Stealth Designer 36000 BTU Slim Duct Heat Pump System
Submittal Data: SC-36CD-UM / SC-36Z-UM
General Features
- Multi-Speed Fan
- Medium Static Pressure Capability
- Return Air From Rear Only
- Internal Condensate Drain Pump
- Sentry Condensate Overflow Protection
- Wired Remote Controllers
- Acrylic Resin/Anti-Corrosion Fin Coating
System Ratings
Cooling
Rated Capacity | 34000 BTU/H |
Capacity Range | 10800-39000 BTU/H |
Power Input (Max) | 4500 W |
SEER | 16.0 |
EER | 10.4 |
Heating at 47° F
Rated Capacity | 41000 BTU/H |
Capacity Range | 9800-49500 BTU/H |
Power Input (Max) | 4600 W |
HSPF | 9.0 |
COP | 3.2 |
Heating at 17° F
Rated Capacity | 24600 BTU/H |
Operating Range
Cooling (Max) | 118°F (48°C) |
Cooling (Min) | 0°F (-18°C) |
Heating (Max) | 75°F (24°C) |
Heating (Min) | 0°F (-18°C) |
Refrigerant Piping Data
Gas Pipe Size (OD) | 5/8-in |
Liquid Pipe Size (OD) | 3/8-in |
Connection Method | Flared |
Factory Charge | 123.2 oz |
Additional Charge | 0.6 oz/ft |
Pre-Charge Length | 25-ft |
MAX Refrigerant Pipe Length | 164-ft |
MIN Refrigerant Pipe Length | 10-ft |
MAX Refrigerant Pipe Elevation | 49-ft |
Indoor Unit Data
Feature | Value |
---|---|
Fan Motor Output Power | 249 W |
FLA | 2.1 A |
Airflow Cooling Wet (Lo/Hi) | 950/1175 CFM |
Airflow Heating Dry (Lo/Hi) | 950/1175 CFM |
Sound Power Level Cooling (Min/Max) | 44/52 dB(A) |
Sound Power Level Heating (Min/Max) | 44/52 dB(A) |
Dehumidification | 1.28 pt/hr |
Condensate Drain Lift (Height) | 33-in |
Power Supply (Dedicated Circuit: Size Per Local Code) | 208/230 V, 1 Phase, 60 Hz |
Voltage Range | 187-253 V |
MCA | 3 A |
MOCP/Breaker Size | 15A |
Communication Wire Size | 18-2 AWG / 300V THHN |
Outdoor Unit Data
Feature | Value |
---|---|
Compressor | DC Inverter Driven Rotary |
RLA | 21.2 A |
Refrigerant Type | R410A |
Fan Motor Output Power | 2/9HP |
FLA | 2.0 A |
Sound Power Level Cooling/Heating | 63/63 dB(A) |
Power Supply (Dedicated Circuit) | 208/230 V, 1 Phase, 60 Hz |
Normal Operational Voltage | 187-253 V |
Main Supply Wire Size | 8 AWG |
MCA | 27.7 A |
MOCP/Breaker Size | 45 A |
Features & Function Summary
System Features
Feature | Status |
---|---|
Inverter Type | G10 |
Ultra Low Frequency Torque Control | YES |
Power Factor Correction | YES |
Compressor Type | Rotary |
Refrigerant Type | R410A |
Basepan With Electric Heater | YES |
Compressor With Electric Heater | NO |
Outdoor Fin Coating | Acrylic Resin |
Intelligent Defrosting | YES |
Intelligent Preheating | YES |
Low Voltage Startup | YES |
Memory/Power Failure Recovery | YES |
Self Diagnosis | YES |
Low Ambient Cooling | YES |
Internal Condensate Pump | YES |
XK60 Wired Controller Interface | YES |
Wi-Fi Interface | NO |
Indoor Fan Type | Centrifugal |
Multi Fan Speeds | 3 Speeds |
LED Display Indoor Unit | NO |
Advance Filter | NO |
Auxiliary Electrical Heater | NO |
Ventilation (Outdoor Air) | Optional |
Wired Controller Functions
Function | Status |
---|---|
Auto Mode | YES |
Auto Fan | YES |
Auto Swing (Continuous Sweep) | NO |
Adjustable Swing Louvers (5 pos.) | NO |
Clock on Remote Controller | YES |
Dry Mode | YES |
Dry Anti-Mildew (X-Fan) Mode | YES |
Energy Saving Mode | NO |
Dirty Filter Alert | NO |
I Feel Function | YES |
Lock on Wired Controller | YES |
Quiet Mode | NO |
Room Temperature Display (5 sec.) | YES |
Sleep Mode | YES |
Timer Mode | YES |
Turbo Mode | YES |
Display On/Off Control | NO |
Freeze Guard Mode | YES |
Performance Data
Fan Performance Curves
This section describes the relationship between Air Flow Volume (CFM) and External Static Pressure (InWa) for different fan speeds:
- Super high speed: Shows the highest airflow volume across the tested static pressure range.
- High speed: Offers slightly lower airflow than super high speed.
- Middle speed: Provides a moderate airflow volume.
- Low speed: Delivers the lowest airflow volume.
The curves generally show a decrease in airflow volume as external static pressure increases for all speeds.
Cooling Performance
This graph illustrates the cooling capacity (BTU) of the unit at various outdoor dry bulb temperatures (°F). The capacity generally increases as the outdoor temperature rises from 68°F to 95°F, peaking around 95°F, and then slightly decreases at 104°F and 113°F.
Heating Performance
This graph shows the heating capacity (BTU) of the unit at various outdoor dry bulb temperatures (°F). The capacity increases significantly as the outdoor temperature rises from 14°F to 50°F.
Minimum Spacing Requirements
Indoor Unit
Diagram shows the indoor unit mounted to a ceiling. Minimum clearances are indicated:
- Sides: Greater than 12 inches (305 mm) from walls.
- Front/Bottom: Greater than 72 inches (2195 mm) clearance.
Outdoor Unit
Diagram shows the outdoor unit with required clearances for airflow:
- Sides: Greater than 20 inches (500 mm) from obstructions.
- Front: Greater than 40 inches (1000 mm) from obstructions.
- Rear Inlet: Greater than 20 inches (500 mm) from obstructions.
- Rear Discharge: Greater than 80 inches (2000 mm) from obstructions.
Dimensional Specifications
Indoor Unit Dimensions & Weights
The indoor unit has the following dimensions (referencing labels A-J):
Label | Dimension (inch/mm) |
---|---|
A | 39.75 (1011) |
B | 29.5 (748) |
C | 32.25 (820) |
D | 43.875 (1115) |
E | 48.25 (1226) |
F | 30.5 (775) |
G | 38.5 (979) |
H | 6.25 (160) |
I | 9.125 (231) |
J | 11.375 (290) |
Net Weight: 101.2 lbs
Shipping Weight: 116.6 lbs
Refrigerant Line Connections:
- Liquid Line Valve: 3/8-in OD Flared
- Gas Line Valve: 5/8-in OD Flared
- Drain Connector: 13/16 in OD
Notes:
- Refrigerant line sizes are based on evaporator port sizes.
- Refrigerant and Drain pipe configurations vary by unit size.
- Pump Drain outlet is positioned above the gravity drain outlet.
Outdoor Unit Dimensions & Weights
The outdoor unit has the following dimensions (referencing labels A-E):
Label | Dimension (inch/mm) |
---|---|
A | 43.625 (1107) |
B | 17.375 (440) |
C | 43.25 (1100) |
D | 24.875 (631) |
E | 15.75 (400) |
Net Weight: 204.6 lbs
Shipping Weight: 222.2 lbs
Refrigerant Line Connections:
- Liquid Line Valve: 3/8-in OD Flared
- Gas Line Valve: 5/8-in OD Flared
Notes:
- Recommended Communication Wire: Type 18-2 AWG Stranded Copper THHN 300V Wire.
- Power wiring size must comply with applicable national and local codes for both ID and OD dedicated circuits.
- Test conditions are based on AHRI 210/240.
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.