Cooper&Hunter CH-R48LCU-230VO + CH-RSH48LCFC
Split System Air Conditioner
Key Features
- Refrigerant Sensor
- Humidity Sensor
- GoldFin Anti-Corrosive Coating
- Multiple Fan Speeds
- Easy service
- TU1 Cooper Coil
- Can be applied horizontally from the ceiling or vertically on a wall
- Inverter technology
Indoor Unit Specifications (CH-RSH48LCFC)
Specification | Value |
---|---|
Indoor Model | CH-RSH48LCFC |
Power supply | 208-230V, 1Ph, 60Hz |
Communication wiring | AWG 14-3 |
Cooling Capacity | 48,000 (10,100~50,000) Btu/h |
Cooling Input | 5,053 (830~5,280) W |
Cooling Rated current | 22 (5.9~23.1) A |
Cooling EER/EER2 | 22 (5.9~23.1) Btu/w |
Cooling SEER/SEER2 | 50,000 (15,800~59,100) Btu/w |
Heating Capacity | 5,196 (575~5,860) Btu/h |
Heating Input | 22.6 (6.3~25.7) W |
Heating Rated current | 2.82 A |
Heating COP | 2.82 W/W |
Heating HSPF4/HSPF2-4 | 10.2 |
Heating HSPF5/HSPF2-5 | 7.8 |
Indoor fan motor Qty | 2 |
Indoor fan motor Input | 90 W |
Indoor fan motor RLA | 1 A |
Indoor air flow (Turbo/Hi/Med/Lo) (No duct) | 1,353.8 / 1,236.1 / 1,083 / 800.5 CFM |
ESP (range) | / In.wg. |
Indoor noise level (Hi/Med/Lo) | 53/49/39 dB(A) |
Dehumidification | 12.58 L/H |
Indoor unit Dimensions (WxDxH) | 64.96 x 26.57 x 9.25 inch |
Indoor unit Packing (WxDxH) | 67.91 x 29.72 x 12.52 inch |
Indoor unit Net/Gross weight | 89.07/105.16 lbs |
Drainage water pipe diameter | 1" inch |
Refrigerant piping (Liquid side/Gas side) | 3/8"/3/4" inch |
Design pressure | 550/340 PSIG |
Controller | remote controller |
Room temperature Cooling | 60~90 F |
Room temperature Heating | 32~86 F |
Outdoor Unit Specifications (CH-R48LCU-230VO)
Specification | Value |
---|---|
Outdoor Model | CH-R48LCU-230VO |
Power supply | 208-230V, 1Ph, 60Hz |
Min. circuit ampacity | 39 A |
Max. fuse | 40 A |
Compressor Model | KTQ420D1UMU |
Compressor Type | ROTARY |
Compressor Brand | GMCC |
Compressor Capacity | 46.74 Btu/h |
Compressor Input | 3.7 W |
Compressor Rated current (RLA) | 24 A |
Compressor Refrigerant oil | VG74 47.3 OZ |
Outdoor fan motor Qty | 2 |
Outdoor fan motor Input | 85 W |
Outdoor fan motor RLA | 1.2 A |
Outdoor fan motor Speed | 850/750/650 r/min |
Outdoor air flow (Max) | 4,237,9 CFM |
Outdoor noise level (Max) | 62.5 dB(A) |
Throttle type | EXV+Throttle valve |
Outdoor unit Dimensions (WxDxH) | 37.48 x 16.34 x 52.48 inch |
Outdoor unit Packing (WxDxH) | 43.11 x 19.49 x 57.48 inch |
Outdoor unit Net/Gross weight | 208.78/239.86 lbs |
Refrigerant Type | R454B |
Refrigerant Precharge | 25 ft |
Refrigerant Additional charge for 1/4 inch liquid pipe | / OZ |
Refrigerant Additional charge for 3/8 inch liquid pipe | 0.32 OZ |
Refrigerant piping Liquid side/Gas side | 3/8"/3/4" inch |
Refrigerant piping Max. pipe length | 246 ft |
Refrigerant piping Max. difference in level | 98.4 ft |
Ambient temperature Cooling | -13~ 122 F |
Ambient temperature Heating | -13~75 F |
Diagrams and Dimensions
Indoor Unit Connection and Dimension Details:Diagrams illustrate the Cooper&Hunter indoor unit's connection points and dimensions. Key connection ports include a 1-1/2 inch (40mm) drain discharge port, 4-3/4 inch (120mm) fresh air intake, and a 7/8 inch (22mm) wiring connection port. The unit also features refrigerant pipe holes. A table provides dimensions (A, B, C, D) for different models: 18K/24K units measure 42in (1068mm) for A, 26-1/2in (675mm) for B, 9-1/4in (235mm) for C, and 38-3/4in (983mm) for D. 36K/48K/60K units measure 65in (1650mm) for A, with B, C, and D dimensions remaining the same as the smaller models, except D is 61-5/8in (1565mm).
Outdoor Unit Dimension Details:Diagrams show the Cooper&Hunter outdoor unit's dimensions and views from the front, side, and top. Key dimensions are labeled: A (52-1/2in / 1333mm), D1 (37-1/2in / 952mm), and other measurements for width, depth, and height are provided, such as 25-1/4in (634mm) and 41-1/8in (1045mm).
Cooper&Hunter products are subject to continuous improvements. Cooper&Hunter reserves the right to modify product design, specifications and information in this data sheet without notice and without incurring any obligations. Actual unit design may differ from images shown in this submittal sheet.