STEALTH SC-18CD-UM / SC-18Z-UM: 18,000 BTU Slim Duct Heat Pump System
Submittal Data
General Features
- Multi-Speed Fan
- Medium Static Pressure Capability
- Flexible Return Air From Bottom Or Rear
- Internal Condensate Drain Pump
- Sentry Condensate Overflow Protection
- Wired Remote Controllers
- Acrylic Resin/Anti-Corrosion Fin Coating
System Ratings
Cooling | Indoor Unit Data | ||
---|---|---|---|
Rated Capacity | 17100 BTU/H | Fan Motor Output Power | 60 W |
Capacity Range | 5400-19800 BTU/H | FLA | 0.6 A |
Power Input (Max) | 1750 W | Airflow | |
SEER | 16.0 | Cooling Wet (Lo/Hi) | 362/585 CFM |
EER | 11.0 | Heating Dry (Lo/Hi) | 362/585 CFM |
Heating at 47° F | Sound Level | ||
Rated Capacity | 18800 BTU/H | Cooling (Min/Max) | 28/39 dB(A) |
Capacity Range | 4700-23200 BTU/H | Heating (Min/Max) | 28/39 dB(A) |
Power Input (Max) | 1900 W | Dehumidification | |
HSPF | 9.5 | Condensate Drain Lift (Height) | 33-in |
COP | 3.3 | ||
Heating at 17° F | Power Supply (Dedicated Circuit: Size Per Local Code) | ||
Rated Capacity | 10900 BTU/H | Normal Operational Voltage | 208/230 V, 1 Phase, 60 Hz |
Operating Range | Voltage Range | 187-253 V | |
Cooling (Max) | 118°F (48°C) | MCA | 1.0A |
Cooling (Min) | 0°F (-18°C) | MOCP/Breaker Size | 15A |
Heating (Max) | 75°F (24°C) | Communication Wire Size | |
Heating (Min) | 0°F (-18°C) | 18-2 AWG / 300V THHN |
Outdoor Unit Data | |
---|---|
Compressor | DC Inverter Driven Rotary |
RLA | 12.0 A |
Refrigerant Type | R410A |
Fan Motor Output Power | 1/6HP |
FLA | 1.5 A |
Sound Level Cooling/Heating | 56/56 dB(A) |
Power Supply (Dedicated Circuit) | |
Normal Operational Voltage | 208/230 V, 1 Phase, 60 Hz |
Voltage Range | 187 - 253 V |
Main Supply Wire Size | 10 AWG |
MCA | 15.9 A |
MOCP/Breaker Size | 25 A |
Refrigerant Piping Data
Gas Pipe Size (OD) | 1/2-in |
Liquid Pipe Size (OD) | 1/4-in |
Connection Method | Flared |
Factory Charge | 49.6 oz |
Additional Charge | 0.3 oz/ft |
Pre-Charge Length | 25-ft |
MAX Refrigerant Pipe Length | 164-ft |
MIN Refrigerant Pipe Length | 10-ft |
MAX Refrigerant Pipe Elevation | 49-ft |
Features & Function Summary
System Features
Inverter Type | G10 |
Ultra Low Frequency Torque Control | YES |
Power Factor Correction | YES |
Compressor Type | Rotary |
Refrigerant Type | R410A |
Basepan With Electric Heater | YES |
Compressor With Electric Heater | NO |
Outdoor Fin Coating | Acrylic Resin |
Intelligent Defrosting | YES |
Intelligent Preheating | YES |
Low Voltage Startup | YES |
Memory/Power Failure Recovery | YES |
Self Diagnosis | YES |
Low Ambient Cooling | YES |
Internal Condensate Pump | YES |
XK60 Wired Controller Interface | YES |
Wi-Fi Interface | NO |
Indoor Fan Type | Centrifugal |
Multi Fan Speeds | 3 Speeds |
LED Display Indoor Unit | NO |
Advance Filter | NO |
Auxiliary Electrical Heater | NO |
Ventilation (Outdoor Air) | Optional |
Wired Controller Functions
Auto Mode | YES |
Auto Fan | YES |
Auto Swing (Continuous Sweep) | NO |
Adjustable Swing Louvers (5 pos.) | NO |
Clock on Remote Controller | YES |
Dry Mode | YES |
Dry Anti-Mildew (X-Fan) Mode | YES |
Energy Saving Mode | NO |
Dirty Filter Alert | NO |
I Feel Function | YES |
Lock on Wired Controller | YES |
Quiet Mode | NO |
Room Temperature Display (5 sec.) | YES |
Sleep Mode | YES |
Timer Mode | YES |
Turbo Mode | YES |
Display On/Off Control | NO |
Freeze Guard Mode | YES |
Performance Curves
Fan Performance Curves
This graph illustrates the relationship between external static pressure and airflow volume for different fan speeds.
- X-axis: External Static Pressure (InWg)
- Y-axis: Air Flow Volume (CFM)
- Lines: Representing Super high speed, High speed, Middle speed, and Low speed. Airflow decreases as static pressure increases for all speeds.
Cooling Performance
This graph shows the cooling capacity in BTU/H relative to the outdoor dry bulb temperature in °F.
- X-axis: Outdoor dry bulb temperature (°F)
- Y-axis: Capacity/BTU
- The graph indicates that cooling capacity increases as the outdoor temperature rises from 68°F to 113°F.
Heating Performance
This graph displays the heating capacity in BTU/H relative to the outdoor dry bulb temperature in °F.
- X-axis: Outdoor dry bulb temperature (°F)
- Y-axis: Capacity/BTU
- The graph shows that heating capacity increases as the outdoor temperature rises from 14°F to 50°F.
Minimum Spacing Requirements
Indoor Unit Spacing
Diagram showing minimum clearance requirements for the indoor unit, typically mounted in a ceiling.
- Clearance from sides: >12 inches (305 mm)
- Clearance from ceiling: >72 inches (2195 mm)
Outdoor Unit Spacing
Diagram illustrating minimum clearance requirements for the outdoor unit.
- Front clearance: >40 inches (1000 mm)
- Side clearances: >20 inches (500 mm)
- Discharge clearance: >80 inches (2000 mm)
- Inlet clearance: >20 inches (500 mm)
Dimensional Specifications
Indoor Unit Dimensions & Weights
Diagram showing the indoor unit with labeled dimensions (A-J) and notes regarding refrigerant lines and drain outlet.
Dimension | Units: inch (mm) |
---|---|
A | 37.25 (945) |
B | 24.375 (618) |
C | 29.0 (738) |
D | 35.125 (892) |
E | 40.88 (1037) |
F | 28.375 (721) |
G | 29.0 (738) |
H | 4.875 (125) |
I | 8.0 (203) |
J | 10.5 (266) |
Net Weight: 72.6 lbs
Shipping Weight: 83.6 lbs
Refrigerant Line Connections: Liquid Line Valve: 1/4-in OD Flared, Gas Line Valve: 1/2-in OD Flared
Drain Connector: 1-3/16 in OD
Notes:
- Size refrigerant lines based on evaporator port sizes.
- Refrigerant and Drain pipe configurations vary by unit size.
- Pump Drain outlet is above gravity drain outlet.
Outdoor Unit Dimensions & Weights
Diagram showing the outdoor unit with labeled dimensions.
Dimension | Units: inch (mm) |
---|---|
Width | 22 (560) |
Depth | 15.6 (396) |
Height | 37.6 (955) |
Other Dimension | 27.5 (700) |
Net Weight: 105.6 lbs
Shipping Weight: 114.4 lbs
Refrigerant Line Connections: Liquid Line Valve: 1/4-in OD Flared, Gas Line Valve: 1/2-in OD Flared
Notes:
- Recommended Communication Wire Type: 18-2 AWG Stranded Copper THHN 300V Wire
- Power wiring size must comply with applicable national and local codes for both ID and OD dedicated circuits.
- Test conditions are based on AHRI 210/240.
Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.