Copeland XR30CHC Digital Controller with Bluetooth Connectivity
Model: XR30CHC
Version: 82 rel. 1.0.1
1 General Warnings
1.1 Please Read Before Using This Manual
This manual is part of the product and should be kept near the instrument for easy and quick reference. The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. Check the application limits before proceeding. Copeland Controls S.r.l. reserves the right to change the composition of its products, even without notice, ensuring the same and unchanged functionality.
1.2 Safety Precautions
- Check the supply voltage is correct before connecting the instrument.
- Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high atmospheric humidity to prevent formation of condensation.
- Warning: disconnect all electrical connections before any kind of maintenance.
- Fit the probe where it is not accessible by the End User. The instrument must not be opened.
- In case of failure or faulty operation send the instrument back to the distributor or to "Copeland Controls S.r.l." (see address) with a detailed description of the fault.
- Consider the maximum current which can be applied to each relay (see Technical Data).
- Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining.
- In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful.
2 General Description
The XR30CHC, 32x74x60mm format, is a microprocessor-based controller suitable for applications on medium or low temperature ventilated refrigeration units. It has 2 relay outputs to control compressor and fans, light or defrost. The device is also provided with up to 3 NTC, PTC or PT1000 probe inputs to control temperature, to manage the condenser and for visualization purpose. There are also two configurable digital inputs. By using the HOT-KEY it is possible to program the instrument in a quick and easy way. The controller has Bluetooth 4.2 connectivity.
3 Regulation
The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential, the compressor will start. The compressor will stop when the temperature reaches the set point value again.
Diagram: A graph showing temperature on the Y-axis and time on the X-axis. A line represents the temperature, with two thresholds marked: 'SET' and 'SET + HY'. The compressor is shown to turn ON when the temperature crosses 'SET + HY' and OFF when it crosses 'SET'.
4 Energy Saving Algorithm
4.1 Description
The device permits to set different temperature to be used during normal and reduced power use. The standard SET-POINT (SET) is used to maintain the temperature at a certain value when the energy saving status (ES) is not active. On the other side, when the ES status is active a different SET-POINT (SET_ES), higher than the standard one, will be used. The parameter HES will have to be set to change the regulation temperature according to the following formula: SET_ES = SET + HES
There are also two different differential values for SET and SET_ES, which are used for compressor cut-in and cut-out: when ES status is active the HYE parameter will be used instead of the HY parameter.
4.2 Basic Energy Saving Algorithm
The energy saving status will be always saved in the internal memory to resume previous operation if a power failure occurs. It needs the presence of a door switch to work (for example: i1F=dor).
4.2.1 Parameters Involved
- i1F or i2F: set as door input to monitor the appliance usage
- StE: interval to change from normal to energy saving mode
- EtS: interval to change from energy saving to normal mode
- HES: differential for SETPOINT when energy saving mode active
- HYE: differential for regulation when energy saving mode is active
- dS: interval for door opening detection
- LdE: light output controlled (OFF when energy saving mode is active)
Diagram: Two tables showing state transitions. One table shows transitions from Normal to Energy Saving mode, triggered by conditions like 'Pushing the DOWN button for 3 sec (if enabled)' or 'Door continuously closed for the StE time'. The other table shows transitions from Energy Saving to Normal mode, triggered by conditions like 'Controller in ES mode for the Ets time' or 'If the controller is in ES mode, it returns in Standard mode (normal set-point) after opening the door more than dS time'.
Note: The cycling mode (ES - Normal mode ES etc.) works if i1F=dor and EtS and StE are different from zero. If EtS=0 or StE=0, the controller will not change the operating mode, and it will be possible to change from the normal mode to the energy saving mode by using ES button or by setting i1F=ES.
Diagram: A state transition diagram illustrating the Energy Saving (ES) and Normal modes, showing how the controller switches between them based on time intervals and door status.
Diagram: A state transition diagram illustrating the Energy Saving (ES) and Normal modes, showing how the controller switches between them based on time intervals and door status.
5 Pull Down Function
The Pull Down is automatically activated:
- When the regulation probe temperature T is: T>SET+HY+oHt value in normal mode
- T>SET+HES+HYE+oHE value in energy saving mode
In this case, a different set-point value (SET+CCS) will be enabled. As soon as the room temperature reaches the SET+CCS value, the compressor will be stopped and the normal regulation will restart. NOTE: Pull Down function is disabled when CCS=0 or CCt=0.
The CCt parameter sets the maximum activation time for any pull down. When CCt expires, the Pull Down will be immediately stopped and the standard SET-POINT will be restored.
6 Condenser Fan
6.1 General Description
The condenser fan is can be managed by dedicated control. To enable it, a condenser probe must be selected by using par. FAC. Here follows the description of all the related parameters:
- FAC: to select the condenser fan probe
- St2: to select the condenser fan deactivation setpoint
- HY2: differential for condenser fan activation
- FCC parameter it can be selected the condenser fan working mode:
- FCC=C-n: condenser fan will switch ON and OFF with the compressor and will not run during defrost
- FCC=o-n: condenser fan will run even if the compressor is off, and will not run during defrost
- FCC=C-Y: condenser fan will switch ON and OFF with the compressor and will run during defrost
- FCC=o-Y: condenser fan will run continuously, also during defrost.
7 Defrost
7.1 Defrost Mode
Any defrost operation can be controlled in the following way:
- EdF=rtC: by using an internal real-time clock (only for models equipped with RTC)
- EdF=in: timed defrost, in this case a new defrost will start as soon as the idF timer expires
7.2 Timed Mode
Defrost control is timed only. A couple of parameters is used to control the interval between defrost cycles (idF) and its maximum length (MdF). During the defrost cycle is possible to select some different display indications by using the dFd parameter.
8 Digital Output Configuration
Depending on the model, one or more digital outputs (relays) can be configurated with one of the following functionalities.
8.1 ON/OFF Output (OAX = ONF)
In case of fault because of the thermostat probe, the start and stop of the compressor are timed through parameters CoF and Con.
When oAx=onF, the output is activated when the controller is turned on and de-activated when the controller is turned off.
8.2 Dead Band Regulation
With oAx=db the output can be used to control, for example, a heater element. It is used to implement a dead band regulation. If so:
- oAx=db cut in is SET-HY
- oA1=db cut out is SET
8.3 Alarm Output
With oAx=ALr the output operates as alarm output. It is activated every time an alarm happens. Its status depends on the tba parameter: if tbA=Y, the output is deactivated by pressing any key. If tbA=n, the alarm output stays on until the alarm condition recovers.
8.4 Activation During Energy Saving Cycles
With oAx=HES, the output is activated when the energy saving cycle begins.
9 Front Panel Commands
Diagram: Image of the controller's front panel with a display showing "18.5" and several buttons labeled SET, AUX, and directional arrows (UP/DOWN).
SET: Press to display target set point and the real set point. When in programming mode, it selects a parameter or confirms an operation.
AUX: (AUX/DEF) Programmable button, see par. LGC and LG2.
UP (↑): In programming mode it browses the parameter codes or increases the displayed value. Other functions related to par. UPC and UP2 (if available).
DOWN (↓): In programming mode it browses the parameter codes or decreases the displayed value. Other functions related to the par. dnc and dn2 (if available).
ON/OFF: Keep it pressed for 3 sec to switch on and off the device.
Diagram: A table showing icons, their modes (On/Flashing), and their meanings. Icons include SET, AUX, UP, DOWN, ON/OFF, and various status indicators like compressor enabled, anti-short cycle delay, light output enabled, etc.
9.1 Set Point Menu
The SET key gives access to a quick menu where it is possible to see:
- the set point value
- the real set point value (rSE)
Push and release the SET key five times or wait for 60 sec to return to normal visualization.
9.2 Change the Setpoint
- Push the SET key for more than 3 sec to change the Set point value;
- The value of the set point will be displayed and the "°C" LED starts blinking;
- To change the Set value, push the UP or DOWN button.
- To memorize the new set point value, push the SET button again or wait for 60 sec.
9.3 Start a Manual Defrost
Push the DEFROST button for more than 3 sec to start a manual defrost.
10 Parameter Menu
The device has a parameter menu available from keyboard and where it is possible to modify some specific parameters. A couple of parameter levels are present:
- PR1: user menu, standard parameters are placed into this menu
- PR2: protected menu, application specific parameters are placed here. A password can be used to protect these values from unauthorized modification.
10.1 Menu Navigation
A tree-structured menu is implemented to simplify the parameter browsing and modification. Follow the button functions (valid both in PR1 and PR2):
- SET: used to enter a submenu or a stored value
- UP and DOWN: used to scroll the menu labels, the parameters into a submenu and to modify a parameter value
- AUX/DEF: used to go back to the upper menu level (for example, from a submenu list of parameters to the main menu labels)
10.2 Change a Parameter Value
To change a parameter value, operate as follows:
- Enter the Programming mode by pressing the SET+DOWN buttons for 3 sec ("°C" LED starts blinking).
- Select the required parameter. Press the SET button to display its value
- Use UP or DOWN buttons to change its value.
- Press SET to store the new value and move to the following parameter.
To exit: Press SET+UP buttons or waits for 15 sec without pressing any button.
Note: The modified value will be stored even if the programming mode ends by timeout.
10.3 Protected Level
The Protected Level has all the parameters of the instrument. This level is password protected. The default password is: "000". It is strongly recommended to change the standard password after ending the installing operations.
10.3.1 Enter the Protected Level
- Enter the Programming mode by pressing SET+DOWN buttons for 3 sec (°C or °F LED starts blinking)
- Released the buttons and then search for submenu Pr2
- Per SET button and then insert the password value
- Confirm with SET. If the password is correct, the label "Pr2" will blink for some time and then protected parameter menu will be enabled.
10.3.2 Protected Menu
- Select the parameter to modify
- Press the SET key to display its current value
- Use UP or DOWN to change its value
- Press SET to store the new value and move to the following parameter
To exit: Press SET+UP or wait for 15 sec without pressing any button.
Note:
- If there are no parameters into the User Level, after 3 sec the "nP" label will be displayed. Go to submenu Pr2 and follow the previous procedure.
- The modified value will be stored even if the programming mode ends by timeout.
- Modify the par. PSU (when into Protected Level) to change the current password
10.3.3 Move Parameters Through Levels
Each parameter present into the Protected Level can be moved into the User Level by pressing both SET+DOWN buttons. If a parameter is into the User Level, when visualized into the Protected Level it will have also the decimal point.
10.4 Keyboard Management
10.4.1 Temporary Lock
- Keep both UP and DOWN buttons pressed for more than 3 sec.
- The "OFF" label will be displayed and the keyboard will be locked. If any button is pressed more than 3 sec, the "oFF" message will be displayed.
10.4.2 Temporary Unlock
Keep both UP and DOWN buttons pressed together for more than 3 sec till the "on" message will be displayed.
10.4.3 Advanced Lock Function
It is possible to selectively lock the keyboard by using the following parameters:
- brd: select the kind of lock:
- UnL: all buttons unlocked
- SEL: buttons UP, DOWN and DEFROST are locked
- ALL: all keyboard is locked
- tLC: delay after power-on before activating the advanced lock function
Note: when advanced lock function is active, temporary lock and unlock functions are disabled.
10.5 The ON/OFF Function
If onF = OFF, the instrument will be switched off by pushing the ON/OFF button. The "OFF" message will appear on the display. In this configuration the regulation is disabled. To switch the instrument on, push again the ON/OFF button.
Warning: any load connected to the normally closed contacts of the relays is always supplied from the main voltage, even if the instrument is in standby mode.
11 Parameters
Menu List:
- REG: Regulation: it includes all parameters related to main temperature regulation
- Prb: Probe setup: it includes all parameters related to probe configuration
- dis: Display: it includes all parameters related to the user interface
- dEF: Defrost: it includes all parameters to control any defrost operation
- FAn: Ventilators: it includes all parameters to control the ventilators
- ALr: Alarms: it includes all parameters to set up the alarm conditions
- oUt: Outputs: it includes all parameters to set up the digital outputs
- inP: Inputs: it includes all parameters to set up the digital inputs
- ES: Energy Saving: it includes all parameters to define the energy saving mode
- Cnt: Counters: to see the counters values
- rtC: Real Time Clock: it includes all parameters to set up the internal clock
- bLE: Bluetooth: it includes all parameters to set up the Bluetooth communication
- E2: EEPROM: it includes all parameters to set up the datalogger
- oth: Other: it includes all parameters to set up the serial communication and the keyboard
- vis: Visualization: it includes the read only parameters (probe values and FW info)
12 Digital Inputs
The free voltage digital input is programmable in different configurations by the i1F and i2F.
DOOR SWITCH (ixF=dor)
It signals the door status and the corresponding relay output status through the odC parameter: no = normal (any change); FAn = Fan OFF; CPr = Compressor OFF; F-C = Compressor and fan OFF. Since the door is opened, after the delay time set through parameter did, the door alarm is enabled, the display shows the message “dA” and the regulation restarts if rrd = Y. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled.
START DEFROST (ixF=dEF)
It starts a defrost if there are the right conditions. After finishing any defrost, the normal regulation will restart only if the digital input is disabled, otherwise the instrument will wait until the MdF safety time is expired.
ENERGY SAVING (ixF=ES)
The energy saving mode will be enabled / disabled with the digital input.
MOTION SENSOR (ixF=EMt)
It counts the motion sensor detections.
AUXILIARY OUTPUT (ixF=AUS)
The AUX output (if present and configured) will be enabled / disabled with the digital input.
EXTERNAL WARNING ALARM (ixF=EAL)
It is used to detect an external alarm. It does not lock the regulation.
EXTERNAL LOCK ALARM (ixF=bAL)
It is used to detect any critical external alarm. It locks immediately the regulation.
EXTERNAL PRESSURE ALARM (ixF=PAL)
It is used to detect any pressure external alarm. This signal locks the regulation after nPS events in dxd interval od time.
EVAPORATOR FAN MODE (ixF=FAn)
It is used to control the evaporator fan.
REMOTE HOLYDAY MODE (ixF=HdF)
It is used to force the holyday mode.
REMOTE ONOFF (ixF=onF)
It is used to switch ON and OFF the device remotely.
LIGHT OUTPUT (ixF=LiG)
It is used to control the light output.
CHANGE CONFIGURATION (ixF=CC)
It is used to change the controller configuration.
MOTION SENSOR DETECTOR (ixF=EMt)
To use the X-MOD motion sensor. Please note that the motion sensor can be connected only to the HOTKEY port, so it needs digital input 2 properly configurated.
13 Installation and Mounting
Instrument XR30CHC shall be mounted on vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. The temperature range allowed for correct operation is 0 to 60°C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.
14 Optional Features
- MDP/CX rear cover: The MDP/CX rear cover can be used to increase the protection from water and dust.
- HOT-KEY: The HOT-KEY is used for a quick and easy upload (from device to HOT-KEY) or download (from HOT-KEY to device) the parameter map.
- XJ485LE serial interface: The XJ485LE serial interface converts the TTL output into an RS485 signal that can be used to connect the unit to the controlling and supervising system. Please note that other version of this converter does not work with XR-CHC devices.
15 Electrical Connections
The instrument is provided with screw terminal block to connect cables with a cross section up to 2.5mm². Before connecting cables make sure the power supply complies with the instrument’s requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.
Diagram: Wiring diagram showing terminal connections for the XR30CHC controller, including power supply, probes, relay outputs (Compressor, OA2), Hot Key, and digital inputs.
15.1 Probes
The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
16 Use the Hot-Key
16.1 Save Parameters in a Hot-Key (Upload from Instrument)
- Program one controller with the front keypad.
- When the controller is ON, insert the "HOT-KEY" and push UP button; the "UP" message appears followed a by flashing "End".
- Push "SET" key and the "End" will stop flashing.
- Turn OFF the instrument and then remove the "HOT-KEY". At the end turn the instrument ON again.
Note: the "Err" message appears in case of a failed programming operation. In this case push again the UP button if you want to restart the upload again or remove the "HOT-KEY" to abort the operation.
16.2 Copy Parameters from a Hot-Key (Download Parameter Values)
- Turn OFF the instrument.
- Insert a programmed "HOT-KEY" into the 5-PIN port and then turn the Controller ON.
- The parameter list of the "HOT-KEY" is automatically copied into the controller memory. During this operation the "do" message will blink.
- A flashing "End" label will inform that the operation was successful.
- Remove the "HOT-KEY".
- After some seconds the instrument will restart, using with the new parameters.
Note: the message "Err" is displayed for failed programming. In this case turn the unit off and then on if you want to restart the download again or remove the "HOT-KEY" to abort the operation.
17 Internal Memory
The controller has an internal memory where are stored:
- Two different parameter maps identified as C1 and C2
- Factory default configurations for both C1 and C2 parameters map
The controller is always shipped with:
- Parameter map C1 = factory default configuration C1
- Parameter map C2= factory default configuration C2
Any modification to parameter map C1 or C2 does not change the default factory values. It is possible to change parameter map between C1 and C2 by using a digital input or a button properly configurated (ixF or LG2=CC). It is possible to restore factory defaults values for both C1 or C2 parameters map by using UP2=LdC (Load default configuration) function.
Notes:
- If controller is using C1 parameter map, the factory default configuration C1 will be reloaded overwriting C1 parameter map. The same for parameter map C2.
- The factory default configurations are read only (it is not possible to modify them on the field).
18 Alarm Signalling
Diagram: A table listing alarm labels, their causes, and the resulting output status.
18.1 Alarm Recovery
Probe alarms "P1", "P2" and "P3" start some seconds after the fault in the related probe; they automatically stop some seconds after the probe restarts normal operation. Check connections before replacing the probe. Temperature alarms "HA", "LA", "H2" and "L2" automatically stop as soon as the temperature returns to normal values. It is possible to reset the "EE" alarm by pressing any button. The alarms "EA", "CA" and "dA" will automatically stop as soon as the digital input is disabled. The internal buzzer can be muted by pressing any key if parameter tbA=Y.
19 Technical Data
- Housing: self-extinguishing ABS
- Case: frontal 32x74 mm; depth 60mm
- Mounting: panel mounting in a 71x29mm panel cut-out
- Body Protection: IP20
- Frontal protection: IP65
- Terminal blocks: Screw terminal block ≤ 2.5 mm² wiring
- Power supply: (according to the model) 230Vac ±10%, 50/60Hz; 110Vac ±10%, 50/60Hz
- Power absorption: 3.5VA max
- Display: 3-digit LED, H=14.2 mm
- Inputs: up to 4 NTC, PTC or PT1000 probes
- Digital input: up to 2 voltage free contacts
- Relay outputs: Compressor SPST 16(5)A, 250VAC; OA2: SPDT 8(2)A, 250VAC;
- Data storing: EEPROM
19.1 Standards
19.1.1 The XR30CHC is compliant with the following standards: ETSI EN 300 328 V2.1.1 (2016-11), ETSI EN 301 489-17 V3.1.1 (2016-11), IEC EN 60730-2-9: 2008 (Third Edition) and Am. 1:2011 in conjunction with IEC 60730-1:2010 (Fourth Edition), UL 60730-1 Fourth Edition and CAN/CSA-E60730-1:02 Third Edition along with its Amendment 1 dated February 2007, the Standards for Automatic electrical controls for household and similar use - Part 1: General requirements.
It therefore meets the essential requirements of the following Directives: Radio equipment Directive 2014/53/EU, Electromagnetic compatibility 2004/108/EC, Low Voltage equipment 2006/95/EC.
19.1.2 FCC 15.247
19.1.3 The XR30CHC is compliant with the following standards: THE XR30CHC IS COMPLIANT TO PART 15 OF THE FCC RULE. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Unauthorized repairs, changes or modifications could result in permanent damage to the equipment and void your warranty and your authority to operate this device under Part 15 of the FCC Rules.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
19.1.4 The XR30CHC is compliant to RSS 102
This device complies with Industry Canada RSS-210. Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
19.1.5 CET XR30CHC INSTRUMENT REPOND AUX NORMES RSS 102
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio RSS-210. L'exploitation est autorisée aux deux conditions suivantes: (1) l'appareil ne doit pas produire de brouillage, et (2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le fonctionnement.
20 Wirings
20.1 XR30CHC, 16+8+8AMP
Diagram: A detailed wiring diagram showing the terminal connections for the XR30CHC controller, including power supply, probe connections, relay outputs (Compressor, OA2), Hot Key port, and digital inputs.
Power Supply (terminals 5-6): 110 or 230 Vac @50 or 60Hz
21 Bluetooth Communication
The controller implements a Bluetooth 4.2 communication module. This gives the possibility to communicate with external devices (for example with a mobile APP able to recognize and decode the device). All controllers use a unique MAC-ADDRESS, which is used both for identification and communication. The communication range is about 5 m (worst case, indoor coverage in presence of obstacles). Over this distance it is possible to suffer interruptions in the communication or quality degradation of the communication. A 6-digit pairing secure code can be required for connection. Please follow the Copeland Connected APP instruction for more information.
21.1 First Installation
After installation, it will be possible to manage the controller by using the Copeland Connected APP. It will be required to:
- Install the Copeland Connected APP on your mobile device (smartphone or tablet)
- Create a new user account before using the APP
The owner is the only account that can:
- Manage the controller via Bluetooth
- Extend rights of access to a specific appliance also to other users
A Cloud portal will be used for:
- Extend rights of access to a specific appliance also to other users
- Select the permission level for any new user
The link for opening the Cloud webpage is on the left side menu of the mobile APP (slide right the screen of the APP when on the Device List page and follow the "Cloud management" link. Please note that the login and password for the Cloud webpage are the same of the mobile APP.
21.2 Reset to Factory Default
In case a factory reset is required, please follow these operations:
- Access to the Cloud webpage and select the appliance you want to reset (search for name and/or MAC-ADDRESS)
- Click on the "DELETE" link, the appliance will be removed from the list of owned appliances
- Go to the device controller (with the same MAC-ADDRESS)
- Enter the programming mode
- Go to the "bLE" menu
- Select the par. rPS (reset device ownership)
- Select "Y" and confirm with SET button
- Select the par. rLi (reset device whitelist)
- Select "Y" and confirm with SET button
- Exit from the programming menu
- Logout and login from the mobile APP
After this, the controller will be reset to factory default configuration and it will be ready for a new association.
File Info : application/pdf, 6 Pages, 631.70KB
DocumentDocumentRelated Documents
![]() |
Copeland XR02CH Digital Controller User Manual Comprehensive guide to the Copeland XR02CH digital controller, covering general warnings, safety precautions, general description, regulation modes (cooling and heating), defrost functions, front panel commands, parameter settings, alarm signaling, wiring, installation, and technical data. |
![]() |
Copeland FULL TOUCH XH78T Quick Start Guide This document provides a quick start guide for the Copeland FULL TOUCH XH78T digital temperature controller, detailing its features, user interface, technical specifications, and safety information. |
![]() |
Copeland XR70CHC Digital Controller with Bluetooth Connectivity User Manual Explore the features and functionalities of the Copeland XR70CHC digital controller, a versatile solution for refrigeration units, offering Bluetooth connectivity, advanced regulation, and energy-saving algorithms. This manual provides comprehensive guidance on installation, operation, and parameter settings. |
![]() |
Copeland XM679K Controllers: Installation and Operation Guide Comprehensive guide for Copeland XM679K controllers, detailing installation, wiring, programming, and operation for multiplexed cabinets. Includes technical specifications and safety precautions. |
![]() |
Universal-XR Unit of Measure Change Instructions A comprehensive guide to the Copeland Universal-XR microprocessor-based controller, covering installation, quick start-up, parameter configuration, button functions, alarms, troubleshooting, and technical specifications for refrigeration applications. |
![]() |
Copeland XER Cold Room Temperature Controller Installation Guide Comprehensive installation guide for the Copeland XER Cold Room Temperature Controller, covering user interface, regulation, defrost operations, wiring, and technical specifications. |
![]() |
Copeland XR60CHC Digital Controller with Bluetooth Connectivity Manual Comprehensive manual for the Copeland XR60CHC digital controller, detailing its features, installation, operation, and technical specifications, including Bluetooth connectivity. |
![]() |
Copeland Discus Digital Upgrade Procedures for Refrigeration Compressors This document outlines the upgrade procedures for Copeland Discus Digital and Intelligent Store Discus v2.x compressors, detailing the conversion of the head and valve plate, wiring the digital components, and programming the controller for enhanced capacity control. |