Universal-XR Unit of Measure Change Instructions
1. General Description
The Model Universal-XR is a 71x29 mm format microprocessor-based controller. It is available in 12/24Vac/dc, 120Vac, or 230Vac versions and is suitable for applications on high, medium, or low temperature refrigeration units. It features three relay outputs to control the compressor, defrost (which can be electrical or hot gas), and evaporator fans. It can operate with PTC or NTC probes. If defrost is terminated by time, it can function with a single thermostat probe. If defrost is terminated by temperature, it includes an input for an evaporator probe(s). The Universal-XR is equipped with a flashing visual alarm and buzzer. Each instrument is fully configurable through special parameters that can be easily programmed via the keypad.
2. Quick Start Up Procedure - Up And Running In 5 Easy Steps
This Quick Start Up section is designed to get you up and running with the minimum of fuss. Follow these 5 simple steps:
- STEP 1: Install the new Universal-XR per the installation instructions included with the controller.
- STEP 2: Turn on power.
- STEP 3: THEN WITHIN 1 MINUTE COMPLETE STEPS 3, 4 AND 5. Press the [Set] and [Down Arrow] keys for 3 seconds. The controller will automatically recognize and adjust itself to the type of probes connected. (The display briefly shows 'tPd' followed by 'ntC' or 'PtC').
- STEP 4: Press the [Auxiliary]/[Type Controller] key for 3 seconds. The setting of parameter 'tC' is displayed. Use the [Up Arrow] or [Down Arrow] keys to adjust to the required setting, then confirm by pressing [Set] (see Table 1 below).
- STEP 5: Press [Set] for 3 seconds until the [Celsius] or [Fahrenheit] icon starts to flash. Then, adjust the SET POINT using the [Up Arrow] or [Down Arrow] keys, and press [Set] again to confirm.
Notes:
- All probes must be of the same type, either PTC or NTC.
- Probes must be between -58 to 140°F for auto-recognition to work.
- If 1 minute expires before completing the quick set up, either cycle the power OFF then ON to start the set up again, or enter Pr2 as per the instructions and adjust your parameter settings manually (see Section 9).
Table 1: Parameter “tC” Settings
Parameter tC | Type of Control | Models Replaced | Required probes |
---|---|---|---|
1 | On/Off thermostat - Heating | XR110C, XR01CX, XR10C, XR10CX | x1 |
2 | Off cycle defrost (timed) | XR120C, XR02CX, XR20C, XR20CX | x1 |
3 | Off Cycle defrost time initiated / temperature terminated | XR120C, XR02CX, XR20C-E | x2 |
4 | Off Cycle defrost time initiated / temperature terminated, Alarm Relay | XR130C, XR03CX, XR30CX | x2 |
5 | Electrical / Hot Gas defrost, time initiated / temperature terminated | XR140C, XR04CX, XR40CX | x2 |
6 | Electrical / Hot Gas defrost, time initiated / temperature terminated + evap. Fan delay and control | XR160C, XR06CX, XR60CX | x2 |
7 | Full open map of parameters configure your own control | Your determination | 1 to 3 |
Note: As you change parameter tC, defaults change and should be approximately correct for that application. However, it is strongly recommended to check all parameter default values listed in these instructions to ensure they suit your particular application and make further adjustments if necessary. Read the following sections for information about programming.
3. Typical Connections - For General Guidance Only
The following tables describe typical connection configurations for different control types (TC=1 through TC=7). These diagrams illustrate how to wire the Universal-XR controller for various refrigeration applications.
TC=1 Heating: Controls heating systems.
TC=2 Cooling, Off Cycle Defrost, Time Ended: For cooling with time-based defrost.
TC=3 Cooling, Off Cycle Defrost, Temperature Ended: For cooling with temperature-based defrost.
TC=4 Cooling, Off Cycle Defrost, Temperature Ended, Alarm Relay: For cooling with temperature-based defrost and alarm relay.
TC=5 Cooling, Electric or Hot Gas Defrost, Temperature Ended: For cooling with electric or hot gas defrost terminated by temperature.
TC=6 Low Temp, Elec. Or Hot Gas Defrost, Temp. Ended, Fan Control: For low-temperature applications with electric or hot gas defrost, temperature termination, and fan control.
TC=7 Open Map to be Configured for any application: A fully configurable mode.
Power Supply Note: 12/24Vac/dc units use Terminals 4 & 5 for power supply. 120Vac units use Line and Neutral.
Load Description: Load1 is always Compressor or Heat. Load2 is OAA and Load3 is OAb.
4. Parameter Table and Factory Default Settings
IMPORTANT: Always set parameter "tC" first. As you move "tC" between settings 1 to 7, all non-relevant parameters will be masked. After setting "tC", it will be possible to modify all other relevant parameters. Once the program is completed, you may want to save the parameter map to a Hot Key. If "tC" is changed after final programming, the parameters will revert to the defaults listed below.
WARNING: Always switch the power OFF and then ON at the end of programming to update any parameter changes. Make sure you connect the correct number of probes to suit the setting of parameter tC. Failure to do this will cause probe alarms.
Table 3: Default Controller Parameters
Description | Label | Adjustment Range | tC Settings | ||||||
---|---|---|---|---|---|---|---|---|---|
tC1 | tC2 | tC3 | tC4 | tC5 | tC6 | tC7 | |||
Type (category) of controller | tC | 1 = On/Off Thermostat; 2 = Off cycle defrost; 3 = Time / time defrost; 4 = Time / temp defrost + alarm; 5 = Time / temp defrost; 6 = Time / temp defrost + fan delay; 7 = Full Open Map Configurable | 1 | 2 | 3 | 4 | 5 | 6 | 7 |
Set Point | LS to US | 40.0°C; 104°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | |
Probe type | PbC | PTC=0 NTC=1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Differential | HY | 0.1 to 25.5°C; 1 to 45°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F |
Minimum Set Point limit | LS | -55°C to Set Point; -67°F to Set Point | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F |
Maximum Set Point limit | US | Set Point to 150°C; Set Point to 302°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F |
Anti-short cycle delay | AC | 0 to 50 min | 1 | 1 | 1 | 1 | 1 | 1 | 0 |
Second compressor start delay | ACI | 0 to 255 sec | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Temperature alarm configuration | ALC | rE (0)= Relative to Set Point; Ab (1) = Absolute | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
High temperature alarm | ALU | 0 to 50°C (Rel); ALL to 150°C (Abs); 0 to 90°F (Rel); ALL to 302°F (Abs) | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F |
Low temperature alarm | ALL | 0 to 50°C (Rel); -55°C to ALU (Abs); 0 to 90°C (Rel); -67°C to ALU (Abs) | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F |
Temperature alarm delay | Ald | 0 to 255 min | 15 | 15 | 15 | 15 | 15 | 15 | 15 |
Delay of temperature alarm at start up | dRo | 0 to 720 min | 90 | 90 | 90 | 90 | 90 | 90 | 90 |
Outputs activation delay at start up | od5 | 0 to 255 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Thermostat override | CCE | 0 to 990 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Set point for continuous cycle | CCS | -55 to 150°C; -67 to 302°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F |
Defrost delay after thermostat override | dAF | 0 to 255 min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
Interval between defrosts | dF | 1 to 250 hours | 4 | 6 | 6 | 6 | 4 | 4 | 4 |
Delay start of defrost | d5d | 0 to 255 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Maximum duration of defrost | NAF | 0 to 255 min | 15 | 15 | 30 | 30 | 30 | 30 | 30 |
Defrost termination temperature | dEE | -55 to 50°C; -67 to 122°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F |
Maximum duration of defrost (second evaporator) | NdS | 0 to 255 min | 30 | 30 | |||||
Defrost termination temperature (second evaporator) | dtS | -55 to 50°C; -67 to 122°F | 8.0°C; 46°F | 8.0°C; 46°F | |||||
Display during defrost | dFd | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
Defrost display time out | dAd | 0 to 255 min | 3 | 10 | 10 | 10 | 10 | 10 | 10 |
Defrost type (forced) | tdF | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Drain down time | Fdt | 0 to 255 min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
First defrost after power on | dPo | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Evaporator fan operating mode | FnC | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Evaporator fan stop temperature | FSt | -55 to 50°C; -67 to 122°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F |
Evaporator fan delay after defrost | Fnd | 0 to 255 min | 7 | 7 | 7 | 7 | 7 | 7 | 7 |
Fan ON time | Fon | 0 to 15 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Fan Off time | FoF | 0 to 15 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Thermostat probe calibration | ot | -12.0 to 12.0°C; -21 to 21°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F |
Evaporator probe presence | P2P | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Evaporator probe calibration | oE | -12.0 to 12.0°C; -21 to 21°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F |
Third probe presence | P3P | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Third probe calibration | o3 | -12.0 to 12.0°C; -21 to 21°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F |
Display Resolution | rES | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Temperature measurement unit (°C/°F) | CF | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Instrument display | Lod | 0 = P1 = Thermostat probe; 1= P2 = Evaporator probe; 2= P3 = Third probe; 3 = sEt = SET-POINT | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Display delay | dLy | 0 to 20min0sec, res. 10sec | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Type of action | CH | 0 = Cl = cooling; 1 = Ht = heating | 1 | 0 | 0 | 0 | 0 | 0 | 0 |
Compressor ON time with faulty probe | Con | 0 to 255 min | 15 | 15 | 15 | 15 | 15 | 15 | 15 |
Compressor OFF time with faulty probe | CoF | 0 to 255 min | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
Alarm muting configuration for buzzer & relay | E6A | 0 = n = Mute buzzer only; 1 = Y = Mute buzzer & relay | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
Second Digital input configuration | i2F | 0 = Starts a defrost; 1 = Input from a door switch (see parameter odC); 2 = Activates the auxiliary relay; 3 = Starts Energy Saving (Control Point becomes Set Point +/- value in HES); 4 = Remote On/OFF (puts the controller into standby); 5 = Generic external alarm (normal regulation continues); 6 = Serious external alarm (regulation is stopped). | 5 | 5 | 5 | 5 | 5 | 5 | 5 |
Second Digital input polarity | i2P | 0 = the digital input is activated by closing the circuit; 1 = the digital input is activated by opening the circuit. | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Digital input 2 delay | di2 | Time interval/delay for digital input 2 alarm: (0 to 255min) it defines the time delay between the detection and the subsequent signalling of the alarm. | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Door open – compressor / fan status | odC | 0 = no = normal; 1 = FAn = Fan OFF; 2 = CPr= Compressor OFF; 3 = F_C = Compressor and fan OFF. | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Defrost relay configuration | DAA | Only on tC=7 0 = Alr = Alarm; 1 = db = Dead Band; 2 = AUS = Auxiliary; 3 = Cp2 = Second compressor output; 4 = LIG = Light output; 5 = dF2 = Second defrost output. dEF (6) =1st Defrost output; Fan (7) = Fan output | 6 | 6 | |||||
Auxiliary relay configuration | oAb | 1 = Alr = Alarm; 2 = db = Dead Band; 3 = AUS = Auxiliary; 4 = Cp2 = Second compressor output; 5 = LIG = Light output; 6 = dF2 = Second defrost output. dEF (6) =1st Defrost output; Fan (7) = Fan output | 7 | 7 | |||||
Alarm relay polarity | RoP | 0 = CL= contact [11-12] closed with alarm; 1 = oP = contact [11-12] open with alarm. | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Exclude temperature alarm - door open | dot | 0 to 255 min | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
Restart regulation with door open alarm | rrd | n (0) = No; Y (1) = Yes. | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
5. Parameters - Their Functions in Detail
This section provides detailed descriptions of the controller's parameters.
Table 4: Controller Parameters in Detail
Display Visualisation | Description | Label | Adjustment Range | tC1 | tC2 | tC3 | tC4 | tC5 | tC6 | tC7 |
---|---|---|---|---|---|---|---|---|---|---|
EC | Type of Controller: tells the Universal-XR which type of controller it will be operating as. 1 = on/off Heating thermostat - 1 relay & 1 probe; 2 = Combined thermostat with off cycle defrost timer - 1 relay & 1 probe; 3 = Combined thermostat with time initiated & time terminated defrost - 2 relays & 2 probes; 4 = Combined thermostat with time initiated & temperature terminated defrost - 2 relays & 2 probes; alarm; 5 = Combined thermostat with time initiated, temperature terminated defrost + 2 relays & 2 probes; defrost; 6 = Combined thermostat with time initiated, temperatures terminated defrost + evaporator fans control with delay after defrost - 3 relays & 3 probes; 7 = Combined thermostat with time initiated, temperatures terminated defrost + evaporator fans control with delay after defrost - 3 relays & 3 probes. Fully open map | tC | 1 | 2 | 3 | 4 | 5 | 6 | 7 | |
PbC | Probe Type: configures the controller to work with PTC or NTC probes. 0 = ptC = PTC, 1 = ntC = NTC. | PbC | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
HY | Differential: (1 to 50) sets the degrees above Set Point at which the compressor cuts in. Note: when tC = 1 (heating applications) the tC value is automatically set below the Set Point. If the temperature decreases and reaches set point minus differential the regulation output is activated and then turned off when the temperature reaches the set point value again. | HY | 0.1 to 25.5°C; 1 to 45°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F | 2.0°C; 2°F |
LS | Minimum set point limit: (-55°C to SET or -67°F to SET) sets the lower limit of set point adjustment. | LS | -55°C to Set Point; | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F |
US | Maximum set point limit: (SET to 150°C or SET to 302°F) sets the upper limit of set point adjustment. | US | Set Point to 150°C; Set Point to 302°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F |
AC | Anti-short cycle delay: (0 to 50min) minimum interval between the compressor stop and the next possible restart. | AC | 0 to 50 min | 1 | 1 | 1 | 1 | 1 | 1 | 0 |
ACI | Second compressor start delay: (0 to 255sec) | ACI | 0 to 255 sec | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
ALC | Temperature alarm configuration: rE = Related to Set Point; Ab = Absolute. Note: Relative means alarms are linked to the Set Point and will follow it if it is adjusted. In this case ALU & ALL set the temp over & under Set Point for alarm. Absolute means ALU & ALL are fixed alarm temperatures, which are not affected by any Set Point adjustment. | ALC | rE (0)= Relative to Set Point; Ab (1) = Absolute | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
ALU | High temperature alarm: ALC = rE→ [0 to 50°C] or [0 to 90°F]; ALC = Ab→ [ALL to 150°C] or [ALL to 302°F]. | ALU | 0 to 50°C (Rel); ALL to 150°C (Abs); 0 to 90°F (Rel); ALL to 302°F (Abs) | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F | 50.0°C; 122°F |
ALL | Low temperature alarm: ALC = rE→ [0 to 50°C] or [0 to 90°F]; ALC = Ab→ [-55°C to ALU] or [-67 to ALU]. | ALL | 0 to 50°C (Rel); -55°C to ALU (Abs); 0 to 90°C (Rel); -67°C to ALU (Abs) | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F | -50.0°C; -58°F |
Ald | Temperature alarm delay: (0 to 255min) time interval between an alarm condition occurring and the alarm is signalling. | Ald | 0 to 255 min | 15 | 15 | 15 | 15 | 15 | 15 | 15 |
dRo | Delay of temperature alarm at start-up: (from 0 to 720min; res. 10min) time delay of any temperature alarm during pull down following "power on". | dRo | 0 to 720 min | 90 | 90 | 90 | 90 | 90 | 90 | 90 |
od5 | Outputs activation delay at start up: (0 to 255min) time delay before any output relay activates following "power on". | od5 | 0 to 255 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
CCE | Thermostat override: (0 to 990min; res. 10min) period during which the compressor will run continuously, regardless of temperature. Setting this parameter to 0 disables this function. | CCE | 0 to 990 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
CCS | Set point for continuous cycle: (-55 to 150 °C or -67 to 302°F) it sets the set point used during the continuous cycle. | CCS | -55 to 150°C; -67 to 302°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F | 2.0°C; 36°F |
dAF | Defrost delay after fast freezing: (0 to 255min) time interval between the end of the thermostat override period and the start of the following defrost related to it. | dAF | 0 to 255 min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
dF | Interval between defrosts: (0 to 255hours) time interval between the beginning of two consecutive defrosts. | dF | 1 to 250 hours | 4 | 6 | 6 | 6 | 4 | 4 | 4 |
d5d | Delay start of defrost: (0 to 255min) delay between reaching the defrost interval time (as defined by parameter idF) and when a defrost cycle actually starts. Used to stagger defrosts between multiple systems. | d5d | 0 to 255 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
NAF | (Maximum) duration of defrost: (0 to 255min) time duration of a defrost cycle when only one probe is in use, or defrost time out override when second (evaporator) probe is in use. Set it to zero to disable defrost cycles. | NAF | 0 to 255 min | 15 | 15 | 30 | 30 | 30 | 30 | 30 |
dEE | Defrost termination temperature: (-55 to 50°C or -67 to 122°F) sets the defrost termination temperature. Measured by the evaporator probe. | dEE | -55 to 50°C; -67 to 122°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F | 8.0°C; 46°F |
NdS | (Maximum) length for second defrost: (0 to 255min) when P3P = 0, (not evaporator probe: timed defrost) it sets the defrost duration, when P3P = 1 (defrost end based on temperature) it sets the maximum length for defrost. *** Only if being used with tC7*** Note: The P3 probe will be automatically set as second evaporator probe by the tC parameter. | NdS | 0 to 255 min | 30 | 30 | |||||
dtS | Second termination temperature: (-55 to 50°C or -67 to 122°F) sets the temperature measured by the second evaporator probe (P3), which causes the end of defrost. | dtS | -55 to 50°C; -67 to 122°F | 8.0°C; 46°F | 8.0°C; 46°F | |||||
dFd | Display during defrost: 0= rt = real temperature; 1 = it = temperature at defrost start; 2 = sEt = set point; 3 = dEF = dEF label; 4 = dEG = dEG label. | dFd | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
dAd | Defrost display time out: (0 to 250min) after a defrost, the controller will revert to current temperature display when the temperature is back down within its normal working range, or after the time set in this parameter, whichever is the sooner. | dAd | 0 to 255 min | 3 | 10 | 10 | 10 | 10 | 10 | 10 |
tdF | Defrost type: 0 = El = electrical heater; 1 = rE = hot gas, compressor runs during defrost. | tdF | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
Fdt | Drain down time: (0 to 255min) drain down time. Runs concurrently with Fnd (Fan delay after defrost time). Both fan and compressor are off during this time period. | Fdt | 0 to 255 min | 2 | 2 | 2 | 2 | 2 | 2 | 2 |
dPo | First defrost after power-on: 0 = Y = immediately; 1 = n = after the idF interval time. | dPo | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
FnC | Fan operating mode: 0= C_n = cycles on/off with the compressor, OFF during defrost; 1= O_n= continuous mode, OFF during defrost; 2= C_Y = cycles on/off with the compressor, ON during defrost; 3= O_Y = continuous mode, ON during defrost; | FnC | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
FSt | Fan stop temperature: (-55 to 50°C or -67 to 122°F) temperature above which the evaporator fan stops (during the normal refrigeration cycle). | FSt | -55 to 50°C; -67 to 122°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F | 8°C; 46°F |
Fnd | Fan delay after defrost: (0 to 255min) the time interval between the end of a defrost cycle and evaporator fans starting. Runs concurrently with Fdt (Drain down time). Always keep Fnd longer that Fdt. | Fnd | 0 to 255 min | 7 | 7 | 7 | 7 | 7 | 7 | 7 |
Fon | Fan ON time: (0 to 15min) used to set an On/Off cycle of the evaporator fans while the compressor is off. With FnC = 0 or FnC = 2, it sets the evaporator fan ON cycling time when the compressor is OFF. With Fon = 0 and FoF ≠ 0, the fans are always off. With Fon = 0 and FoF = 0 the fans are always off. | Fon | 0 to 15 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
FoF | Fan OFF time: (0 to 15min) used to set an On/Off cycle of the evaporator fans while the compressor is off. With FnC = 0 or FnC = 2, it sets the evaporator fan OFF cycling time when the compressor is OFF. With Fon = 0 and FoF ≠ 0, the fans are always off. With Fon = 0 and FoF = 0 the fans are always off. | FoF | 0 to 15 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
ot | Thermostat probe calibration: (-12.0 to 12.0°C or -21 to 21°F) adjustment for thermostat probe (Room) offset. | ot | -12.0 to 12.0°C; -21 to 21°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F |
P2P | Evaporator probe presence (Evap on the label): 0 = n = not present; 1 = Y = present. | P2P | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
oE | Evaporator probe calibration: (-12.0 to 12.0°C or -21 to 21°F) adjustment for evaporator probe offset. | oE | -12.0 to 12.0°C; -21 to 21°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F |
P3P | Third probe presence (probe named Evap.2 on the label): 0 = n = not present, the third input (the one signed with label "D.I. / Pb3") Input operates as digital input; 1 = Y = present, the third input (the one signed with label "D.I. / Pb3") Input operates as third probe. | P3P | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
o3 | Third probe calibration: (-12.0 to 12.0°C or -21 to 21°F) adjustment for third probe offset. | o3 | -12.0 to 12.0°C; -21 to 21°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F | 0.0°C; 0°F |
rES | Display resolution (Only available in Celsius): 0 = dE = with decimal point; 1 = in = without decimal point. | rES | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
CF | Temperature measurement unit: 0 = °C = Celsius; 1 = °F = Fahrenheit. Warning: If you alter the setting of parameter rES (decimal point on/off) re-check the settings of all temperature related parameters Set Point, HY, LS, US, ALU, ALL, dtE, FSt, ot & oE, as they can be effected. | CF | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
Lod | Probe for Display: 0 = P1 = Thermostat probe; 1= P2 = Evaporator probe; 2= P3 = Third probe; 3 = sEt = DISPLAY ONLY SHOWS THE SET-POINT. THE ACTUAL TEMPERATURE CAN BE SEEN BY PRESSING THE SET BUTTON. | Lod | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
dLy | Display delay: (0 – 20min0sec; resolution 10 sec) when the temperature increases, the display is updated of 1°C or 1°F after this time. | dLy | 0 to 20min0sec, res. 10sec | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
CH | Type of action: 0 = Cl = cooling; 1 = Ht = heating. | CH | 1 | 0 | 0 | 0 | 0 | 0 | 0 | |
Con | Compressor ON time with faulty probe: (0 to 255min) If there is a P1 probe failure the controller will automatically cycle the compressor on/off according to Con & CoF to maintain basic cooling. Con is the compressor "ON" time. | Con | 0 to 255 min | 15 | 15 | 15 | 15 | 15 | 15 | 15 |
CoF | Compressor OFF time with faulty probe: (0 to 255min) If there is a P1 probe failure the controller will automatically cycle the compressor on/off according to Con & CoF to maintain basic cooling. CoF is the compressor "OFF" time. | CoF | 0 to 255 min | 30 | 30 | 30 | 30 | 30 | 30 | 30 |
E6A | Alarm muting: 0 = n = Alarm relay remains active when alarm buzzer is muted; 1 = Y = Alarm relay is cancelled when alarm buzzer is muted. | E6A | 1 | 1 | 1 | 1 | 1 | 1 | 1 | |
i2F | Second Digital input configuration: configures the second digital input function: 0 = Starts a defrost; 1 = Input from a door switch (see parameter odC); 2 = Activates the auxiliary relay; 3 = Starts Energy Saving (Control Point becomes Set Point +/- value in HES); 4 = Remote On/OFF (puts the controller into standby); 5 = Generic external alarm (normal regulation continues); 6 = Serious external alarm (regulation is stopped). | i2F | 5 | 5 | 5 | 5 | 5 | 5 | 5 | |
i2P | Second Digital input polarity: 0 = the digital input is activated by closing the circuit; 1 = the digital input is activated by opening the circuit. | i2P | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
di2 | Digital input 2 delay: Time interval/delay for digital input 2 alarm: (0 to 255min) it defines the time delay between the detection and the subsequent signalling of the alarm. | di2 | 0 to 255 min | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
odC | Compressor and fan status when open door: 0 = no = normal; 1 = FAn = Fan OFF; 2 = CPr= Compressor OFF; 3 = F_C = Compressor and fan OFF. | odC | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
DAA | Defrost relay configuration: Only on tC=7 0 = Alr = Alarm; 1 = db = Dead Band; 2 = AUS = Auxiliary; 3 = Cp2 = Second compressor output; 4 = LIG = Light output; 5 = dF2 = Second defrost output. dEF (6) =1st Defrost output; Fan (7) = Fan output | DAA | 6 | 6 | ||||||
oAb | Auxiliary relay configuration: 1 = Alr = Alarm; 2 = db = Dead Band; 3 = AUS = Auxiliary; 4 = Cp2 = Second compressor output; 5 = LIG = Light output; 6 = dF2 = Second defrost output. dEF (6) =1st Defrost output; Fan (7) = Fan output | oAb | 7 | 7 | ||||||
RoP | Alarm relay polarity: 0 = CL= contact [11-12] closed with alarm; 1 = oP = contact [11-12] open with alarm. | RoP | 0 | 0 | 0 | 0 | 0 | 0 | 0 | |
dot | Exclude temperature alarm - door open: 0 to 255 min | dot | 0 to 255 min | 20 | 20 | 20 | 20 | 20 | 20 | 20 |
rrd | Restart regulation with door open alarm: n (0) = No; Y (1) = Yes. | rrd | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
6. Buttons and Their Functions
6.1 Single Button Functions
Table 5: Single Button Functions
Button | Function |
---|---|
[Type Controller] (tC) | Type Controller menu: Keep this button pressed for at least 3 sec within 1 min after power on to enter the "Type Controller Menu" (tC). |
[Auxiliary] | AUX output control: Switches the AUX relay output (if enabled as such). |
[Set] | Display current set point: After pressing and releasing this button, the set point will be displayed for 5 sec. This will not allow the set point to be altered. Changing set point value: Keep this button pressed for at least 2 sec. Set point change mode is entered indicated by the small LEDs flashing. Change the set point using the [Up Arrow] and [Down Arrow] buttons. The new value can be stored either by pressing the [Set] button (the instrument restores temperature display) or by waiting the exit time-out to expire (15 sec). |
[Up Arrow] | (UP): To see the max stored temperature; in programming mode it browses the parameter codes or increases the displayed value. |
[Down Arrow] | (DOWN): To see the min stored temperature; in programming mode it browses the parameter codes or decreases the displayed value. Keep pressed for 3 sec just after powering on the device (and within the first 60 sec) to start automatic probe recognizing. |
[Energy Saving] | Energy Saving: Allows the control to use the HES offset parameter to change the set point. |
6.2 Button Combination Functions
Table 6: Button Combination Functions
Combination | Function |
---|---|
[Set] + [Down Arrow] | Lock & unlock the keyboard: Keeping both buttons pressed for 3 sec will lock or unlock the keyboard. The display will flash 'PoF' or 'Pon' for a few seconds to confirm locking or unlocking respectively. |
[Set] + [Auxiliary] | Enter programming mode: Keep both buttons pressed for 3 sec, release them, and then press them again for 8 sec. The first label of Pr2 level will be displayed. |
[Set] + [Auxiliary] | Exit programming mode: Press together to return to normal display. |
7. Programming Mode
7.1 User Programming Level – Pr1
To enter programming level Pr1 (user programming level), keep both [Set] and [Down Arrow] buttons pressed for 3 sec. The first parameter label will appear. Browse the parameter list by using the [Up Arrow] or [Down Arrow] keys. Press [Set] to see a parameter's current value and [Up Arrow] or [Down Arrow] keys to alter its value. Press [Set] to confirm the change (the display will blink for 3 sec and then the next parameter will appear) or by waiting for the menu timeout to expire (15 sec). If no parameter is available for changes in Pr1 level, a 'nop' label will be shown.
7.2 Protected Programming Level - Pr2 (All Visible Parameters Can Be Found Here)
First enter Pr1 level (as described above). Then, with any parameter label displayed, keep both [Set] and [Down Arrow] buttons pressed for 8 sec. The first parameter label will appear. Browse the parameter list by using the [Up Arrow] or [Down Arrow] keys. Press [Set] to see a parameter's current value and [Up Arrow] or [Down Arrow] keys to alter its value. Press [Set] to confirm the change (the display will blink for 3 sec and then the next parameter will appear) or by waiting for the menu timeout to expire (15 sec).
From Pr2 level, it is also possible to add or remove any parameter to/from Pr1 by pressing both [Set] & [Down Arrow] while its label is displayed. Accessibility of any particular parameter via Pr1 level is confirmed by the alarm [!] icon lighting up while its label is displayed.
WARNING: If no button is pressed for 15 sec, any modified value will be stored into memory and the controller will return to the normal display mode.
8. Other Features of the Universal-XR
As well as the main digital display, there are some small icons on the front panel. These are used to indicate the status of the loads controlled by the instrument. Each icon function is described in the following table.
Table 7: Display Signalling Description
Combination | Function | Meaning |
---|---|---|
ON | Light (AUX) output enabled. | [Auxiliary] |
ON | Cooling enabled. | [Cooling] |
FLASHING | Anti-short cycle delay in progress. | [Anti-short cycle] |
ON | Fan enabled. | [Fan] |
FLASHING | Delay time on fan activation is running (Fnd > 0) | [Fan delay] |
ON | Defrost in progress. | [Defrost] |
FLASHING | Drip time in progress (Fdt > 0) or delay on start defrosting is running (dSd > 0). | [Drip/Delay] |
ON | Auxiliary output activated. | [Auxiliary Output] |
ON | Energy Saving activated. | [Energy Saving] |
ON | Thermostat override enabled. | [Thermostat Override] |
ON | ALARM signal: when in programming mode and in Pr2 level, this icon lights up notifying that this parameter is also accessible in the Pr1 level. | [Alarm] [!] |
ON | All measurement units are in Celsius degrees. | [Celsius] |
ON | Programming mode. | [Programming Mode] |
FLASHING | All measurement units are in Fahrenheit degrees. | [Fahrenheit] |
FLASHING | Programming mode. | [Programming Mode] |
9. Thermostat Override (not available when parameter tC = 1)
For rapid chilling or freezing, the thermostat can be overridden by pressing the [Up Arrow] button until the [Thermostat Override] icon lights up. The compressor will run in continuous mode, for the time period set in parameter CCE. Normal operation will then resume automatically after the CCE is exhausted or when the CCS is exhausted (Continuous Cycle Set Point). The cycle can also be terminated manually by pressing the [Up Arrow] button again for about 3 seconds.
10. Defrost Types
tC Parameter Value | Action |
---|---|
1 | No defrost |
2 or 3 | Off cycle defrost by timer |
4, 5, 6 or 7 | Forced type of defrost: Electrical or Hot Gas |
Note: tdF = 0: defrost is electrical; tdF = 1: defrost is by hot gas.
11. Evaporator Fan Control (only when parameter tC = 6 or 7)
The fan control mode is selected by means of the "FnC" parameter:
FnC Parameter | Action |
---|---|
C_n | Fans will cycle ON and OFF with the compressor and be off during defrost cycle. |
O_n | Fans will run continuously, but be off during defrost cycle. |
C_Y | Will switch ON and OFF with the compressor and be on during defrost cycle (*). |
O_Y | Fans will run continuously and be on during defrost cycle (*). |
(*) Note: Fans will stop if the temperature value set in parameter "FSt" is exceeded. Parameter FSt sets the fan stop temperature. This is the maximum temperature, detected by the evaporator probe, above which the evaporator fans will stop. Leave FSt above ambient temperature during commissioning to avoid fan short cycle.
After finishing the defrost phase, there is a stand still drain time, set by parameter Fdt. When this period has expired, the refrigeration cycle commences but the evaporator fans remain off until Fnd (fan delay) times out.
12. Special Applications – Dead Band Control
12.1 Dead Band Control (Cooling & Heating) tc=7
With [oAb = db], the compressor relay controls cooling as normal, but the 3rd (auxiliary/fan) relay is used to control a heater. The value entered in parameter HY will now be set equal on both sides of the SET POINT. For example, if [HY = 1°C], that will create a 2°C Dead Band. At [SET POINT + HY], cooling switches on. At [SET POINT – HY], heating switches on. Either cooling or heating switches off when the temperature returns to SET POINT.
13. Alarms
Message / Mode | Cause | Outputs |
---|---|---|
EE Flashing | Data or memory failure | Alarm output ON; Other outputs unchanged. |
P1 Flashing | Thermostat probe failure | Alarm output ON; Compressor output according to parameters Con and CoF. |
P2 Alternating with room temperature | Evaporator probe failure | Alarm output ON; Other outputs unchanged; End defrost is timed. |
P3 Alternating with room temperature | Second evaporator probe failure | Alarm output ON; Other outputs unchanged; End defrost is timed. |
HA Alternating with room temperature | High temperature alarm | Alarm output ON; Other outputs unchanged. |
LA Alternating with room temperature | Minimum temperature alarm | Alarm output ON; Other outputs unchanged. |
HA2 Alternating with room temperature | Condenser max temp alarm | Alarm output ON; Other outputs unchanged. |
LA2 Alternating with room temperature | Condenser max temp alarm | Alarm output ON; Other outputs unchanged. |
dA Alternating with room temperature | Door open alarm | Alarm output ON: Outputs re-start if parameter rrd = 1. |
EA Alternating with room temperature | Generic external alarm | Alarm output ON; Other outputs unchanged. |
bAL Alternating with room temperature | Serious external alarm | Alarm output ON; Other outputs OFF. |
13.1 Muting Alarm Buzzer & Relay
The alarm buzzer can be muted by pressing any button. The controller will briefly show the reset "rES" label. Parameter tbA defines how the alarm relay will respond to the muting of the buzzer:
- tbA = n: The alarm relay will remain active until the alarm condition is rectified.
- tbA = Y: The alarm relay de-activates when the buzzer is muted.
In either case, the display will flash an alarm label until the condition is rectified.
13.2 Alarm "EE"
The Copeland Universal-XR is provided with an internal watchdog verifying data and memory integrity. Alarm "EE" will flash after detecting a failure in data or in the internal memory. In this case, the alarm output is enabled.
WHAT TO DO:
- Cancel the alarm by pressing a key.
- Check the value of all parameters and restore correct values when wrong.
- Check the correct instrument operation and in case of further errors replace it.
13.3 Alarm Recovery
Probe alarms "P1", "P2", and "P3" start 30 seconds after a fault in a probe is detected; they automatically stop 30 seconds after the probe restarts normal operation. Check connections before replacing the probe.
Temperature alarms "HA" and "LA" automatically stop as soon as the thermostat temperature returns to normal values and when defrost starts. Temperature alarms "HA2" and "LA2" automatically stop as soon as the condenser temperature returns to normal values.
14. Removing Security Level Protection
It is possible to allow access to any parameter from Pr1 level. To do this, go into Pr2 as previously described. Scroll to the label of the parameter you require and then press the [Set] and [Down Arrow] buttons in quick succession. The decimal point LED will be on, indicating that access to this particular parameter is now possible from Pr1 level. Its label will now appear when in Pr1 programming level and its value can be altered. To restore security level protection, use the same procedure (the decimal point LED will go out after pressing both buttons).
15. Mounting
The Universal-XR should be mounted in a panel, in a 29mm (1.14") x 71mm (2.8") hole, and fixed using the special brackets supplied. Ambient temperature for correct operation is 32 to 140°F. Avoid places subject to strong vibrations, corrosive gases, excessive dirt, or humidity (20 to 85% non-condensing RH is the recommended working range). Make sure air can freely circulate through the cooling holes slots at the rear side of the controller.
16. Electrical Connections
The instrument is provided with a screw terminal block to connect cables with a cross section up to 2.5 mm². Before connecting cables, make sure the power supply complies with the instrument's requirements. Separate the probe cables from the power supply cables, from the outputs, and from the power connections. Do not exceed the maximum current rating for each relay; in case of heavier loads, use a suitable external relay.
17. Probes
It is recommended to place the thermostat probe away from rapid air streams to correctly measure the average room temperature. Place the defrost termination probe among the evaporator fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during defrost, to prevent premature defrost termination.
18. Technical Data
Housing: | Self-extinguishing ABS |
Size: | Frontal 32x74 mm; depth 70mm |
Mounting: | Panel mounting in a 71x29 mm panel cut-out |
Frontal protection: | IP65 |
Connections: | Screw terminal block ≤ 2.5 mm² wiring |
Power supply: | 120Vac, -10% +15% or 230Vac, -10% +15% |
Power absorption: | 4 VA max |
Display: | 3 digits, red LED, 14.2mm high |
Inputs: | A maximum of 3 temperature probes, PTC or NTC type. |
Probes (supplied): | 2 x NTC, range -50 TO 110°C (-58 to 230°F) with 1.5 meter (4.98') cables |
Relay outputs: | Compressor: SPST relay 16FLA/96LRA, 250Vac Defrost: SPDT relay 10A, 250Vac Fans: SPST relay 5A, 250Vac |
Other output: | Buzzer for acoustic signalling of alarms |
Data storing: | Non-volatile memory (EEPROM) |
Ambient temperature: | 0 to 60°C (32 to 140°F) |
Ambient humidity: | 20 to 85% (non condensing) |
Storage temperature: | -30 to 85°C (-22 to 185°F) |
Operating range: | PTC: -50 to 150°C (-58 to 302°F); NTC: -50 to 110°C (-40 to 230°F) |
Resolution: | 0.1°C or 1°F (selectable) |
Accuracy at 25°C: | (range -40 to 50°C) ±0.5 °C ±1digit |
19. Troubleshooting
Problem | Possible Reason | Notes |
---|---|---|
Display flashing HA | Temperature too high. | Check cooling system. Check alarm settings. |
Display flashing LA | Temperature too low. | Check cooling system. Check alarm settings. |
Display flashing HA2 | Condenser temperature too high. | Check condenser cooling system. Check alarm settings. |
Display flashing LA2 | Condenser temperature too low. | Check condenser cooling system. Check alarm settings. |
Display flashing P1 | Fault with thermostat probe. Wrong type of probe fitted (NTC/PTC). | Check probe connections and resistance value. Change probe type or alter parameter PbC. |
Display flashing P2 | Fault with evaporator probe. Wrong type of probe fitted (NTC/PTC) Parameter tC has been set to 4, 5 or 6 without evaporator probe fitted. | Check probe connections and resistance value. Change probe type or alter parameter PbC. Fit evaporator probe or alter parameter tC. |
Display flashing P3 | Fault with third probe. Wrong type of probe fitted (NTC/PTC). Parameter tC has been set to 6 without third probe fitted. | Check probe connections and resistance value. Change probe type or alter parameter PbC. Fit evaporator probe or alter parameter tC. |
Display flashing EE | Data corruption. | Check for electrical spikes and interference. Fit filters DIXL930 & DIXL932. Ensure probe cables are separated from power cables. Re-check all parameter settings. Replace controller if still not working. |
Display flashing dA | Door has been left open too long. | Shut the door. |
Display flashing EA | A non-serious external alarm has been detected by the digital input. | Trace and rectify the external problem. |
Display flashing bAL | A serious external alarm has been detected by the digital input. | Trace and rectify the external problem. |
Buttons will not work | Buttons have been locked. | Unlock buttons by pressing both [Up Arrow] & [Down Arrow] buttons until display flashes 'Pon'. |
Parameter cannot be adjusted over its full range | Some other parameter is conflicting and preventing further adjustment. | Check other parameter settings. |
Power on but no output operates (Small LEDs flashing) | Anti-short cycle delay in progress, all relays being held off until it expires. | Wait or adjust parameters AC or odS. |
Evaporator fan short cycling | Parameter FSt set too low. | Adjust FSt to a higher setting. During commissioning, set it above ambient until pull down is complete, then re-set to a more suitable temperature. |
20. Change over from F to F or Vis-versa
- Hold the [Set] & [Down Arrow] buttons, until HY is displayed, release both buttons then hold the [Set] and [Down Arrow] buttons until Pr2 is displayed. Release the buttons.
- Scroll with the [Up Arrow] button to CF, then press and release [Set]. Change the 1 to 0, then press and release [Set].
- Scroll down and adjust the ALL, ALU, FST, AFH, ALH, LS, US, rES as well as the HY.
- Let the control time out to the temp display.
Adjust the Set temp by holding the [Set] until the [Celsius] or [Fahrenheit] starts to flash, adjust the set point.
21. Enter Your Settings Here For Future Reference
(Tc=7 Set Up As Dead Band Control)
This section is for users to record their specific settings.
Table: Parameter Settings
Label | Description | Edit | Original | Vis. Level | Min | Max | Comment |
---|---|---|---|---|---|---|---|
tC | Parameter map selection | 7 | 7 | Pr2 | 1 | 7 | |
PbC | Kind of probe | ntC | ntC | Pr2 | |||
Hy | Differential | 4 | 4 | Pr1 | 1 | 45 | |
LS | Minimum set point value | -50 | -50 | Pr2 | -67 | 75 | |
US | Maximum set point value | 230 | 230 | Pr2 | 75 | 302 | |
AC | Anti-short cycle delay | 1 | 1 | Pr2 | 0 | 50 | |
AC1 | Second compressor start delay | 0 | 0 | Pr2 | 0 | 255 | |
ALP | Probe selection for temperature alarms | 0 | 0 | Pr2 | |||
ALC | Temperature alarm configuration | Ab | Ab | Pr2 | |||
ALU | High temperature alarm | 230 | 230 | Pr1 | -50 | 302 | |
ALL | Low temperature alarm | -50 | -50 | Pr1 | -67 | 230 | |
AFH | Differential for temperature alarm recovery | 1 | 1 | Pr1 | 1 | 45 | |
ALd | Temperature alarm delay | 15 | 15 | Pr2 | 0 | 255 | |
dAo | Delay before activating a temperature alarm at start up | 90 | 90 | Pr2 | 0 | 720 | |
odS | Delay before activating outputs at start up | 0 | 0 | Pr2 | 0 | 255 | |
CCt | Continuous cycle duration | 0 | 0 | Pr2 | 0 | 990 | |
CCS | Set point for continuous cycle | 0 | 0 | Pr2 | -67 | 302 | |
dAF | Defrost delay after fast freezing | 2 | 2 | Pr2 | 0 | 255 | |
idF | Interval between defrost cycles | 6 | 6 | Pr1 | 0 | 250 | |
dSd | Start defrost delay | 0 | 0 | Pr2 | 0 | 255 | |
dFP | Probe selection for first defrost | 3 | 3 | Pr2 | |||
MdF | (Maximum) length for first defrost | 30 | 30 | Pr1 | 0 | 255 | |
dtE | Defrost termination temperature (first evaporator) | 46 | 46 | Pr1 | -67 | 122 | |
dSP | Probe selection for second defrost | 0 | 0 | Pr2 | |||
MdS | (Maximum) length for second defrost | 0 | 0 | Pr2 | 0 | 255 | |
dtS | Defrost termination temperature (second evaporator) | 0 | 0 | Pr2 | -67 | 122 | |
dFd | Display during defrost | 3 | 3 | Pr2 | |||
dAd | Max display delay after defrost | 10 | 10 | Pr2 | 0 | 255 | |
tdF | Defrost type | 0 | 0 | Pr2 | |||
Fdt | Drain down time | 2 | 2 | Pr1 | 0 | 255 | |
dPo | First defrost after start-up | 0 | 0 | Pr2 | |||
FnC | Fan operating mode | 1 | 1 | Pr2 | |||
FSt | Fan stop temperature | 46 | 46 | Pr1 | -67 | 122 | |
Fnd | Fan delay after defrost | 5 | 5 | Pr1 | 0 | 255 | |
Fon | Fan on time with compressor off | 0 | 0 | Pr2 | 0 | 15 | |
FoF | Fan off time with compressor off | 0 | 0 | Pr2 | 0 | 15 | |
FAP | Probe selection for fan management | 1 | 1 | Pr2 | |||
FCt | Differential of temperature to force fan activation | 5 | 5 | Pr2 | 0 | 90 | |
FSU | Fan management | 0 | 0 | Pr2 | |||
ot | Thermostat probe calibration | 0 | 0 | Pr2 | -21 | 21 | |
P2P | Evaporator probe presence | 1 | 1 | Pr2 | |||
oE | Evaporator probe calibration | 0 | 0 | Pr2 | -21 | 21 | |
P3P | Third probe presence | 0 | 0 | Pr2 | |||
o3 | Third probe calibration | 0 | 0 | Pr2 | -21 | 21 | |
rES | Display resolution | 1 | 1 | Pr2 | |||
CF | Temperature measurement unit | 1 | 1 | Pr2 | |||
Lod | Display visualization | 0 | 0 | Pr2 | |||
dLy | Delay before updating the displayed temperature | 0.00 | 0.00 | Pr2 | |||
CH | Kind of action: heating or cooling | 0 | 0 | Pr2 | |||
Con | Compressor ON time with faulty probe | 15 | 15 | Pr2 | 0 | 255 | |
CoF | Compressor OFF time with faulty probe | 310 | 310 | Pr2 | 0 | 255 | |
tbA | Alarm output disabling by pushing any button | 0 | 0 | Pr2 | |||
i2F | Digital input 2 configuration | 5 | 5 | Pr2 | |||
i2P | Digital input 2 polarity | 0 | 0 | Pr2 | |||
di2 | Digital input 2 alarm delay | 0 | 0 | Pr2 | 0 | 255 | |
odC | Compressor and fan status when the door is open | 0 | 0 | Pr2 | |||
oAA | First output configuration | 0 | 0 | Pr2 | |||
oAb | Second output configuration | 3 | 3 | Pr2 |