Mitsubishi Electric M-Series Submittal Data
MSZ-GL06NA-(U1)(U2)
6,000 BTU/h WALL-MOUNTED INDOOR UNIT FOR MXZ-C MULTI-ZONE HEAT PUMP SYSTEMS
Job Information
Job Name:
Purchaser:
Submitted to:
System Designation:
Location:
Engineer:
Date:
For: Reference ☐ Approval ☐ Construction ☐
Schedule No.:
Unit Overview
Indoor Unit: MSZ-GL06NA-U1
Wireless Remote Controller
Accessories:
- Indoor Unit
- Anti-Allergy Enzyme Filter (MAC-408FT-E)
- Wireless Controller (MHK1)
- Wired Remote Controller PAR-40MAA (Requires MAC-334IF-E)
- Thermostat Interface (PAC-US444CN-1)
Specifications
Attribute | Value | Unit |
---|---|---|
Rated Capacity* Cooling | 6,000 | Btu/h / W |
Heating at 47° F | 7,200 | Btu/h / W |
Rating Conditions per AHRI Standard:
1 Cooling | Indoor: 80° F(27° C)DB / 67° F (19° C)WB; Outdoor: 95° F (35° C)DB / 75° F (24° C)WB
2 Heating at 47°F | Indoor: 70° F (21° C)DB / 60° F (16° C)WB; Outdoor: 47° F (8° C)DB / 43° F (6° C)WB
For data on specific indoor units (all ducted, all non-ducted, and both ducted and non-ducted) combinations, see the MXZ Technical and Service Manual.
Applications should be restricted to comfort cooling only; equipment cooling applications are not recommended for low ambient temperature conditions.
Attribute | Value | Unit |
---|---|---|
Electrical Power Requirements | 208/230V, 1-Phase, 60 Hz | |
Minimum Circuit Ampacity (MCA)* | 1 | A |
Blower Motor (ECM) F.L.A. | 0.76 | A |
Blower Motor Output | 30 | W |
Moisture Removal | 1.5 | pt./h |
Field Drainpipe Size O.D. | 5/8 | In.(mm) |
Airflow Rate (Quiet - Lo - Med - Hi - Super Hi) Cooling | DRY: 145-170-237-321-399 CFM WET: 109-134-201-286-364 CFM |
|
Heating | DRY: 145-170-237-321-406 CFM | |
Sound Pressure Level (Quiet - Lo - Med - Hi - Super Hi) Cooling | 19-22-30-37-43 | dB(A) |
Heating | 19-22-30-37-43 | dB(A) |
External Dimensions (H x W x D) | 11-5/8 x 31-7/16 x 9-1/8 | In.(mm) (295 x 798 x 232) |
Net Weight | 22 | Lbs.(kg) (10) |
External Finish | Munsell 1.0Υ 9.2/0.2 | |
Refrigerant Piping (Flared) Liquid (High Pressure) | 1/4 | In.(mm) (6.35) |
Gas (Low Pressure) | 3/8 | In.(mm) (9.52) |
*All electrical work shall comply with National (CEC) and local codes and regulations.
Dimensions
The following dimensions are provided for the MSZ-GL06NA-(U1)(U2) unit:
- Height: 11-5/8 inches (295 mm)
- Width: 31-7/16 inches (798 mm)
- Depth: 9-1/8 inches (232 mm)
Detailed diagrams illustrating installation plate, piping, and drain hose connections are available in the original document.