Gree Vireo R32 VIR24HP230V1R32AH Submittal Data
Product: 24000 BTU/H Wall Mounted Unit
Submittal Data

YBE1FBF

VIR24HP230V1R32AH

XE71 (Optional)
General Features
- Auto-Clean Function
- Wireless Remote with LCD Display
- Wired Controller Options
- New R32 Refrigerant
- Wi-Fi Included (Factory Installed)
- Low Ambient Cooling Based on Outdoor Unit Performance
- Low Ambient Heating Based on Outdoor Unit Performance
- Coil (Indoor) Copper Tube / Aluminum Fin
- Blue Colored Fin - 500 Hrs Salt Spray Tested
Specifications, Features & Function Summary
System Type
Indoor Model | Heat Pump | Features & Functions Summary |
---|---|---|
VIR24HP230V1R32AH | Wired Controller Interface: Yes | |
WiFi Included: Yes | ||
NEW! Easy Service Access: Yes | ||
System Performance | Indoor Fan Type: Crossflow | |
Nominal | Btu/h 22,000 | Multi Fan Speeds: 7 Speeds |
Cooling Capacity | Rated Capacity @95°F Btu/h | Indoor Unit Display: Yes |
Nominal | Btu/h 24,000 | Auxiliary Electrical Heater: No |
Heating Capacity | Rated Capacity @47°F Btu/h | Ventilation (Outdoor Air): No |
Rated Capacity @17°F Btu/h | ||
Rated Capacity @5°F Btu/h | ||
SEER2 | Remote Controller Functions | |
EER2 | NEW! Auto Clean: Yes | |
HSPF2 | Auto Mode: Yes | |
COP @5°F | System Performance Based on the Connected Outdoor Unit Performance | Auto Fan: Yes |
Cooling Temperature Range | °F | Auto Swing (Horizontal Auto Swing): Yes |
Heating Temperature Range | °F | Auto Swing - 180° (Vertical Auto Swing): Yes |
Refrigerant Type | R32 | Clock: Yes |
Indoor Unit | VIR24HP230V1R32AH | Dry Mode: Yes |
Air flow (Min - Max) | CFM 383-736 | Dry Anti-Mildew (X-Fan) Mode: Yes |
Sound Pressure Level (Min - Max) | dB(A) 34-52 | Energy Saving Mode: Yes |
Dehumidification | pt/hr 4.23 | Dirty Filter Alert: Yes |
External Dimensions (W x H x D) | in 42-21/64 x 13-7/64 x 9-11/16 | Fan Speed Control: Yes |
Package Dimension (W x H x D) | in 44-39/64 x 16-19/64 x 13-7/64 | I Feel Function: Yes |
Net Weight | lbs | Privacy Lock: Yes |
Gross Weight | lbs 35.3 | Quiet Mode: Yes |
41.9 | Room Temperature Display: Yes | |
Refrigerant Piping | Sleep Mode: Yes | |
Line Set Sized by the Indoor Unit (Liquid - Gas) | in 1/4 - 5/8 | 3 Sleep Mode Options: Yes |
- Flared Connections | Timer Mode: Yes | |
Electrical | Turbo Mode: Yes | |
Power Supply | 208-230V/1Ph/ 60Hz (Powered by the Outdoor Unit) | Display On/Off Control: Yes |
Freeze Guard Mode: Yes | ||
Power Failure Mode: Yes | ||
Humidity Control: Yes |
Dimensions & Clearances
Indoor Unit Dimensions
Unit: inch | W | H | D | W1 | W2 | W3 |
---|---|---|---|---|---|---|
VIR24HP230V1R32AH | 42 21/64 | 13 7/64 | 9 11/16 | 77/32 | 27 55/64 | 7 1/4 |
Top View Diagram
W: Width
D: Depth
W1: Side Clearance 1
W2: Main Width
W3: Side Clearance 2
Side View Diagram
W: Width
H: Height
D: Depth
Indoor Unit Minimum Clearance
Space to the ceiling at least 3 inch ⬆️
Space to the wall at least 2 inch ⬅️
Space to the floor at least 48 inch ⬇️
Space to the wall at least 2 inch ➡️
Space to the obstruction at least 48 inch
W1: 6 57/64
W2: 27 55/64
W3: 7 1/4
Clearance W1: 2 23/64
Clearance W3: 1 11/16
Diagram illustrating minimum clearances around the indoor unit for proper installation and airflow.