SOPHIA SERIES Middle Static Pressure Duct Type Installation Manual

Models: CH-M09DTUI, CH-M12DTUI, CH-M18DTUI, CH-M24DTUI, CH-24LCUO

IMPORTANT NOTE: Read this manual carefully before installing or operating your new air conditioning unit. Be sure to save this manual for future reference.

Section 1: Accessories

The air conditioning system comes with the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock and fire, or cause the equipment to fail.

NAME SHAPE QUANTITY
Tubing & Fittings: Soundproof / insulation sheath [Coil icon] 2
Drainpipe Fittings (for cooling & heating): Drain joint (some models) [Drain joint icon] 1
Seal ring (some models) [Seal ring icon] 1
Others: Owner's manual [Document icon] 1
Installation manual [Document icon] 1
Transfer connector (some models) (Ø0.375in-Ø0.375in)/(Ø9.52-Ø9.52) (Packed with the indoor unit) [Connector diagram] 1
Component of display control unit (some models) [Control unit icon] 1
EMC Magnetic Ring (some models): Magnetic ring (wrap the electric wires S1 & S2 (P & Q & E) around the magnetic ring twice) [Ring diagram] 1
Magnetic ring (Hitch on the connective cable between the indoor unit and outdoor unit after installation.) [Ring diagram] 1

Optional accessories: There are two types of remote controls: wired and wireless. Select a remote control based on customer preferences and requirements and install in an appropriate place. Refer to catalogues and technical literature for guidance on selecting a suitable remote control.

Section 2: Safety Precautions

Read Safety Precautions Before Installation

Incorrect installation due to ignoring instructions can cause serious damage or injury. The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.

WARNING: Failure to observe a warning may result in death. The appliance must be installed in accordance with national regulations.

CAUTION: Failure to observe a caution may result in injury or equipment damage.

WARNING

Note about Fluorinated Gasses

  1. This air-conditioning unit contains fluorinated gasses. For specific information on the type of gas and the amount, please refer to the relevant label on the unit itself.
  2. Installation, service, maintenance and repair of this unit must be performed by a certified technician.
  3. Product uninstallation and recycling must be performed by a certified technician.
  4. If the system has a leak-detection system installed, it must be checked for leaks at least every 12 months.
  5. When the unit is checked for leaks, proper record-keeping of all checks is strongly recommended.

Section 3: Installation Overview

INSTALLATION ORDER

  1. Install the indoor unit (Page 7)
    Diagram shows an indoor unit.
  2. Install the outdoor unit (Page 13)
    Diagram shows an outdoor unit.
  3. Install the drainpipe (Page 16)
    Diagram shows a drainpipe.
  4. Connect the refrigerant pipes (Page 18)
    Diagram shows pipes connecting.
  5. Connect the wires (Page 21)
    Diagram shows wiring terminals.
  6. Evacuate the refrigeration system (Page 25)
    Diagram shows pressure gauges.
  7. Perform a test run (Page 27)
    Diagram shows a unit operating.

Section 4: Indoor Unit Installation

Indoor Unit Parts

Diagram shows an indoor unit with labels for Air outlet, Air inlet, Heat exchanger, Air filter (optional), Electric control cabinet, Drain hose, and Refrigerant connecting pipe.

Safety Precautions

WARNING:

CAUTION:

CAUTION: DO NOT install the unit in the following locations:

Indoor Unit Installation Instructions

Step 1: Select installation location

The indoor unit should be installed in a location that meets the following requirements:

Diagram shows recommended clearances: Maintenance roomage 20 inches or more, Air inlet 23 inches or more, Air outlet 23x23 inches checking orifice.

Step 2: Hang indoor unit

1. Please refer to the following diagrams to locate the four positioning screw bolt holes on the ceiling. Be sure to mark the paces where you will drill ceiling hook holes. The size of installation for indoor unit following the Fig.4-3, This unit has installed with air filter.

Diagram Fig. 4.3 shows dimensions (A-O) with measurements in inches/mm for various models.
MODEL (Btu/h) Outline dimension A B C size of mounted lug D E air outlet opening size (symmetry of air outlet opening) F G H I J air inlet opening size (symmetry of air inlet opening) K L M N O
24K 20.6/525 35.4/900 10.6/270 15.6/397 36.8/936 33.2/844 7.2/185 6.3/160 30.7/780 4.7/120 33.5/851 8.9/226 8.4/215 26.2/665 4.3/110
30K~36K 20.6/525 43.7/1110 10.6/270 15.6/397 45/1146 41.5/1054 7.2/185 8.6/220 37.8/960 4.7/120 41.7/1061 8.9/226 12.4/315 34.4/875 4.3/110
45K~60K 24.6/625 47.2/1200 15/380 19.5/495 48.6/1236 39.3/1000 10/253 10.6/270 35.4/900 6.7/170 45/1145 13.1/334 12.8/325 36.4/925 5.1/130
55K~60K 33.8/858 55.1/1400 17.3/440 27.5/700 56.5/1436 46.7/1188 15/385 20/500 39.3/1000 11/280 46.7/1188 12.8/325 20/500 39.3/1000 11/280
Number Name fixed-frequency inverter
1 Gas pipe connection Ø5/8″ (24~36K units) Ø3/4″ (48~60K units) Ø5/8″
2 Liquid pipe connection Ø3/8″ Ø3/8″
3 Drain pipe connection OD Ø1″ ID Ø3/4″ OD Ø1″ ID Ø3/4″
4 Drain pipe connection Using drain pump (optional) Using drain pump (optional)
5 Power supply connection
6 Air inlet duct flange
7 Air outlet duct flange
8 Air filter optional optional

Step 3: Diagrammatic sketch for installing the main body

Installing the dust proof net and canvas air passage
  1. Install the dust proof net according to the installation manual.
  2. Install the canvas air passage underneath the dust proof net.

Step 4: Duct and accessories installation

  1. The air inlet and air outlet duct should be far enough apart to prevent air outlet entering Air Inlet.
  2. There is a dust filter on the indoor unit.
  3. Attach the outside air duct to the indoor air outlet/inlet flange using the type ST3.9 x 10 screw.
  4. Connect the duct according to the following diagram:
    Diagram Fig. 4.10 shows duct connections with labels for Isolation booth, Air outlet, Air inlet, and Air dust filter.

NOTES:

Step 5: Motor and drain pump maintenance

Pump maintenance:
  1. Remove four screws from the drain pump.
  2. Unplug the pump power supply and water level switch cable.
  3. Detach the pump.
    Diagram Fig. 4.11 shows a pump.
Motor maintain:

There are three methods:

  1. Method 1: Remove the front side plate from the top.
    • Remove the top cover.
      Diagram Fig. 4.12
    • Loosen the four bolts and two screws used to fasten the front side plate.
      Diagram Fig. 4.13
    • Remove the cord of the motor, take off the front side plate and repair the motor.
      Diagram Fig. 4.14
  2. Method 2: Remove the front side plate from the bottom.
    • Remove the bottom base.
      Diagram Fig. 4.15
    • Loosen the four bolts and two screws used to fasten the front side plate (Be careful, the front side plate may fall down).
      Diagram Fig. 4.16
    • Remove the cord of the motor, take off the front side plate and repair the motor.
      Diagram Fig. 4.17
  3. Method 3: Repair it directly (only applicable to plastic scroll and fan wheel).
    • Take off the chassis assembly and filter.
    • Take off the volute.
    • Take off the motor.
      Diagram Fig. 4.18 shows Motor, Volute, Filter, Chassis assembly.

Mounting Methods for Ceiling Installation

Wood: Place the wood mounting across the roof beam, then install the hanging screw bolts.

Diagram Fig. 4.4 shows Wood mounting, Roof beam, Ceiling, Hanging screw bolts.

New concrete bricks: Inlay or embed the screw bolts.

Diagram Fig. 4.5 shows (Blade shape insertion) and (Slide insertion).

Original concrete bricks: Use an embedding screw bolt, crock, and stick harness.

Diagram Fig. 4.6 shows Steel bar, Embedding screw bolt, Pipe hanging and embedding screw bolt.

Steel roof beam structure: Install and use the supporting steel angle.

Diagram Fig. 4.7 shows Hanging screw bolt, Hanging/bolts, Supporting angle steel.

Installation Steps (continued):

  1. Install hanging screw bolts. Cut off the roof beam. Strengthen the point at which the cut was made. Consolidate the roof beam.
  2. After you select an installation location, align the refrigerant pipes, drain pipes, as well as indoor and outdoor wires with their connection points before mounting the unit.
  3. Drill 4 holes 4″ (10cm) deep at the ceiling hook positions in the internal ceiling. Be sure to hold the drill at a 90° angle to the ceiling.
  4. Secure the bolt using the washers and nuts provided.
  5. Install the four suspension bolts.
  6. Mount the indoor unit with at least two people to lift and secure it. Insert suspension bolts into the unit's hanging holes. Fasten them using the washers and nuts provided.
    Diagram Fig. 4.8
  7. Mount the indoor unit onto the hanging screw bolts with a block. Position the indoor unit flat using a level indicator to prevent leaks.
    Diagram Fig. 4.9 shows Shockproof cushion, Screw nut, Washer, Overhang part, Hanging screw bolt.

CAUTION: The unit body must be completely aligned with the hole. Ensure that the unit and the hole are the same size before moving on.

NOTE: Confirm the minimum drain tilt is 1/100 or more.

Section 5: Outdoor Unit Installation

Outdoor Unit Installation Instructions

Step 1: Select installation location

The outdoor unit should be installed in the location that meets the following requirements:

Step 2: Install outdoor unit

Fix the outdoor unit with anchor bolts (M10).

Diagram Fig. 5.3 shows fixing the unit with bolts, indicating a clearance of >23.6" /60cm.
Diagrams Fig. 5.4, 5.5, 5.6 show Split Type Outdoor Unit dimensions and mounting.
Diagrams Fig. 5.7, 5.8, 5.9 show Vertical Discharge Type Outdoor Unit dimensions and mounting, including clearance from walls.
Table 5.1: Length Specifications of Split Type Outdoor Unit (unit: mm/inch)
Outdoor Unit Dimensions W x H x D Mounting Dimensions
Distance A Distance B
29.9x23.2x11.2 (760x590x285) 20.85 (530) 11.4 (290)
31.9x22x12.2 (810x558x310) 21.6 (549) 12.8 (325)
33.27x27.5x12.6 (845x700x320) 22 (560) 13.2 (335)
35.4x33.85x12.4 (900x860x315) 23.2 (590) 13.1 (333)
37.2x31.9x15.55 (945x810x395) 25.2 (640) 15.95 (405)
38.98x38x13.58 (990x965x345) 24.58 (624) 14.4 (366)
36.93x53.9x15.43 (938x1369x392) 24.96 (634) 15.9 (404)
35.4x46x13.8 (900x1170x350) 23.2 (590) 14.88 (378)
31.5x21.8x13.1 (800x554x333) 20.24 (514) 13.39 (340)
33.27x27.6x14.3 (845x702x363) 21.26 (540) 13.8 (350)
37.24x31.9x16.53 (946x810x420) 26.5 (673) 15.87 (403)
37.24x31.9x16.14 (946x810x410) 26.5 (673) 15.87 (403)
37.5x52.5x16.14 (952x1333x410) 24.96 (634) 15.9 (404)
37.5x52.5x16.3 (4952x1333x415) 24.96 (634) 15.9 (404)
Table 5.2: Length Specifications of Vertical Discharge Outdoor Unit (unit: mm/inch)
MODEL W D H
18 21.8/554 21.8/554 25/633
24 21.8/554 21.8/554 25/633
36 21.8/554 21.8/554 29.8/759
36 23.6/600 23.6/600 25/633
48 28/710 28/710 29.8/759
60 28/710/ 28/710 33/843

Drain Joint Installation

Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit.

Diagram Fig. 5.12 shows drain joint installation (A) and (B).

  1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
  2. Insert the drain joint into the hole in the base pan of the unit.
  3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
  4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

NOTE: Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard.

Notes On Drilling Hole In Wall

You must drill a hole in the wall for the refrigerant piping, and the signal cable that will connect the indoor and outdoor units.

  1. Determine the location of the wall hole based on the location of the outdoor unit.
  2. Using a 2.5″ (65 mm) core drill, drill a hole in the wall.
    Diagram shows drilling a hole in a wall at a slight downward angle.
  3. Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.

NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

Diagram Fig. 5.10 shows outdoor unit clearance requirements (M, N, P).
Diagram Fig. 5.11 shows clearances for rows of series installation and Table 5.3 relates H, A, and L.

Section 6: Drainpipe Installation

The drainpipe is used to drain water away from the unit. Improper installation may cause unit and property damage.

CAUTION:

NOTE ON PURCHASING PIPES: Installation requires a polyethylene tube (exterior diameter = 1.5″, interior diameter = 1.25″), which can be obtained at your local hardware store or dealer.

Indoor Drainpipe Installation

Install the drainpipe as illustrated in Figure 6.2.

  1. Cover the drainpipe with heat insulation to prevent condensation and leakage.
  2. Attach the mouth of the drain hose to the unit's outlet pipe. Sheath the mouth of the hose and clip it firmly with a pipe clasp.
    Diagram Fig. 6.1 shows a drain hose, pipe clasp, and insulation.

NOTE ON DRAINPIPE INSTALLATION:

Drainpipe installation for units with a pump

Diagram Fig. 6.2 shows drainpipe installation with ceiling, slope, and spacing. Diagram Fig. 6.3 shows a close-up of the slope. Diagram Fig. 6.4 shows connecting multiple drainpipes.

Drainage Test

Check that the drainpipe is unhindered. This test should be performed on newly built houses before the ceiling is paved.

The unit with pump:

  1. Remove the test cover. Fill the water pan with 2.11 quart of water.
    Diagram Fig. 6.7 shows the unit with test cover removed and water pan. Diagram Fig. 6.8 shows the test setup with stow tube and test cap.
  2. Turn on the unit in COOLING mode. You will hear the drain pump. Check whether the water is discharged properly (a 1-minute lag is possible, depending on the length of the drain pipe). Check whether water leaks from the joints.
  3. Turn off the air conditioner and put the cap back on.

The unit without pump:

Fill the water pan with 2.11 quart of water. Check that the drainpipe is unhindered.

Diagram Fig. 6.6 shows filling the water pan.

3. Using a 2.5″ (65-mm) core drill, drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 0.5″ (12mm). This will ensure proper water drainage.

Diagram Fig. 6.5 shows drilling a wall hole.
Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.

NOTE: When drilling the wall hole, make sure to avoid wires, plumbing, and other sensitive components.

4. Pass the drain hose through the wall hole. Make sure the water drains to a safe location where it will not cause water damage or a slipping hazard.

NOTE: The drainpipe outlet should be at least 1.9″ (5cm) above the ground. If it touches the ground, the unit may become blocked and malfunction. If you discharge the water directly into a sewer, make sure that the drain has a U or S pipe to catch odors that might otherwise come back into the house.

Section 7: Refrigerant Piping Connection

Safety Precautions

WARNING:

Notes On Pipe Length and Elevation

Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in Table 7.1:

Table 7.1: The Maximum Length And Drop Height Based on Models. (Unit: ft/m)
Type of model Capacity (Btu/h) Length of piping Maximum drop height
North America, Australia and the eu frequency conversion Split Type <15K 82/25 32.8/10
≥15K - <24K 98.4/30 65.6/20
≥24K - <36K 164/50 82/25
≥36K - ≤60K 213/65 98.4/30
Other Split Type 12K 49/15 26/8
18K-24K 82/25 49/15
30K-36K 98.4/30 65.6/20
42K-60K 164/50 98.4/30

Refrigerant Piping Connection Instructions

CAUTION:

Step 1: Cut pipes

When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.

  1. Measure the distance between the indoor and outdoor units.
  2. Using a pipe cutter, cut the pipe a little longer than the measured distance.

CAUTION: DO NOT deform pipe while cutting. Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.

1. Make sure that the pipe is cut at a perfect 90° angle.

Diagram Fig. 7.1 shows examples of bad cuts (Oblique, Rough, Warped) and a 90° cut.

Step 2: Remove burrs

Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.

  1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
  2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.
    Diagram Fig. 7.2 shows using a reamer.

Step 3: Flare pipe ends

Proper flaring is essential to achieve an airtight seal.

  1. After removing burrs from cut pipe, seal the ends with PVC tape to prevent foreign materials from entering the pipe.
  2. Sheath the pipe with insulating material.
  3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you can't put them on or change their direction after flaring.
    Diagram Fig. 7.3 shows a flare nut and copper pipe. Diagram Fig. 7.4 shows a flare form.
  4. Remove PVC tape from ends of pipe when ready to perform flaring work.
  5. Clamp flare form on the end of the pipe. The end of the pipe must extend beyond the flare form.

6. Place flaring tool onto the form. 7. Turn the handle of the flaring tool clockwise until the pipe is fully flared. Flare the pipe in accordance with the dimensions shown in table 7.2.

Diagram Fig. 7.5 shows flare shapes.

Table 7.2: PIPING EXTENSION BEYOND FLARE FORM
Pipe gauge Tightening torque Flare dimension (A) (Unit: in/mm) Flare shape
Min. Max.
Ø 1/4″ 14.2-17.2 N.m (144-176 kgf.cm) 0.3/8.3 0.3/8.3 90 ± 4
Ø 3/8″ 32.7-39.9 N.m (333-407 kgf.cm) 0.48/12.4 0.48/12.4 45 ±2
Ø 1/2″ 49.5-60.3 N.m (504-616 kgf.cm) 0.6/15.4 15.8/0.62 R0.4~0.8
Ø 5/8″ 61.8-75.4 N.m (630-770 kgf.cm) 0.7/18.6 0.74/19
Ø 3/4″ 97.2-118.6 N.m (990-1210 kgf.cm) 0.9/22.9 0.91/23.3
Ø 7/8″ 109.5-133.7 N.m (1117-1364 kgf.cm) 1.06/27 1.07/27.3

8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.

Step 4: Connect pipes

Connect the copper pipes to the indoor unit first, then connect it to the outdoor unit. You should first connect the low-pressure pipe, then the high-pressure pipe.

  1. When connecting the flare nuts, apply a thin coat of refrigeration oil to the flared ends of the pipes.
  2. Align the center of the two pipes that you will connect.
    Diagram Fig. 7.6 shows indoor unit tubing, flare nut, and pipe.
  3. Tighten the flare nut as tightly as possible by hand.
  4. Using a spanner, grip the nut on the unit tubing.
  5. While firmly gripping the nut, use a torque wrench to tighten the flare nut according to the torque values in table 7.2.

NOTE: Use both a spanner and a torque wrench when connecting or disconnecting pipes to/from the unit.

6. After connecting the copper pipes to the indoor unit, wrap the power cable, signal cable and the piping together with binding tape.

NOTE: DO NOT intertwine signal cable with other wires. While bundling these items together, do not intertwine or cross the signal cable with any other wiring.

7. Thread this pipeline through the wall and connect it to the outdoor unit.

8. Insulate all the piping, including the valves of the outdoor unit.

9. Open the stop valves of the outdoor unit to start the flow of the refrigerant between the indoor and outdoor unit.

CAUTION: Ensure to wrap insulation around the piping. Direct contact with the bare piping may result in burns or frostbite. Make sure the pipe is properly connected. Over tightening may damage the bell mouth and under tightening may lead to leakage.

NOTE ON MINIMUM BEND RADIUS: Carefully bend the tubing in the middle according to the diagram below. DO NOT bend the tubing more than 90° or more than 3 times.

Diagram Fig. 7.8 shows bending the pipe with thumb, indicating a minimum radius of 3.9" (10cm).

CAUTION: Check to make sure there is no refrigerant leak after completing the installation work. If there is a refrigerant leak, ventilate the area immediately and evacuate the system (refer to the Air Evacuation section of this manual).

Section 8: Wiring

Safety Precautions

WARNING:

CAUTION:

Follow these instructions to prevent distortion when the compressor starts:

TAKE NOTE OF FUSE SPECIFICATIONS

The air conditioner's printed circuit board (PCB) is designed with a fuse that provides overcurrent protection. The specifications of the fuse are printed on the circuit board, examples of such are T5A/250VAC and T10A/250VAC.

Outdoor Unit Wiring

WARNING: Before performing any electrical or wiring work, turn off the main power to the system.

1. Prepare the cable for connection

a. You must first choose the right cable size before preparing it for connection. Be sure to use H07RN-F cables.

Table 8.1: Minimum Cross-Sectional Area of Power and Signal Cables in North America
Rated Current of Appliance (A) AWG
<7 18
7 - 13 16
13 - 18 14
18 - 25 12
25 - 30 10
Table 8.2: Other World Regions
Rated Current of Appliance (A) Nominal Cross-Sectional Area (mm²)
≤ 6 0.75
6 - 10 1
10 - 16 1.5
16 - 25 2.5
25 - 32 4
32 - 45 6

b. Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal approximately 15cm (5.9″) of wire.

c. Strip the insulation from the ends.

d. Using a wire crimper, crimp u-lugs on the ends.

NOTE: When connecting the wires, strictly follow the wiring diagram found inside the electrical box cover.

2. Remove the electric cover of the outdoor unit. If there is no cover on the outdoor unit, take off the bolts from the maintenance board and remove the protection board.

Diagrams Fig. 8.1 and 8.2 show the outdoor unit, cover, screw, wiring diagram, and protection board.

Indoor Unit Wiring

1. Prepare the cable for connection

a. Using wire strippers, strip the rubber jacket from both ends of the signal cable to reveal about 15cm (5.9″) of the wire.

b. Strip the insulation from the ends of the wires.

c. Using a wire crimper, crimp the u-lugs to the ends of the wires.

2. Remove the cover of the electric control box on your indoor unit.

3. Connect the u-lugs to the terminals.

Match the wire colors/labels with the labels on the terminal block, and firmly screw the u-lug of each wire to its corresponding terminal. Refer to the Serial Number and Wiring Diagram located on the cover of the electric control box.

Diagram Fig. 8.3 shows wiring diagrams and connective wiring diagrams.

4. Clamp down the cable with the cable clamp.

The cable must not be loose or pull on the u-lugs.

5. Insulate unused wires with electrical tape. Keep them away from any electrical or metal parts.

6. Reinstall the cover of the electric control box.

CAUTION:

Using the wire control to set external static pressure (some models)

  1. Make sure the test run is done with a dry coil. If the coil is not dry, run the unit for 2 hours in FAN ONLY mode to dry the coil.
  2. Check that both power supply wiring and duct installation have been completed. Check that any closing dampers are open. Check that the air filter is properly attached to the air suction side passage of the unit.
  3. Set the parameters for automatic airflow adjustment. When the air conditioning unit is off, perform the following steps:
    • Press the button “COPY” long.
    • Press "+" or "-" to select the AF.
    • Press “CONFIRM”. The air conditioning unit will then start the fan for airflow automatic adjustment.

ON will flash during when the fan is on during automatic airflow adjustment.

CAUTION:

Section 9: Air Evacuation

Safety Precautions

CAUTION:

Evacuation Instructions

Before using a manifold gauge and a vacuum pump, read their operation manuals to make sure you know how to use them properly.

Diagram Fig. 9.1 shows Manifold Gauge, Compound gauge, Pressure gauge, Low pressure valve, High pressure valve, Charge hose, and Vacuum pump.
  1. Connect the manifold gauge's charge hose to the service port on the outdoor unit's low pressure valve.
  2. Connect the manifold gauge's charge hose from the to the vacuum pump.
  3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.
  4. Turn on the vacuum pump to evacuate the system.
  5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76cmHG (-1x105Pa).
  6. Close the manifold gauge's Low Pressure valve and turn off the vacuum pump.
  7. Wait for 5 minutes, then check that there has been no change in system pressure.

NOTE: If there is no change in system pressure, unscrew the cap from the packed valve (high pressure valve). If there is a change in system pressure, there may be a gas leak.

8. Insert hexagonal wrench into the packed valve (high pressure valve) and open the valve by turning the wrench 1/4 counterclockwise. Listen for gas to exit the system, then close the valve after 5 seconds.

Diagram Fig. 9.2 shows Valve body, Valve stem, Flare nut, and Cap.

9. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. It should read slightly higher than the atmospheric pressure.

10. Remove the charge hose from the service port.

11. Using hexagonal wrench, fully open both the high pressure and low pressure valves. OPEN VALVE STEMS GENTLY: When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT try to force the valve to open further.

12. Tighten valve caps by hand, then tighten it using the proper tool.

Note On Adding Refrigerant

CAUTION:

Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is 7.5m (25′). In other areas, the standard pipe length is 5m (16′). The additional refrigerant to be charged can be calculated using the following formula:

Liquid Side Diameter
Ø1/4″(6.35) Ø3/8″(9.52) Ø1/2″(12.7)
R22 (orifice tube in the indoor unit): (Total pipe length - standard pipe length)x 0.32oz(30g)/ft(m) (Total pipe length - standard pipe length)x 0.69oz(65g)/ft(m) (Total pipe length - standard pipe length)x 1.23oz(115g)/ft(m)
R22 (orifice tube in the outdoor unit): (Total pipe length - standard pipe length) x0.16oz(15g)/ft(m) (Total pipe length - standard pipe length) x0.32oz(30g)/ft(m) (Total pipe length - standard pipe length) x0.64oz(60g)/ft(m)
R410A: (orifice tube in the indoor unit): (Total pipe length - standard pipe length) x0.32oz(30g)/ft(m) (Total pipe length - standard pipe length) x0.69oz(65g)/ft(m) (Total pipe length - standard pipe length) 1.23oz(115g)/ft(m)
R410A: (orifice tube in the outdoor unit): (Total pipe length - standard pipe length) x0.16oz(15g)/ft(m) (Total pipe length - standard pipe length) x0.32oz(30g)/ft(m) (Total pipe length - standard pipe length) 0.69oz(65g)/ft(m)

Section 10: Test Run

Before Test Run

A test run must be performed after the entire system has been completely installed. Confirm the following points before performing the test:

CAUTION: Failure to perform the test run may result in unit damage, property damage or personal injury.

Test Run Instructions

  1. Open both the liquid and gas stop valves.
  2. Turn on the main power switch and allow the unit to warm up.
  3. Set the air conditioner to COOL mode.
  4. For the Indoor Unit:
    • Ensure the remote control and its buttons work properly.
    • Ensure the louvers move properly and can be changed using the remote control.
    • Double check to see if the room temperature is being registered correctly.
    • Ensure the indicators on the remote control and the display panel on the indoor unit work properly.
    • Ensure the manual buttons on the indoor unit works properly.
    • Check to see that the drainage system is unimpeded and draining smoothly.
    • Ensure there is no vibration or abnormal noise during operation.
  5. For the Outdoor Unit:
    • Check to see if the refrigeration system is leaking.
    • Make sure there is no vibration or abnormal noise during operation.
    • Ensure the wind, noise, and water generated by the unit do not disturb your neighbors or pose a safety hazard.
  6. Drainage Test:
    • Ensure the drainpipe flows smoothly. New buildings should perform this test before finishing the ceiling.
    • Remove the test cover. Add 2.11 quart of water to the tank through the attached tube.
    • Turn on the main power switch and run the air conditioner in COOL mode.
    • Listen to the sound of the drain pump to see if it makes any unusual noises.
    • Check to see that the water is discharged. It may take up to one minute before the unit begins to drain depending on the drainpipe.
    • Make sure that there are no leaks in any of the piping.
    • Stop the air conditioner. Turn off the main power switch and reinstall the test cover.

NOTE: If the unit malfunctions or does not operate according to your expectations, please refer to the Troubleshooting section of the Owner's Manual before calling customer service.

PDF preview unavailable. Download the PDF instead.

Installation manual Duct 09-24 Adobe Illustrator CS6 (Windows)(Foxit Advanced PDF Editor) Adobe PDF library 10.01

Related Documents

Preview Cooper&Hunter Ceiling Cassette Air Conditioner Installation Manual
Detailed installation manual for Cooper&Hunter Ceiling Cassette Split-Type Room Air Conditioners (R454B), covering safety, product overview, installation steps, wiring, piping, testing, and warranty information.
Preview Cooper&Hunter PEAQ Multi-Position Air Handler Unit: High Performance HVAC
Explore the Cooper&Hunter PEAQ Multi-Position Air Handler Unit, offering high performance, energy efficiency up to 19 SEER2, and advanced features for residential and commercial HVAC systems. Learn about its specifications, cold climate capabilities, and installation flexibility.
Preview Cooper&Hunter 2025 Catalog: HVAC Systems & Solutions
Explore the comprehensive Cooper&Hunter 2025 Catalog featuring a wide range of innovative HVAC solutions, including single-zone and multi-zone systems, air handlers, PTAC units, and more. Discover energy-efficient and reliable air conditioning and heating products for residential and commercial applications.
Preview Cooper&Hunter SOPHIA Series CH-24MSPHCT-230VI Cassette Type Air Conditioner Submittal Data Sheet
Detailed submittal data sheet for the Cooper&Hunter SOPHIA Series CH-24MSPHCT-230VI cassette type air conditioner, including specifications, performance data, electrical, and piping information.
Preview Cooper&Hunter SOPHIA Series Cassette Type Air Conditioner Submittal Data
Detailed submittal data sheet for the Cooper&Hunter SOPHIA Series Cassette Type Air Conditioner, including technical specifications, performance data, and operational ranges for models CH-09MSPHCT-230VI and CH-09SPH-230V0.
Preview Cooper&Hunter MIA Split-Type Room Air Conditioner Owner's Manual
Comprehensive owner's manual for Cooper&Hunter MIA Series Split-Type Room Air Conditioners. Includes installation guides, safety precautions, operation instructions, maintenance, and troubleshooting for models like CH-RLS06MIA, CH-RLS09MIA, CH-RLS12MIA, CH-RLS18MIA, and CH-RLS24MIA.
Preview Cooper&Hunter CH-RHP18-230VO + CH-RSH18MCT Air Conditioner Specifications
Detailed technical specifications, key features, and dimensions for the Cooper&Hunter CH-RHP18-230VO + CH-RSH18MCT air conditioning system, including indoor and outdoor unit details.
Preview Cooper&Hunter CH-R48LCU-230VO + CH-RSH48LCFC Air Conditioner Technical Specifications
Detailed technical specifications, key features, and dimensional information for the Cooper&Hunter CH-R48LCU-230VO + CH-RSH48LCFC split system air conditioner, including performance data and unit measurements.