Cooper&Hunter SOPHIA Series CASSETTE TYPE
Submittal Data Sheet
Model Numbers: CH-24MSPHCT-230VI (Indoor Unit), CH-24SPH-230V0 (Outdoor Unit)
Project Information
Job Name: ...................................................................................................................................
Location: .....................................................................................................................................
Engineer:.....................................................................................................................................
Submitted to:...............................................................................................................................
Submitted by: .............................................................................................................................
Reference: ...................................................................................................................................
Date: ...........................................................................................................................................
Approval: ....................................................................................................................................
Construction:................................................................................................................................
Unit #: .........................................................................................................................................
Drawing #: ..................................................................................................................................
Warranty Information
This warranty should be registered on our web-site www.cooperandhunter.us within 60 days of installation. The warranty is only valid when installed by a Licensed HVAC Technician. A warranty period of Seven (7) years on compressor to the original registered end-user. A warranty period of Five (5) years on all parts to the original registered end user. Warranty applies only to products remaining in their original installation location.
Indoor Unit Specifications
Air Flow (Hi/Mi/Lo) | 820/740/590 CFM |
Noise Level (Hi/Mi/Lo) | 51/47/43 dB(A) |
Unit Dimension (WxDxH) | 33.07x33.07x8.07 in |
Net/Gross Weight | 45.19/52.91 lb |
Outdoor Unit Specifications
Air flow | 2355 CFM |
Noise Level | 61 dB(A) |
Dimension (WxDxH) | 37.24x16.14x31.89 in |
Net/Gross weight | 136.69/147.27 lb |
Refrigerant type/Quantity | R410A/82.9 oz |
Refrigerant precharge | 25 ft |
Additional charge for each ft | 0.32 oz |
Performance and Efficiency
Cooling | Heating | |
Capacity | 24,000 Btu/h | 24,400 Btu/h |
SEER | 20 | |
EER | 12.5 | |
HSPF | 10.5 (Region IV) |
Performance Data
Heating/ Cooling | Outdoor Dry Bulb | Indoor Dry Bulb | Unit | Min | Rated | Max |
---|---|---|---|---|---|---|
Heating | 5°F | 70°F | Btu/h | 3,596 | 15,800 | 16,933 |
kW | 0.77 | 1.81 | 2.55 | |||
COP | 1.37 | 2.56 | 1.95 | |||
Heating | 17°F | 70°F | Btu/h | 5,360 | 15,800 | 17,841 |
kW | 0.78 | 1.81 | 2.5 | |||
COP | 2.01 | 2.56 | 2.09 | |||
Heating | 47°F | 70°F | Btu/h | 10,936 | 24,400 | 30,998 |
kW | 0.67 | 2.04 | 2.86 | |||
COP | 4.78 | 3.51 | 3.18 | |||
Cooling | 82°F | 80°F | Btu/h | 8,317 | 24,528 | 24,528 |
kW | 0.32 | 1.58 | 1.58 | |||
COP | 7.62 | 4.55 | 4.55 | |||
Cooling | 95°F | 80°F | Btu/h | 11,822 | 24,000 | 24,958 |
kW | 0.79 | 1.92 | 2.31 | |||
COP | 4.39 | 3.66 | 3.17 |
Operation Temperature Range
Indoor | Outdoor | |||
---|---|---|---|---|
Cooling | Heating | Cooling | Heating | |
62~90°F | 32~86°F | -13~122°F | -13~86°F |
Electrical Specifications
Power supply | 208-230V/60Hz, 1Ph |
MCA | 18 A |
MFA | 25 A |
MCA: Minimum Circuit Ampacity MFA: Max. fuse A
Piping Specifications
Refrigerant piping Liquid side/Gas side | 3/8 - 5/8 in |
Max. refrigerant pipe length | 164 ft |
Max. difference in level | 82 ft |
Diagram Descriptions
Indoor Unit Diagram Description
The indoor unit is depicted as a rectangular cassette designed for ceiling installation. Key connection points are shown: a drain pipe connection, a liquid refrigerant pipe connection, and a gas refrigerant pipe connection. A float switch is also indicated. Dimensions provided include the ceiling hole size (34.65 inches), suspension bolt spacing (30.71 inches), body dimensions (33.08 inches), and ceiling opening (37.41 inches). The unit requires a ceiling board and has a front panel.
Outdoor Unit Diagram Description
The outdoor unit is shown as a rectangular box with a fan grille on one side. Dimensions are provided: Width (W), Height (H), and Depth (D). Specific dimensions are given as 37.24 inches (Width) x 16.14 inches (Depth) x 31.89 inches (Height). Mounting dimensions are also specified: Distance A (26.5 inches) and Distance B (15.87 inches).