNIT (HOUSEHOLD) | |
CSFM | 7165-1615:0238 FIRE ALARM CONTROL UNIT (COMMERCIAL) | |
CSFM | 7167-1615:0239 | |
FDNY CoA | 6059 [D9412GV3 & D7412GV3] |
FCC: Designed to comply with Part 15.
Installation and Configuration Notes
Compatible Products
Keypads
- D1260 Series Keypads (D1260, D1260W, D1260R, D1260BLK, D1260B)
- D720 Series Keypads (D720, D720W, D720R, D720B)
- D1255 Series Keypads (D1255, D1255W, D1255B, D1255RB)
- D1256RB Fire Keypad
- D1257RB Remote Fire Alarm Annunciator
- D1265 Touch Screen Keypad
- D279A Independent Zone Control
Detectors
- D7050 Series Addressable Photoelectric Smoke and Smoke Heat Detector Heads
- F220-B6PM/S Addressable Detector Bases with POPITS
- MX775i Addressable PIR Detector
- MX794i Long Range Multiplex PIR Detector
- MX934i Addressable PIR Detector
- MX938i Addressable PIR Detector
- ZX776Z PIR Detector
- ZX794Z Long Range PIR Detector
- ZX835 TriTech Microwave/PIR Detector
- ZX935Z PIR Detector
- ZX938Z PIR Detector
- ZX970 PIR/Microwave Detector
- Bosch conventional detectors (Blue Line, seismic, PIR, TriTech PIR Microwave, photoelectric, heat, and smoke).
Enclosures
- D8103 Universal Enclosure
- D8108A Attack-resistant Enclosure
- D8109 Fire Enclosure
Magnetic Contacts
Bosch magnetic contacts include recessed, terminal connection, miniature, overhead door, and surface mount types.
Modules
- Conettix ITS-DX4020-G GPRS/GSM Integrated Communicator
- Conettix DX4020 Network Interface Module
- Conettix DX4010V2 USB/Serial Interface Module
- Conettix C900V2 Dialer Capture Module
- D113 Battery Lead Supervision Module
- D125B Dual Class B Initiating Module
- D127 Reversing Relay Module
- D129 Class A Initiating Module
- D130 Auxiliary Relay Module
- D185 Reverse Polarity Signaling Module
- D192G Notification Appliance Circuit Module
- D928 Phone Line Switcher
- D5060 MUX Programmer
- D8125 POPEX Point Expander
- D8128D OctoPOPIT Eight-point Expander
- D8125MUX Point Expander
- D8125INV Wireless Interface Module
- D8129 Octo-relay Module
- D8130 Door Release Module
- D9127 Series POPIT Modules
- D9131A Parallel Printer Interface Module
- D9210BLC Access Control Interface Module
- DS7432 Eight-input Remote Module
- DS7457i Series Single-zone Multiplex Input Modules
- DS7460i Two-input Module
- DS7461i Single-input Multiplex Module
- DS7465i Input and Output Module
- ICP-SDI-9114 SDI Splitter
Programming
- RPS or RPS-LITE Remote Programming Software
Readers
- ARD-R10 iCLASS Mullion Reader
- ARD-R40 iCLASS Switchplate Reader
- ARD-RK40-09 iCLASS PIN Reader
- ARD-VSMART iCLASS Reader
- D8223 Prox Pro Reader
- D8224 Mullion Reader
- D8224-SP Switch Plate Reader
- D8225 Mini Mullion Reader
- D8301W Low-profile Proximity Readers
Commercial Wireless Products
- ISW-D8125CW Commercial Wireless Interface
- ISW-EN7280 Serial Receiver
- ISW-EN4200 Serial Receiver
- ISW-EN4204R LED Receiver
- ISW-EN4216R LCD Receiver
- ISW-EN4016SK Survey Receiver
- ISW-EN5040-T High-power Repeater
- ISW-EN1210 Universal Transmitter (Single-input)
- ISW-EN1210EOL Universal Transmitter with EOL Resistor
- ISW-EN1210SK Survey Transmitter
- ISW-EN1210W Door-Window Transmitter with Reed Switch
- ISW-EN1215EOL Universal Transmitter with Wall Tamper and EOL Resistor
- ISW-EN1215WEOL Door-Window Transmitter with Wall Tamper, Reed Switch, and EOL Resistor
- ISW-EN1223D Water-resistant Pendant Transmitter (Double-button)
- ISW-EN1223S Water-resistant Pendant Transmitter (Single-button)
- ISW-EN1223SK Survey Pendant Transmitter
- ISW-EN1233D Necklace Pendant Transmitter (Double-button)
- ISW-EN1233S Necklace Pendant Transmitter (Single-button)
- ISW-EN1235D Beltclip Pendant Transmitter (Double-button)
- ISW-EN1235S Beltclip Pendant Transmitter (Single-button)
- ISW-EN1235DF Fixed-location Transmitter (Double-button)
- ISW-EN1235SF Fixed-location Transmitter (Double-button)
- ISW-EN1242 Smoke Detector-Transmitter
- ISW-EN1247 Glassbreak Sensor-Transmitter
- ISW-EN1249 Billtrap Transmitter
- ISW-EN1260 PIR Motion Sensor Transmitter (Commercial and High-end Domestic Applications)
- ISW-EN1261HT PIR Motion Sensor Transmitter (High-traffic Areas)
- ISW-EN1262 PIR Motion Sensor Transmitter (Residential and Low-traffic Commercial Applications)
- ISW-EN1265 PIR Motion Sensor Transmitter (Ceiling-mount Applications)
Parts Included and Technical Specifications
Parts Included
The D9412GV3 includes the following parts:
Quant. | Component |
---|---|
1 | D9412GV3 Board |
1 | Mounting Skirt |
1 | Faceplate with D9412GV3 Label |
1 | Literature pack (Installation Instructions, Owners Manual, Release Notes) |
1 | Literature CD containing all product literature |
The available kits include:
Components | Kit -A | Kit -B | Kit -C |
---|---|---|---|
D9412GV3 Board | 1 | 1 | 1 |
D101F Lock and Key Set | 1 | ||
D122 Dual Battery Harness | 1 | ||
D161 Dual Modular Phone Cord | 2 | ||
D928 Dual Phone Line Switcher | 1 | ||
D1640 Transformer | 1 | 1 | |
D8103 Enclosure | 1 | ||
D8108A Attack-resistant Enclosure | 1 | ||
D8109 Fire Enclosure | 1 |
Technical Specifications
Communications
- SDI Bus A (+): 9 VDC, 457.2 m (15,000 ft)
- SDI Bus B (-): 9 VDC, 457.2 m (15,000 ft)
- Telephone Connection: One telephone line; D928 Dual Phone Line Module required for two telephone lines.
Environmental Considerations
- Relative Humidity: 5% to 93% at +30°C (+86°F), non-condensing.
- Temperature (Operating): 0°C to +50°C (+32°F to +122°F).
System Parameters
- Areas: 8
- Card Readers (Doors): 8
- Credentials (Tokens): 996
- Custom Functions: 16
- Events: Up to 1000
- Passcode Users: 249, plus 1 service passcode
- Parallel Printers: 3
- Points: 246 (8 on-board, up to 238 off-board)
- Programmable Relay Outputs: 131
- RF Points: 238
- SKEDS: 64
Power Requirements
- Current Draw (Maximum): 300 mA
- Output (Alarm): 2 A at 12 VDC
- Output (Auxiliary, Continuous Power, and Switched Auxiliary combined): 1.4 A at 12 VDC nominal
- Voltage (Operating): 12 VDC nominal
- Voltage (AC): 16.5 VAC 40 VA plug-in transformer (D1640)
Trademarks
Trademark names are used throughout this document. In most cases, these designations are claimed as trademarks or registered trademarks by their respective owners. Bosch Security Systems, Inc. uses these names in an editorial fashion for the benefit of the trademark owner, with no intention of infringing the trademark.
Inovonics is a trademark of Inovonics Wireless Corporation.
Ordering Information
Control Panel Packages
- D9412GV3 Control Panel: Includes PCB, mounting skirt, faceplate, literature pack, and CD. Order number: D9412GV3.
- D9412GV3-A Attack-resistant Package: Contains PCB, transformer, and attack-resistant enclosure. Order number: D9412GV3-A.
- D9412GV3-B Fire/Burglar Package: Contains PCB, dual battery harness, two telephone cords, telephone line switcher, transformer, and fire enclosure. Order number: D9412GV3-B.
- D9412GV3-C Standard Burglar Package: Contains PCB, lock and key set, transformer, and universal enclosure. Order number: D9412GV3-C.
Accessories
- ICP-SDI-9114 SDI Splitter: Enables setup of two independent SDI buses from a single SDI connection. Order number: ICP-SDI-9114.
- D928 Dual Phone Line Switcher: Allows operation over and supervision of two separate phone lines. Requires additional D161 or D162 phone cords. Order number: D928.
- D110 Tamper Switch: Screw-on tamper switch for enclosures. Shipped in packages of two. Order number: D110.
- ICP-EZTS Dual Tamper Switch: Combination tamper switch with wire loop for additional tamper outputs. Order number: ICP-EZTS.
- D101 Lock and Key Set: Short-body lock set with one key. Uses D102 replacement key. Order number: D101.
- D122 Dual Battery Harness: Harness with circuit breaker to connect two batteries. Order number: D122.
- D122L Dual Battery Harness with Long Leads: Color-coded harness with circuit breaker and leads (89 cm / 35 in.). Order number: D122L.
- D126 Standby Battery (12 V, 7 Ah): Rechargeable sealed lead-acid power supply for secondary or auxiliary functions. Order number: D126.
- D1218 Battery (12 V, 18 Ah): 12 V sealed lead-acid battery with bolt-fastened terminals. Includes hardware for battery leads or spade connectors. Order number: D1218.
- D1224 Battery (12 V, 26-28 Ah): 12 V sealed lead-acid battery with bolt-fastened terminals. Includes hardware for battery leads or spade connectors. Order number: D1224.
- D137 Mounting Bracket: For mounting accessory modules in D8103, D8108A, and D8109 enclosures. Order number: D137.
- D138 Mounting Bracket, Right Angle: For mounting accessory modules in D8103, D8108A, and D8109 enclosures. Order number: D138.
- D1640 Transformer: System transformer rated at 16.5 VAC, 40 VA. Order number: D1640.
- D8004 Transformer Enclosure: For applications like fire alarms requiring a transformer enclosure. Order number: D8004.
- D8103 Enclosure: Grey steel enclosure (41 cm x 41 cm x 9 cm / 16 in. x 16 in. x 3.5 in.). Order number: D8103.
- D8108A Attack Resistant Enclosure: Grey steel enclosure (41 cm x 41 cm x 9 cm / 16 in. x 16 in. x 3.5 in.). UL Listed. Includes lock and key set. B520, B4512, and B5512 require the B12 mounting plate. Order number: D8108A.
- D8109 Fire Enclosure: Red steel enclosure (40.6 cm x 40.6 cm x 8.9 cm / 16 in. x 16 in. x 3.5 in). UL Listed. Includes lock and key set. Order number: D8109.
- D9002-5 Mounting Skirt: Mounts inside D8103, D8108A, and D8109 enclosures. Can accept up to six standard 7.62 cm x 12.7 cm (3 in. x 5 in.) cards. Order number: D9002-5.
Software Options
- RPS Kit (USB): Account management and control panel programming software with USB security key (dongle). Order number: D5500C-USB.
Represented By
Americas: Bosch Security Systems, Inc., 130 Perinton Parkway, Fairport, New York, 14450, USA. Phone: +1 800 289 0096. Fax: +1 585 223 9180. Email: security.sales@us.bosch.com. Website: www.boschsecurity.us
Europe, Middle East, Africa: Bosch Security Systems B.V., P.O. Box 80002, 5617 BA Eindhoven, The Netherlands. Phone: +31 40 2577 284. Fax: +31 40 2577 330. Email: emea.securitysystems@bosch.com. Website: www.boschsecurity.com
Asia-Pacific: Robert Bosch (SEA) Pte Ltd, Security Systems, 11 Bishan Street 21, Singapore 573943. Phone: +65 6571 2808. Fax: +65 6571 2699. Email: apr.securitysystems@bosch.com. Website: www.boschsecurity.asia
China: Bosch (Shanghai) Security Systems Ltd., 201 Building, No. 333 Fuquan Road, North IBP, Changning District, Shanghai 200335 China. Phone: +86 21 22181111. Fax: +86 21 22182398. Website: www.boschsecurity.com.cn
America Latina: Robert Bosch Ltda Security Systems Division, Via Anhanguera, Km 98, Campinas, Sao Paulo, Brazil, CEP 13065-900. Phone: +55 19 2103 2860. Fax: +55 19 2103 2862. Email: latam.boschsecurity@bosch.com. Website: www.boschsecurity.com
Bosch Security Systems © 2014 | Data subject to change without notice. Document number: 2491786379 | Version: en, V6, 27. May 2014