Copeland Digital Controller XR02CH FW 1.1

1. GENERAL WARNINGS

1.1 PLEASE READ BEFORE USING THIS MANUAL

1.2 SAFETY PRECAUTIONS

2. GENERAL DESCRIPTION

The XR02CH, format 32x74x60mm, is a microprocessor-based controller, suitable for applications on medium or low temperature ventilated refrigerating units. It has 1 relay output to control the compressor. The device has an NTC probe input for temperature control. A configurable free-of-voltage digital input is present with various functionalities. The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX, to a network line ModBUS-RTU compatible such as the monitoring units of X-WEB family. It allows to program the controller by means of the HOT KEY programming keyboard. The instrument is fully configurable through special parameters that can be easily programmed through the keyboard.

3. REGULATION

3.1 TYPE OF REGULATION

The regulation is performed according to the temperature measured by probe. The XR01CX is provided with the CH programmable parameter which enables the user to set the regulation both for heating or cooling applications:

3.2 COOLING APPLICATION

The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point: if the temperature increases and reaches set point plus differential the compressor is activated and then turned off when the temperature reaches the set point value again.

A visual representation of this process shows temperature on the Y-axis and time on the X-axis. The compressor is OFF until the temperature reaches SET + HY, then it turns ON. It remains ON until the temperature drops back to SET, at which point it turns OFF.

3.3 HEATING APPLICATION

The regulation is performed according to the temperature measured by the thermostat probe with a negative differential from the set point: if the temperature decreases and reaches set point minus differential, the heating output is activated and then turned off when the temperature reaches the set point value again.

A visual representation of this process shows temperature on the Y-axis and time on the X-axis. The heating output is OFF until the temperature drops to SET - HY, then it turns ON. It remains ON until the temperature rises back to SET, at which point it turns OFF.

4. DEFROST

Defrost is controlled by parameters:

5. FRONT PANEL COMMANDS

The front panel features a display and several keys for control and programming.

SET Key

To display target set point, in programming mode it selects a parameter or confirms an operation.

DEF Key

(DEF) To start a manual defrost.

UP Key

(UP) In programming mode it browses the parameter codes or increases the displayed value.

DOWN Key

(DOWN) In programming mode it browses the parameter codes or decreases the displayed value.

ON/OFF Key

To put the controller in "OFF" or "ON" mode.

KEYS COMBINATION

LED Indicators

LEDMODEDESCRIPTION
CompressorOnCompressor enabled
FlashingCompressor activation delay active (during AC time)
DefrostOnCompressor stop for micro-door
FlashingDefrost in progress
FlashingDefrost delay active (during time dd)
OnDripping in progress (during time dt)
AlarmsOnAlarms happened
FlashingAlarms happened

5.1 HOW TO SEE THE SET POINT

  1. Push and immediately release the SET key, the set point will be showed.
  2. Push and immediately release the SET key or wait about 5s to return to normal visualization.

5.2 HOW TO CHANGE THE SETPOINT

  1. Push the SET key for more than 2 seconds to change the Set point value.
  2. The value of the set point will be displayed and starts blinking.
  3. To change the Set value push the UP or DOWN arrows within 10s.
  4. To memorize the new set point value push the SET key again or wait 15s.

5.3 HOW TO START A MANUAL DEFROST

Push the DEF key for more than 2 seconds and a manual defrost will start, the pre-condition is evaporator probe temp lower than dE.

5.4 HOW TO CHANGE A PARAMETER VALUE

  1. Enter the Programming mode by pressing the SET+UP keys for 3s.
  2. Select the required parameter.
  3. Press the "SET" key to display its value (set value starts to blink).
  4. Use UP or DOWN to change its value.
  5. Press "SET" to store the new value and move to the following parameter.

To exit: Press SET+UP or wait 15s without pressing a key.

NOTE: the set value is stored even when the procedure is exited by waiting the time-out to expire. Please restart the controller after changing the parameters.

5.5 HOW TO RESET TO THE FACTORY PARAMETER VALUE

In the first 60s after controller power-on, it allows the user to reset to the factory parameters through key combination with steps below:

  1. Start pressing DEF key and hold for 5s.
  2. Then release just DEF but keep the UP key pressed for another 5s. Then parameter reset is successful by controller re-start automatically.

NOTE:

5.6 HIDDEN MENU

The hidden menu includes all the parameters of the instrument.

HOW TO ENTER THE HIDDEN MENU

  1. Enter the Programming mode by pressing the SET+UP keys for 3s (Set value starts to blink).
  2. Released the keys, then push again the SET+UP keys for more than 7s. The L2 label will be displayed immediately followed by the Hy parameter.

NOW YOU ARE IN THE HIDDEN MENU.

  1. Select the required parameter.
  2. Press the "SET" key to display its value.
  3. Use UP or DOWN to change its value.
  4. Press "SET" to store the new value and move to the following parameter.

To exit: Press SET+UP or wait 15s without pressing a key.

NOTE1: if there aren't any parameter in L1, after 3s the "nP" message is displayed. Keep the keys pushed till the L2 message is displayed.

NOTE2: the set value is stored even when the procedure is exited by waiting the time-out to expire.

HOW TO MOVE A PARAMETER FROM THE HIDDEN MENU TO THE FIRST LEVEL AND VICE VERSA.

Each parameter present in the HIDDEN MENU can be removed or put into "THE FIRST LEVEL" (user level) by pressing SET+UP. In HIDDEN MENU when a parameter is present in First Level the decimal point is on.

5.7 TO LOCK THE KEYBOARD

  1. Keep pressed for more than 3s the UP and DOWN keys.
  2. The "OF" message will be displayed and the keyboard will be locked. If a key is pressed more than 3s the "OF" message will be displayed.

5.8 TO UNLOCK THE KEYBOARD

Keep pressed together for more than 3s the UP and DOWN keys till the "on" message will be displayed.

5.9 THE ON/OFF FUNCTION

With "b3 = oF", by keeping pushed the DOWN key, the instrument is switched off. The "OF" message is displayed. In this configuration, the regulation is disabled.

To switch the instrument on, push again the DOWN key.

WARNING: Loads connected to the normally closed contacts of the relays are always supplied and under voltage, even if the instrument is in stand by mode.

6. PARAMETERS

REGULATION

DISPLAY

PROBES

DEFROST

ALARMS

DIGITAL INPUT

SERIAL OUTPUT

OTHER

7. DIGITAL INPUTS

The free voltage digital input is programmable in different configurations by the "iF" parameter.

7.1 NOT USED (IF=NU)

The digital input is not used.

7.2 DOOR SWITCH (IF=DO)

It signals the door status and the corresponding relay output status through the "dc" parameter: no, Fn = normal (any change); CP, FC = Compressor OFF. Since the door is opened, after the delay time set through parameter "di", the door alarm is enabled, the display shows the message "dA" and the regulation restarts if rd = y. The alarm stops as soon as the external digital input is disabled again. With the door open, the high and low temperature alarms are disabled.

7.3 EXTERNAL ALARM (IF=EA)

As soon as the digital input is activated the unit will wait for "di" time delay before signalling the "EA" alarm message. The outputs status don't change. The alarm stops just after the digital input is de-activated.

7.4 SERIOUS ALARM (IF=BA)

When the digital input is activated, the unit will wait for "di" delay before signalling the "CA" alarm message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-activated.

7.5 START DEFROST (IF=DF)

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation will restart only if the digital input is disabled otherwise the instrument will wait until the "Md" safety time is expired.

7.6 TURN ON THE AUXILIARY RELAY (IF=AU)

It starts a turn on the auxiliary relay if there are the right conditions.

8. TTL SERIAL LINE – for monitoring systems

The TTL serial line, available through the HOT KEY connector, allows by means of the external TTL/RS485 converter, XJ485-CX, to connect the instrument to a monitoring system ModBUS-RTU compatible.

9. INSTALLATION AND MOUNTING

Instrument XR02CH shall be mounted on a vertical panel, in a 29x71 mm hole, and fixed using the special bracket supplied. The temperature range allowed for correct operation is 0÷60 °C. Avoid places subject to strong vibrations, corrosive gases, excessive dirt or humidity. The same recommendations apply to probes. Let air circulate by the cooling holes.

10. ELECTRICAL CONNECTIONS

The instrument is provided with a screw terminal block to connect cables with a cross section up to 2,5 mm². Before connecting cables make sure the power supply complies with the instrument's requirements. Separate the probe cables from the power supply cables, from the outputs and the power connections. Do not exceed the maximum current allowed on each relay, in case of heavier loads use a suitable external relay.

10.1 PROBES

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration. It is recommended to place the thermostat probe away from air streams to correctly measure the average room temperature.

11. HOW TO USE THE HOTKEY

11.1 HOW TO PROGRAM THE HOT KEY FROM THE INSTRUMENT (UPLOAD)

  1. Program one controller with the front keypad.
  2. When the controller is ON, insert the "Hot key" and push the UP key; the "up" message appears followed by a flashing "En".
  3. Push "SET" key and the "En" will stop flashing.
  4. Turn OFF the instrument, remove the "Hot Key", then turn it ON again.

NOTE: the "Er" message is displayed for failed programming. In this case push again the UP key if you want to restart the upload again or remove the "Hot key" to abort the operation.

11.2 HOW TO PROGRAM AN INSTRUMENT USING HOT KEY (DOWNLOAD)

  1. Turn OFF the instrument.
  2. Insert a programmed "Hot Key" into the 5 PIN receptacle and then turn the Controller ON.
  3. Automatically the parameter list of the "Hot Key" is downloaded into the Controller memory, successfully followed by the "En" label.
  4. After 10 seconds the instrument will restart working with the new parameters.
  5. Remove the "Hot Key".

NOTE: the "Er" message is displayed for failed programming. Check the Hotkey connection, check the data into Hotkey and repeat the action above.

12. ALARM SIGNALLING

Mess.CauseOutputs
"P1"Room probe failureCompressor output according to "Cy" and "Cn"
"HA"Maximum temperature alarmOutputs unchanged
"LA"Minimum temperature alarmOutputs unchanged
"EA"External alarmOutputs unchanged
"CA"Serious external alarmAll outputs OFF
"dA"Door OpenCompressor restarts

12.1 ALARM RECOVERY

Probe alarm "P1" starts some seconds after the fault in the related probe; they automatically stop some seconds after the probe restarts normal operation. Check connections before replacing the probe.

Temperature alarms "HA" and "LA" automatically stop as soon as the temperature returns to normal values.

Alarms "EA" and "CA" (with iF=bL) recover as soon as the digital input is disabled.

13. WIRINGS

13.1 XR02CH-20A OR 8A - 110VAC OR 230VAC

A diagram shows the wiring for the XR02CH controller. It indicates terminals for Hot Key - TTL, Digital Input, Power Line Supply, and Outputs (01). Terminal 8-9 are for the compressor relay with absolute ratings of 20(8)A. Terminals 6-7 are for the power supply.

14. DEFAULT SETTING VALUES

This section provides a table of default setting values for various parameters:

LABELDESCRIPTIONRANGEDEFAULT
StSet point-55°C÷US/-55°F÷US3.0°C/37 °F
HyDifferential0.1°C÷45°F2.0°C/4 °F
LSMinimum Set Point-55°C÷SET/-67°F÷SET-55 °C/-55°F
USMaximum Set PointSET÷99°C/SET÷99°F99 °C/99°F
odOutputs activation delay at start0 ÷ 99 min1
ACAnti-short cycle delay0 ÷ 50 min1
CyCompressor ON time faulty probe0 ÷ 99 min15
CnCompressor OFF time faulty probe0 ÷ 99 min30
CHType of action: CL: cooling, Ht: heatingCL, HtCL
CFMeasurement units°C - °F°C/°F
rEResolution (only for °C)dE - indE/in
dyDisplay delay0 ÷ 15 min0
PCType of probent; Ptnt
otFirst probe calibration-9.9÷9.9°C/-17÷17°F0.0
F5Filter probe enablingnu; do; ALnu
F6Filter coefficient1 ÷ 9920
idInterval between defrost cycles0 ÷ 99 hours8
MdMaximum length for defrost0 ÷ 99 min.20
dFDisplay during defrostrt-it-SP- dEit
tAMax display delay after defrost0 ÷ 99 min15
AUMaximum temperature alarmAL÷99°C/AL÷99°F99 °C/99 °F
ALMinimum temperature alarm-55°C÷AU/-67°F÷AU-55 °C/-55 °F
AHAlarm hysteresis0.1÷25°C/1÷45°F2.0°C/4 °F
AdTemperature alarm delay0 ÷ 99 min15
dAExclusion of temperature alarm at startup0 ÷ 99 min90
OAOpen door alarm delay0 ÷ 99 min5
iPDigital input polarityCL - OPCL
iFDigital input configurationdo - EA-bA-dF- Fn- Hc-Audo
diDigital input delay0 ÷ 99 min15
dCCompressor status when open doorno/Fn/cP/Fcno
rdRegulation with door openn-yy
SrSerial address1-101
bdBaudrate0-396
PAParityno; od; evno
FrParameter factory resety-ny
rLFirmware release (read only)Read OnlyRead Only
SvSub-version (read only)Read OnlyRead Only
PtParameter code tableRead OnlyRead Only

15. TECHNICAL DATA

FEATURESDESCRIPTION
HousingSelf-Extinguishing PC Resin
DimensionsFront 32x74 mm; Case depth 50 mm
Mounting devicePanel Mounting 71x29mm Cutout
Degree of ProtectionNEMA-UL 50e; IEC 60529: Internal use only, Case Type 1; Front: IP65; Back: IP00
Power Supply230Vac ±10%, 50/60Hz --- 110Vac ±10%, 50/60Hz
Overvoltage CategoryII
Rated Power230VAC: 3,5VA Max (ENEC)
Rated Impulse Voltage2500V
Display2 digits, LED red (white and blue are optional), height 19 mm
BuzzerOptional
Software ClassA
Terminal blocks / Terminal ConnectionsLow Voltage Signals: Screw Terminal Block, wire sections between 1 and 2,5 mm²; Max tightening force: 0,5 N*m. High Voltage Signals: Screw Terminal Block, wire sections between 1 and 2,5 mm²; Max tightening force: 0,5 N*m.
Data StoringParameters: Internal Flash
Type of Action1.B
Pollution Degree2, non-condensing humidity
Ambient Operating Temperature and HumidityUL/IEC: -20÷60°C / 0÷60°C
Shipping and Storage Temperature-40÷85°C
Measurement RangeNTC: -40÷110°C, resolution 0,1°C or 1°C (selectable); -67÷99°F, resolution 1°F. PTC: -100÷150°C, resolution 0,1°C or 1°C (selectable).
AccuracyNTC, PTC: ±1% compared to the full scale. If NTC probe are used: Class 0.5; less than 1% in the range [-25°C a +10°C].
Inputs1 NTC o PTC (configurable)
Relay Outputs Configuration 201 free voltage contact; Output 01 (8-9): Compressor; Nominal 20A; UL 60730, ENEC; 16FLA/96LRA
Relay Outputs Configuration 81 free voltage contact; Output 01 (8-9): Compressor; Nominal 8A; UL 60730, ENEC; 4.9FLA/29.4LRA
I/O PortHOT KEY: MAX voltage allowed 5 VCC. DO NOT CONNECT ANY EXTERNAL POWER SUPPLY.
Purpose of ControlOperating Control
Construction of ControlIncorporated Control, intended to be used in Class I or Class II equipment
ApprovalsIEC/EN/UL 60730-1; IEC/EN/UL 60730-2-9

Copeland Controls S.r.l. Z.I. Via dell'Industria, 27-32016 Alpago (BL) ITALY Tel. +39 0437 9833 r.a. - copeland.com - dixell@copeland.com

Models: XR02CH Digital Controller, XR02CH, Digital Controller, Controller

File Info : application/pdf, 4 Pages, 461.81KB

PDF preview unavailable. Download the PDF instead.

XR02CH-NG-GB Microsoft Word for Microsoft 365

Related Documents

Preview Copeland XR30CHC Digital Controller with Bluetooth Connectivity User Manual
This manual provides detailed information on the Copeland XR30CHC digital controller, including its features, installation, operation, and maintenance. It covers energy saving algorithms, defrost functions, digital output configuration, and alarm signaling.
Preview Copeland XM679K Controllers: Installation and Operation Guide
Comprehensive guide for Copeland XM679K controllers, detailing installation, wiring, programming, and operation for multiplexed cabinets. Includes technical specifications and safety precautions.
Preview Universal-XR Unit of Measure Change Instructions
A comprehensive guide to the Copeland Universal-XR microprocessor-based controller, covering installation, quick start-up, parameter configuration, button functions, alarms, troubleshooting, and technical specifications for refrigeration applications.
Preview Copeland FULL TOUCH XH78T Quick Start Guide
This document provides a quick start guide for the Copeland FULL TOUCH XH78T digital temperature controller, detailing its features, user interface, technical specifications, and safety information.
Preview Copeland Discus Digital Upgrade Procedures for Refrigeration Compressors
This document outlines the upgrade procedures for Copeland Discus Digital and Intelligent Store Discus v2.x compressors, detailing the conversion of the head and valve plate, wiring the digital components, and programming the controller for enhanced capacity control.
Preview Copeland XER Cold Room Temperature Controller Installation Guide
Comprehensive installation guide for the Copeland XER Cold Room Temperature Controller, covering user interface, regulation, defrost operations, wiring, and technical specifications.
Preview Copeland XR70CHC Digital Controller with Bluetooth Connectivity User Manual
Explore the features and functionalities of the Copeland XR70CHC digital controller, a versatile solution for refrigeration units, offering Bluetooth connectivity, advanced regulation, and energy-saving algorithms. This manual provides comprehensive guidance on installation, operation, and parameter settings.
Preview Copeland Supervisory Control Platform: Installation and Operation User Manual
Comprehensive user manual for Copeland's Supervisory Control Platform (E3 and Site Supervisor). Covers installation, operation, hardware overview, software features, wiring, and troubleshooting for advanced facility and refrigeration management.