Cooper&Hunter Air Conditioner
CH-RHP18-230VO + CH-RSH18MCT
Key Features
- Refrigerant Sensor
- Humidity Sensor
- GoldFin Anti-Corrosive Coating
- Multiple Fan Speeds
- Fresh Air Intake
- Omni-Directional Airflow
- Smart-Kit Built-in on Wall Thermostat
- Inverter technology
Indoor Unit Specifications (CH-RSH18MCT)
Parameter | Value |
---|---|
Indoor Model | CH-RSH18MCT |
Power supply | 208-230V, 1Ph, 60Hz |
Communication wiring | AWG 14-4 |
Capacity (Cooling) | 16,000 (7,000~18,500) Btu/h |
Input (Cooling) | 1,280 (320~1,640) W |
Rated current (Cooling) | 8 (2.3~7.2) A |
EER/EER2 | 12.5 Btu/w |
SEER/SEER2 | 20 Btu/w |
Capacity (Heating) | 19,000 (8,700~20,000) Btu/h |
Input (Heating at 47 °F) | 1,750 (500~1,950) W |
Rated current (Heating at 47 °F) | 11 (3.5~12) A |
COP (Heating at 47 °F) | 3.18 W/W |
HSPF4/HSPF2-4 | 12.3 |
HSPF5/HSPF2-5 | 9.5 |
Indoor fan motor Qty | 1 |
Indoor fan motor Input | 45 W |
Indoor fan motor RLA | 1 A |
Indoor air flow (Turbo/Hi/Med/Lo) (No duct) | 447.3 / 388.5 / 317.8 / 194.2 CFM |
ESP (range) | / In.wg. |
Indoor noise level (Hi/Med/Lo) | 44.5/41/27.5 dB(A) |
Dehumidification | 4.23 L/H |
Dimensions (WxDxH) | 22.44 x 22.44 x 9.65 inch |
Packing (WxDxH) | 28.15 x 25.20 x 11.61 inch |
Net/Gross weight | 35.27/41.89 lbs |
Drainage water pipe diameter | 1" inch |
Refrigerant piping (Liquid side/Gas side) | 1/4"/1/2" inch |
Design pressure | 550/340 PSIG |
Controller | wire controller + remote controller available |
Room temperature (Cooling) | 60~90 °F |
Room temperature (Heating) | 32~86 °F |
Outdoor Unit Specifications (CH-RHP18-230VO)
Parameter | Value |
---|---|
Outdoor Model | CH-RHP18-230VO |
Power supply | 208-230V, 1Ph, 60Hz |
Min. circuit ampacity | 19 A |
Max. fuse | 20 A |
Compressor Model | KTM240D46UKT2 |
Compressor Type | ROTARY |
Compressor Brand | GMCC |
Capacity | 25,930 Btu/h |
Input | 2,045 W |
Rated current (RLA) | 11.7 A |
Refrigerant oil | VG74 21 oz |
Outdoor fan motor Qty | 1 |
Outdoor fan motor Input | 80 W |
Outdoor fan motor RLA | 0.9 A |
Outdoor fan motor Speed | 780/700/550 r/min |
Outdoor air flow (Max) | 1,765.8 CFM |
Outdoor noise level (Max) | 57.5 dB(A) |
Throttle type | EXV+Throttle valve |
Dimensions (WxDxH) | 35.04 x 13.46 x 26.50 inch |
Packing (WxDxH) | 39.17 x 15.67 x 29.13 inch |
Net/Gross weight | 99.87/107.80 lbs |
Refrigerant Type | R454B |
Refrigerant Precharge | 25 ft |
Additional charge for 1/4 inch liquid pipe | 0.16 oz |
Additional charge for 3/8 inch liquid pipe | / oz |
Refrigerant piping (Liquid side/Gas side) | 1/4"/1/2" inch |
Refrigerant piping Max. pipe length | 98.4 ft |
Refrigerant piping Max. difference in level | 65.6 ft |
Ambient temperature (Cooling) | -22 ~ 122 °F |
Ambient temperature (Heating) | -22~75 °F |
Product Dimensions and Connections
Indoor Unit Diagram Description
The indoor unit is depicted with its body, featuring connections for liquid and gas refrigerant lines, a fresh air intake port (3 inches / 75mm diameter), and a 1-inch (25mm) drain pipe. A wiring connection port is also visible.
Key dimensions for the indoor unit body are approximately: Height 20-7/8 inches (531mm), Width 24-3/8 inches (620mm), Depth 22-1/2 inches (570mm). The panel dimensions are approximately 24-3/8 inches (620mm) wide and 22-1/2 inches (570mm) deep.
Outdoor Unit Diagram Description
The outdoor unit is shown with its overall dimensions. The main width (W) is 35 inches (890mm), with variations W1 at 26-1/8 inches (663mm), W2 at 37-5/8 inches (955mm), and W3 at 35-1/4 inches (895mm). The depth (D) is 13-1/2 inches (342mm). The height (H) is 26-1/2 inches (673mm).
Further details include mounting hole dimensions: B1 is 2-3/8 inches (61mm), B2 is 2-3/4 inches (325mm). H1 is 4-1/4 inches (108mm), and H2 is 2 inches (52mm). Detail A shows connection points A1 (1/2 inch) and A2 (2-7/8 inches / 74mm).
Certifications and Standards
The product meets standards including R454B certification, AHRI certified, ENERGY STAR, and is listed by Intertek.