Rheem-Ruud Commercial Electric Tank-Type Water Heaters
6 KW THRU 54 KW
Product Overview
Rheem-Ruud Electric Commercial Water Heaters are suitable for general commercial hot water applications and are also ideal for point-of-use installations, eliminating costly temperature loss in long piping runs. A single unit can be used as a booster heater to satisfy the hot water requirements of commercial dishwashers. A single temperature storage unit, when installed with a mixing valve, will supply two temperatures in food service establishments. For larger volume hot water requirements, 2, 3 or 4 units can be parallel manifolded, using optional factory kits.
Construction Features
SYSTEM SENTINEL
An element diagnostic panel, utilizing light emitting diodes (L.E.D.) corresponding to the number and location of each heating element are energized when the electric elements are operating. An unlit L.E.D. pinpoints the exact location of a non-functioning element, making element operation diagnosis simple and positive.
R-FOAM® INSULATION
A rigid polyurethane foam insulation provides superior insulating qualities, improves efficiency. Exceeds R-16 insulation factor. Our patented process of injecting R-Foam directly into the insulating cavity adds additional durability and toughness to the heater jacket. Fiberglass insulation guards against heat loss in the heating element compartment, and provides easy service access.
LIFEGUARD HEATING ELEMENTS
Separate screw-in type elements feature a stainless steel outer sheath of INCO-LOY® 800, surrounding a Nichrome wire filament, to resist water chemical corrosion and burn-out even in air or sediment, for long element life and long life performance. Elements are directly immersed in the water for efficient transfer of heat, and are easily changed by simply screwing new ones into the tank.
GLASS LINED STORAGE TANK
Heavy duty steel tank protects with double coating of exclusive Rheemglas to resist the corrosive action of hot water. Designed for 150 PSI working pressure. Each tank is supplied with factory installed anode rods for cathodic protection.
WATER CONNECTIONS
Hot outlet and cold inlet are 1-1/2" NPS brass nipples which prevent excessive turbulence of heating water and result in optimum tank draw.
SINGLE PANEL CONTROL BOX
With hinged door, provides immediate access to all electrical components and elements.
TERMINAL BLOCK
All models are equipped with CSA listed terminal blocks for simplicity of installation. This new terminal block will accept either copper or aluminum field connect wire.
Certifications and Ratings
EFFICIENCY
These units have been tested according to procedures specified by CSA and meet or exceed the energy efficiency requirements of ASHRAE Standard 90.1b 1992 requirements for energy conservation.
Model Numbers
INPUT KW | IMMERSION THERMOSTATS | ||
---|---|---|---|
50 Gal. (190L) | 85 Gal. (321L) | 120 Gal. (454L) | |
6 | EG50-C-9 | EG85-C-9 | EG120-C-9 |
9 | EG50-C-12 | EG85-C-12 | EG120-C-12 |
12 | EG50-C-15 | EG85-C-15 | EG120-C-15 |
15 | EG50-C-18 | EG85-C-18 | EG120-C-18 |
18 | EG50-C-24 | EG85-C-24 | EG120-C-24 |
24 | EG50-C-30 | EG85-C-30 | EG120-C-30 |
30 | EG50-C-36 | EG85-C-36 | EG120-C-36 |
36 | EG85-C-45 | EG120-C-45 | |
45 | EG85-C-54 | EG120-C-54 | |
54 |
Electrical Characteristics
INPUT KW | NO. OF ELEMENTS | ELEMENT VOLTAGE | FULL LOAD CURRENT IN AMPERES | IMMERSION THERMOSTATS | Number of KW Step Size | |||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
208V | 240V | 600V | Number of Fuses (30A Class G) | Number of Contactors | Optional Models – Staged Models with Suffix "F" | Number of Thermostats | ||||||||||
1 Phase | 3 Phase | 3 Phase | 1 Phase | 3 Phase | 3 Phase | 1 Phase | 3 Phase | 3 Phase | 208/240V | 600V | 208/240V | 600V | ||||
6 | 9 | 3 | 3000 | 43 | 25 | 38 | 22 | 9 | 6 | 3 | 2 | 1 | 1 | N/A | 9 | |
9 | 3 | 4000 | 58 | 33 | 50 | 29 | 12 | 6 | 3 | 2 | 1 | 1 | ONE THERMOSTAT STANDARD | 12 | ||
12 | 3 | 5000 | 72 | 42 | 63 | 36 | 15 | 6 | 3 | 2 | 1 | 1 | 15 | |||
15 | 3 | 6000 | 87 | 50 | 75 | 43 | 18 | 6 | 3 | 2 | 1 | 1 | 18 | |||
18 | 3 | |||||||||||||||
24 | 6 | 4000 | 116 | 67 | 100 | 58 | 23 | 12 | 6 | 4 | 2 | 1 | 2 | 12 | ||
30 | 6 | 5000 | 144 | 84 | 125 | 73 | 29 | 12 | 6 | 4 | 2 | 1 | 2 | 15 | ||
36 | 6 | 6000 | 173 | 100 | 150 | 87 | 35 | 12 | 6 | 4 | 2 | 1 | 2 | 18 | ||
45 | 9 | 5000 | 217 | 125 | 188 | 109 | 43 | 18 | 9 | 6 | 3 | 1 | 3 | 15 | ||
54 | 9 | 6000 | 260 | 150 | 225 | 130 | 52 | 18 | 9 | 6 | 3 | 1 | 3 | 18 |
Recovery Capacities
Recovery in U.S. Gallons/Hr. (GPH) and Liters/Hr. (LPH) at Various Temperature Rises
INPUT KW | EQUIVALENT BTU/HR. | UNITS | Temperature Rise (°F / °C) | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
40°F (22°C) | 50°F (28°C) | 60°F (33°C) | 70°F (39°C) | 80°F (45°C) | 90°F (50°C) | 100°F (56°C) | 110°F (61°C) | 120°F (67°C) | 130°F (72°C) | 140°F (78°C) | |||
6 | 30,709 | GPH | 93 | 74 | 62 | 53 | 47 | 41 | 37 | 34 | 31 | 29 | 27 |
LPH | 352 | 282 | 235 | 201 | 176 | 157 | 141 | 128 | 117 | 108 | 101 | ||
9 | 40,946 | GPH | 124 | 99 | 83 | 71 | 62 | 55 | 50 | 45 | 41 | 38 | 35 |
LPH | 470 | 376 | 313 | 268 | 235 | 209 | 188 | 171 | 157 | 145 | 134 | ||
12 | 51,183 | GPH | 155 | 124 | 103 | 89 | 78 | 69 | 62 | 56 | 52 | 48 | 44 |
LPH | 587 | 470 | 391 | 335 | 294 | 261 | 235 | 213 | 196 | 181 | 168 | ||
15 | 61,420 | GPH | 186 | 149 | 124 | 106 | 93 | 83 | 74 | 68 | 62 | 57 | 53 |
LPH | 705 | 564 | 470 | 403 | 352 | 313 | 282 | 256 | 235 | 217 | 201 | ||
18 | 81,893 | GPH | 248 | 199 | 165 | 142 | 124 | 110 | 99 | 90 | 83 | 76 | 71 |
LPH | 939 | 751 | 626 | 537 | 470 | 417 | 376 | 342 | 313 | 289 | 268 | ||
24 | 102,366 | GPH | 310 | 248 | 207 | 177 | 155 | 138 | 124 | 113 | 103 | 95 | 89 |
LPH | 1174 | 939 | 783 | 671 | 587 | 522 | 470 | 427 | 391 | 361 | 335 | ||
30 | 122,839 | GPH | 372 | 298 | 248 | 213 | 186 | 165 | 149 | 135 | 124 | 115 | 106 |
LPH | 1409 | 1127 | 939 | 805 | 705 | 626 | 564 | 512 | 470 | 434 | 403 | ||
36 | 153,549 | GPH | 465 | 372 | 310 | 266 | 233 | 207 | 186 | 169 | 155 | 143 | 133 |
LPH | 1761 | 1409 | 1174 | 1006 | 881 | 783 | 705 | 640 | 587 | 542 | 503 | ||
45 | 184,259 | GPH | 558 | 447 | 372 | 319 | 279 | 248 | 223 | 203 | 186 | 172 | 160 |
LPH | 2114 | 1691 | 1409 | 1208 | 1057 | 939 | 845 | 769 | 705 | 650 | 604 |
Dimensional Information
MODEL NUMBER | UNITS | DIMENSIONS | APPROX. SHIPPING WEIGHT (LBS.) | ||||
---|---|---|---|---|---|---|---|
A | B | C | D | E | |||
EG50 | inches | 43-5/8 | 26-1/4 | 36-1/4 | 32 | 17-1/4 | 270 lbs. (122 kgs.) |
mm | 1108 | 667 | 920 | 813 | 438 | ||
EG85 | inches | 57-11/16 | 28-1/4 | 49-1/2 | 34 | 18-1/4 | 350 lbs. (159 kgs.) |
mm | 1465 | 718 | 1258 | 864 | 464 | ||
EG120 | inches | 67-5/8 | 30-1/4 | 58-3/4 | 36 | 19-1/4 | 430 lbs. (185 kgs.) |
mm | 1718 | 768 | 1493 | 914 | 489 |
Diagram Description: The diagram illustrates the physical layout and connection points of the water heater. Key dimensions are labeled A through E. Notable connection points include a 3/4" T&P (Temperature and Pressure Relief) valve, a 1 1/2" hot outlet nipple, and a 1 1/2" cold inlet nipple. The System Sentinel diagnostic panel and an automatic temperature control (for immersion models) are also indicated.
Additional Construction Features
ELECTRICAL CONNECTIONS
Prewired, accessible control box with multiple knock-outs on top and side in size selections to match the Canadian Electrical Code. Sizes range from 1/2" to 2". A grounding screw is provided for attaching an equipment grounding conductor.
STANDARD EQUIPMENT ASME T&P VALVE
This is a double safety valve that relieves when temperature or pressure becomes excessive.
AUTOMATIC TEMPERATURE CONTROL
Water temperature settings from OFF and ranging from 90°F up to 180°F (32°C to 82°C) are maintained by immersion thermostat that insures instant shut off at the selected temperature for safety and economy of operation. One thermostat is supplied as standard. For element steps, up to two additional thermostats can be supplied – see optional controls. Over temperature protection is provided by an immersed high temperature limit control, factory set at 200°F (93°C).
MAGNETIC CONTACTORS
All models equipped with contactors, factory wired for simplicity of installation and economical maintenance throughout life of the unit.
240 VOLT CONTROL CIRCUIT
All units are furnished with a 240 volt control circuit. All controls (thermostats, high temperature limit, etc.) are operated off of this basic 240 volt control circuit.
Optional Equipment
ELEMENT FUSING
In addition to all the above construction features, on immersion thermostat models 9 KW through 54 KW there is internal fusing available that protects all elements, magnetic contactors, thermostats and internal wiring circuits. On immersion thermostat models 24 KW and above, additional thermostats are provided so that the maximum element input will not exceed 18 KW per step. Temperature differential between steps can be set as desired. On 24 through 36 KW units, two thermostats are provided and on the 45 and 54 KW units, three thermostats are provided.
For optional fusing, suffix "F" should be added to the model number. Ex. EG120CF-45KW.
Sample Specifications
Water heater(s) shall be Rheemglas Commercial Electric Model ________________, having an input of __________ KW and a recovery rate of _____________ GPH at a _______°F temperature rise, and equipped for ________volt, ________phase operation. Tank shall be lined with a double coating of exclusive Rheemglas high temperature glass formula and furnished with rigidly supported anode rods. Tank shall be designed for 150 PSI working pressure. Tank shall be completely insulated with R-Foam® insulation having a minimum insulating factor of R-16. Water heater shall be equipped with immersion “screw-in” elements, immersion thermostat, magnetic contactors, and manual reset high temperature limit control. Large terminal block that accepts either CU or AL field connect wire, plus grounding screw for attaching an equipment grounding conductor. Water heater shall include a factory installed System Sentinel element diagnostic panel utilizing light emitting diodes. Each L.E.D. will correspond to the number and location of the heating element and monitor their on-off function.
Optional: Thermostats for staging input into maximum element step that will not exceed 18 KW per step. (See table for number of thermostats available.)
Warranty
THREE YEAR LIMITED WARRANTY
This product features a three year limited warranty against tank leaks. Please refer to Commercial Warranty Information brochure for complete warranty information.