Eaton 144060 EU5E SWD Input Card
Specifications
Product Overview
Catalog Number: 144060
Eaton EU5E SWD input card, 24 V DC, 4 digital inputs with 24 V power supply, 0.5A, 3 conductor connection.
Image Description: A compact, dark-colored industrial module, the Eaton EU5E SWD input card, is shown. The front panel features labels for "SWD", "24V", "OV", and "4 input 24V DC". It includes a row of terminal blocks marked "10123" and "AAAAAA AAAAAA AA", a flat plug-in connector on the side, and visible certifications like "CE" and "FAT-N".
General Specifications
Product Name | Eaton EU5E I/O module | Catalog Number | 144060 |
---|---|---|---|
EAN | 4015081405909 | Product Length/Depth | 102 mm |
Product Height | 90 mm | Product Width | 35 mm |
Product Weight | 0.09 kg |
Certifications
- UL File No.: E29184
- UL
- UL Category Control No.: NKCR
- CSA File No.: 2324643
- IEC/EN 61131-2
- CSA
- CSA Class No.: 3211-07
Catalog Notes: Inputs with supply for sensor system.
Features & Functions
Electric connection type: Flat plug-in connection
Features: Fieldbus connection over separate bus coupler possible
Functions: For connection of digital I/O signals
General
Current consumption | 33 mA, SmartWire-DT network | Degree of protection | IP20 |
---|---|---|---|
Mounting method | Wall mounting/direct mounting, Top-hat rail fixing (according to IEC/EN 60715, 35 mm), Rail mounting possible | Overvoltage category | II |
Pollution degree | 2 | Product category | SmartWire-DT slave |
Residual ripple | ≤ 5 % (input voltage) | Terminal capacity | 0.25 - 1.5 mm² (24 - 16 AWG), flexible with ferrule, Terminal for I/O sensor; 0.2 - 1.5 mm² (AWG 24 - 16), solid, Terminal for I/O sensor |
Type | Digital modules | Voltage type | DC |
Ambient Conditions
Mechanical
Constant acceleration | 1 g, 8.4 - 150 Hz, according to IEC/EN 61131-2, Vibrations | Constant amplitude | 3.5 mm, 5 - 8.4 Hz, according to IEC/EN 61131-2, Vibrations |
---|---|---|---|
Drop and topple | 50 mm Drop height, Drop to IEC/EN 60068-2-31 | Height of fall (IEC/EN 60068-2-32) - max | 0.3 m |
Mounting position | As required |
Climatic
Air pressure | 795 - 1080 hPa (operation) | Ambient operating temperature - min | -25 °C |
---|---|---|---|
Ambient operating temperature - max | 55 °C | Ambient storage temperature - min | -40 °C |
Ambient storage temperature - max | 70 °C |
Environmental and Durability
Shock resistance | 15 g, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 11 ms, 9 Impacts | Climatic proofing | Dry heat to IEC 60068-2-2, Damp heat, constant, to IEC 60068-2-3 |
---|---|---|---|
Environmental conditions | Condensation: prevent with appropriate measures | ||
Operating temperature - min | -25 °C | Operating temperature - max | 55 °C |
Relative humidity | 5 - 95 % (non-condensing, IEC/EN 60068-2-30) |
Electromagnetic Compatibility
Air discharge | 8 kV, according to IEC 61131-2, level 3, ESD | Burst impulse | 2 kV, Supply cable, according to IEC/EN 61131-2, Level 3 1 kV, SmartWire-DT cable, according to IEC/EN 61131-2, Level 3 1 kV, Signal cable, according to IEC/EN 61131-2, Level 3 |
---|---|---|---|
Contact discharge | 4 kV, according to IEC/EN 61131-2, Level 2, ESD | Electromagnetic fields | 1 V/m at 2.0 - 2.7 GHz (according to IEC/EN 61131-2:2008) 10 V/m at 80 - 1000 MHz (according to IEC/EN 61131-2:2008) 3 V/m at 1.4 - 2 GHz (according to IEC/EN 61131-2:2008) |
Radiated RFI | 10 V (IEC/EN 61131-2:2008, Level 3) | Radio interference class | Class A (EN 55011) |
Surge rating | 0.5 kV, Surge power cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC 1 kV, Surge I/O cables, Surge (IEC/EN 61131-2:2008, Level 1), EMC |
Electrical Rating
Input current at signal 1 | 4 mA | Output current | 0 A |
---|---|---|---|
Power loss | 1.1 W | Rated operational voltage | 24 V DC (-15%/+ 20 % - power supply) |
Supply voltage at AC, 50 Hz - min | 0 VAC | Supply voltage at AC, 50 Hz - max | 0 VAC |
Supply voltage at DC - min | 0 VDC | Supply voltage at DC - max | 28.8 VDC |
Communication
Connection to SmartWire-DT | Yes | Connection type | Plug, 8-pole, SmartWire-DT |
---|---|---|---|
Connection plug | external device plug SWD4-8SF2-5, SmartWire-DT |
Input/Output
Number of inputs (digital) | 4 | Number of outputs (digital) | 0 |
---|
Safety
Explosion safety category for dust | None | Explosion safety category for gas | None |
---|---|---|---|
Potential isolation | Outputs to SmartWire-DT: yes Inputs for SmartWire-DT: yes | Protection against polarity reversal | Yes Yes, for supply voltage (Siemens MPI optional) |
Design Verification
Equipment heat dissipation, current-dependent Pvid | 0 W | Heat dissipation capacity Pdiss | 0 W |
---|---|---|---|
Heat dissipation per pole, current-dependent Pvid | 0 W | Rated operational current for specified heat dissipation (In) | 0 A |
Static heat dissipation, non-current-dependent Pvs | 1.1 W |
10.2.2 Corrosion resistance: Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures: Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat: Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects: Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation: Meets the product standard's requirements.
10.2.5 Lifting: Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact: Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions: Meets the product standard's requirements.
10.3 Degree of protection of assemblies: Meets the product standard's requirements.
10.4 Clearances and creepage distances: Meets the product standard's requirements.
10.5 Protection against electric shock: Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components: Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections: Is the panel builder's responsibility.
10.8 Connections for external conductors: Is the panel builder's responsibility.
10.9.2 Power-frequency electric strength: Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage: Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material: Is the panel builder's responsibility.
10.10 Temperature rise: The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating: Is the panel builder's responsibility.
10.12 Electromagnetic compatibility: Is the panel builder's responsibility.
10.13 Mechanical function: The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Resources
Brochures
Catalogs
- Product Range Catalog Drives Engineering
- eaton-product-overview-for-machinery-catalogue-ca08103003zen-en-us.pdf
- SmartWire-DT Catalog
Declarations of conformity
Drawings
- eaton-modular-plc-eu5e-i-o-module-dimensions.eps
- eaton-modular-plc-eu5e-i-o-module-dimensions-002.eps
- eaton-general-easy-control-relays-symbol-002.tif
- eaton-general-approval-easy-control-relays-standards.jpg
- eaton-general-eu5e-i-o-module-symbol.eps
- eaton-modular-plc-swd-eu5e-i-o-module-3d-drawing.eps
eCAD model
- DA-CE-ETN.EU5E-SWD-4DX
Installation instructions
Installation videos
- SmartWire-DT in Application
Manuals and user guides
- MN05006002Z_EN
- MN05006001Z_EN
mCAD model
- eaton-eu5e_swd_4dx-drawing.dwg
- eaton-eu5e_swd_4dx-3d-model.stp
- DA-CS-eu5e_swd_1
- DA-CD-eu5e_swd_1
Multimedia
- How to process SmartWire-DT modules using the EASY-COM-SWD-C1 module connected to an easyE4?
- SmartWire-DT Overview and how to use in easySoft 7
- easyE4 SmartWire-DT module with Remote Touch Display and RMQ multi color indicator
Sales notes
- eaton-electro-hydraulic-module-eu1h-flyer-fl120003en-en-us.pdf
- eaton-rmq-chemical-resistance-flyer-fl047011en-en-us.pdf
Wiring diagrams
- eaton-modular-plc-power-supply-eu5e-i-o-module-wiring-diagram.eps