STEALTH Multi-Room Ductless Heat Pump System SC-27Z-HH-M3 Submittal Data

Job Information

Job NameLocationDate
PurchaserEngineer
Submitted ToFor ☐ Reference ☐ Approval ☐ ConstructionSchedule No.
Unit Designation

General Features

System Ratings

System Ratings
Rated Cooling Capacity22,000 BTUH
Cooling Capacity (min-max)7,500-33,000 BTUH
Rated Heating Capacity26,000 BTUH
Heating Capacity (min-max)7,500-31,000 BTUH
SEER/EER23.0 / 12.5
HSPF/COP10.5 / 3.7

Outdoor Unit Data

Description of Outdoor Unit: A rectangular outdoor unit with a fan grille on the front, labeled "STEALTH".

Outdoor Unit Data
Compressor TypeDC Inverter Driven Rotary
RLA17.0 A
Starting Current5.0 A
Fan Motor Output Power90 W
FLA0.4 A
Air Flow (Max)2531 CFM

Sound Pressure Level

Cooling60 dB(A)
Heating60 dB(A)

Dimensions & Weights

Unit Dimensions Overall (WxDxH)*39.5 x 16.8 x 31.1-in
* including Valve Covers and Grilles
Weight (Net/Shipping)174/185-lbs

Operating Range

Min. Number of Indoor UnitsMax. Number of Indoor Units
Cooling - Low/High Ambient (min-max)0-118°F2
-18-48°C3
Heating - Low Ambient (ULTRA) (min-max)-31-75°F
-35-24°C

Refrigerant Piping Data

Refrigerant TypeR410A
Refrigerant Charge95.2 oz
Additional Charge Per Line Length0.2-oz/ft
Connection Method-Flared1/4x3/8-in
Factory Charge for Total Line Length98-ft
Total Refrigerant Pipe Length230-ft
Max Refrigerant Piping Length to any Indoor Unit82-ft
Min Refrigerant Piping Length to any Indoor Unit10-ft
Max Elevation between Indoor Units26-ft
Max Lift from Outdoor to Indoor Unit26-ft
Max Drop from Outdoor to Indoor Unit26-ft

Power Supply

Normal Operational Voltage208/230 V, 1 Phase, 60 Hz
Voltage Range187-253 V
Main Power Wire Size10-2 AWG
Interconnecting Cable Wire Size14-4 AWG
MCA23.0 A
MOCP/Breaker Size40 A

Certifications: INVERTER, R410A non ozone-depleting, AHRI CERTIFIED, ETD LISTED.

Features & Function Summary (SC-27Z-HH-M3)

System Features

FeatureDescription
Compressor TypeInverter Rotary
Core Technology Three Cylinder Two Stage CompressorG10
Ultra Low Frequency Torque ControlYES
Power Factor CorrectionYES
Refrigerant TypeR410A
Electronic Expansion Valve (EEV)3
Basepan With Electric HeaterYES
Compressor PreheatYES
Compressor With Electric Heater (-40°F)YES
-40°F Wiring UL ApprovedYES
Multi "Independent" Port DesignYES
Condenser FanAxial
Condenser Motor TypeDC
Condenser Motor DriveDirect
Condenser CoilAluminum Fin/Copper Tube
Outdoor Fin Coating (Blue)Acrylic Resin
Intelligent DefrostingYES
Low Voltage StartupYES
Memory/Power Failure RecoveryYES
Self DiagnosisYES
Ultra Heating (-31°F - 75°F)YES
Ultra Cooling (0°F - 118°F)YES
Wired Controller InterfaceYES

Remote Controller Functions¹

See individual Indoor Unit Controllers Functions

¹ Not all Remote Controller functions are supported.

Wired Controller Functions²

FunctionSupported
On/OffYES
Operating ModeYES
Fan SpeedYES
Room SetpointYES
Model NumbersYES
Timer ModeYES
Sleep ModeYES
Turbo ModeYES
X-Fan ModeYES
Privacy LockYES

² Note: Some indoor models may not support specific system features or functions.

Outdoor Unit Dimensional Specifications (SC-27Z-HH-M3)

24000 BTUH MODEL

Model # SC-27Z-HH-M3 24000 BTUH 230V

Outdoor Unit Dimensions (Units: inch)

Diagram Description: The outdoor unit is shown from two perspectives: a front/side view and a top view. Key dimensions are labeled A, B, C for the front/side view and D, L, W for the top view. The unit has a fan grille on one side and piping connections on another.

DimensionValue (in)
A (width)36.2
B (depth)14.6
C (height)31.1
D (length)24.0
L (length)15.6
W (width)2.4
Weight (Net/Shipping)Value (lbs)
174/185 lbs

Suction/Gas Line Port Size

Port #Size
Port #13/8-in OD Flared
Port #23/8-in OD Flared
Port #33/8-in OD Flared

Liquid Line Port Size

Port #Size
Port #11/4-in OD Flared
Port #21/4-in OD Flared
Port #31/4-in OD Flared

Minimum Spacing Requirements (Units: inch (mm))

Diagram Description: A diagram showing the outdoor unit with required minimum clearances around it for proper airflow and maintenance. An "Air inlet" is shown on one side and "Air outlet" on another. The clearances are:

Notes:

  1. Recommended Interconnecting Cable Type: Stranded Copper Conductors THHN 600V Unshielded Wire.
  2. Power wiring cable size must comply with applicable national and local codes.
  3. Test conditions are based on AHRI 210/240.

Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.

Extended Ratings (SC-27Z-HH-M3)

Cooling Performance (BtuH)*

Indoor Entering Air Temperatures

Outdoor Ambient Temperature (DB) °F68°F DB
57°F WB
73°F DB
61°F WB
80°F DB
67°F WB
TCSHCTCSHCTCSHC
0°F170671338518044141371987015590
5°F176641385218674146312056416135
14°F185021451119546153242205917302
23°F202711590121682170082484319485
32°F215411689422756178472568220137
41°F223151750223566184822693121116
50°F227041780624284190452782521817
59°F245821927926293206212879722579
68°F278402183529580231963161024792
77°F275112158029261229513132024567
86°F261582051327898218843045023882
95°F247561941726487207682900022746
104°F235581847725278198282824622158
113°F229491799724679193482764721678

Heating Performance (BtuH)*

Indoor Entering Air Temperatures

Outdoor Ambient Temperature (DB) °F68°F DB
57°F WB
73°F DB
61°F WB
80°F DB
67°F WB
TCPower Input (KW)COPTCPower Input (KW)COPTCPower Input (KW)COP
-31°F215005.451.16210005.501.12205005.701.05
-22°F249545.501.33242925.571.28238015.741.21
-13°F273245.581.44266145.641.38260895.821.31
-5°F318465.421.72310345.481.66304335.661.58
0°F313765.511.67305505.581.61299335.751.52
5°F315235.241.76307035.301.70300975.461.61
10°F318725.291.77310445.351.70304235.521.62
17°F312685.251.75304485.311.68298255.481.60
19°F308524.911.84304274.961.80298025.121.71
24°F299035.081.72295465.141.68290115.301.60
32°F291354.861.76288144.921.72283445.071.64
41°F302814.501.97299844.551.93295354.691.84
43°F311103.522.59308133.562.54303733.672.42
47°F340003.602.77330653.642.66323663.762.52
53°F343403.273.08333943.312.96326953.412.81
59°F316143.302.81307343.342.70300853.452.56
64°F322833.033.12313943.063.00307343.162.85
70°F328953.083.13319873.113.01313083.212.86
75°F333542.813.48324362.843.34317572.933.17
78°F336602.843.48327322.873.34320442.963.17

* Maximum system capacity

TC- Total Capacity (BtuH)

COP- Coefficient of Performance

Operational Performance Specifications (SC-27Z-HH-M3)

Cooling Capacity (BTUH)

Indoor Units CombinationsRated System Capacity (BtuH)Indoor Unit Capacity (BtuH)
Unit AUnit BUnit CUnit D
9K + 9K18,0009,0009,000NANA
9K + 12K21,0009,00012,000NANA
9K + 18K25,0008,40016,600NANA
12K + 12K24,00012,00012,000NANA
12K + 18K25,00010,00015,000NANA
18K + 18K26,00013,00013,000NANA
9K + 9K + 9K26,0018,6678,6678,667NA
9K + 9K + 12K26,0008,0008,00010,000NA
9K + 9K + 18K29,0008,0008,00013,000NA
9K + 12K + 12K29,6008,00010,80010,800NA
12K + 12K + 12K30,00010,00010,00010,000NA

Heating Capacity (BTUH)

Indoor Units CombinationsRated System Capacity (BtuH)Indoor Unit Capacity (BtuH)
Unit AUnit BUnit CUnit D
9K + 9K18,0009,0009,000NANA
9K + 12K21,0009,00012,000NANA
9K + 18K27,0009,00018,000NANA
12K + 12K26,00013,00013,000NANA
12K + 18K30,00012,00018,000NANA
18K + 18K31,00015,50015,500NANA
9K + 9K + 9K27,0009,0009,0009,000NA
9K + 9K + 12K29,0009,0009,00011,000NA
9K + 9K + 18K31,0008,0008,00015,000NA
9K + 12K + 12K31,0009,00011,00011,000NA
12K + 12K + 12K31,05010,35010,35010,350NA

Capacity data is based on the following conditions:

Cooling Nominal Test Conditions

Heating Nominal Test Conditions

Specifications are subject to change without notice. Manufacturer reserves the right to discontinue or modify specifications or designs without notice or without incurring obligations. All rights reserved.

PDF preview unavailable. Download the PDF instead.

Stealth MZ Condenser 24k Submittal Lenovo User Adobe PDF Library 20.13.96

Related Documents

Preview Stealth SC-36CD-UM / SC-36Z-UM 36000 BTU Slim Duct Heat Pump System Submittal Data
Detailed submittal data and specifications for the Stealth Designer 36000 BTU Slim Duct Heat Pump System (models SC-36CD-UM and SC-36Z-UM), including general features, system ratings, performance data, dimensional specifications, and minimum spacing requirements.
Preview STEALTH SC-18CD-UM / SC-18Z-UM: 18,000 BTU Slim Duct Mini Split Heat Pump Submittal Data
Detailed submittal data for the STEALTH SC-18CD-UM and SC-18Z-UM 18,000 BTU ductless mini-split heat pump system. Includes system ratings, features, performance curves, spacing requirements, and dimensional specifications.
Preview Stealth Pinnacle Wall Mount Ductless Air Conditioning & Heating System Owner's Manual
Comprehensive owner's manual for the Stealth Pinnacle series of wall mount ductless air conditioning and heating systems. Covers safety precautions, system functions, remote control operation, smart control features, troubleshooting common issues, care and cleaning instructions, energy saving tips, and warranty information.
Preview Stealth Designer Floor Ceiling Air Conditioning & Heating System Quick-Start Guide
Quick-start guide for the Stealth Designer Floor Ceiling Air Conditioning & Heating System (Models SC-18FM-UM, SC-24FM-UM), detailing remote control functions, key features, and frequently asked questions.
Preview Stealth Welding Machines, Helmets, PAPR & Safety Products | SWP
Explore the comprehensive range of Stealth welding machines, including MIG, TIG, and ARC inverters, plasma cutters, and advanced welding safety products like helmets and PAPR systems from SWP.
Preview Operator's Manual: MIG 300-1 Inverter Welding Machine
Comprehensive operator's manual for the Stealth MIG 300-1 Inverter welding machine, covering safety, features, technical data, installation, operation, troubleshooting, and maintenance.
Preview Stealth Light Up XL Gaming Mat Quick Start Guide
Official quick start guide for the Stealth Light Up XL Gaming Mat, providing setup instructions, warranty information, safety precautions, and support contact details.
Preview STEALTH ECVP01 Wet Dry Vacuum Cleaner and Mop User Manual
Comprehensive user manual for the STEALTH ECVP01 Wet Dry Vacuum Cleaner and Mop, including safety instructions, assembly, operation, cleaning, maintenance, troubleshooting, and specifications. Learn how to use and care for your ECVP01 for optimal performance.