General
The RP-2002C is a six-zone FACP designed for single and dual hazard agent releasing applications. It provides reliable fire detection, signaling, and protection for commercial, industrial, and institutional buildings requiring agent-based releasing. The RP-2002C is compatible with System Sensor's i³ detectors, which are conventional smoke detectors capable of transmitting maintenance trouble signals (indicating the need for cleaning) and supervisory 'freeze' signals when ambient temperatures fall below approximately 45°F (7.22°C). The panel also supports conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches, and other normally-open contact devices. Consult the Notifier Device Compatibility Document for a complete list of compatible devices.
Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble, and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are included on the main circuit board. The RP-2002C supervises all wiring, AC voltage, battery charger, and battery level.
Activation of a compatible smoke detector or any normally-open fire alarm initiating device triggers audible and visual signaling devices, illuminates an indicator, displays alarm information on the panel's LCD, sounds the piezo sounder, activates the FACP alarm relay, and can operate an optional module to notify a remote station or initiate an auxiliary control function.
Image Description: A photograph of the RP-2002C control panel, showing its front interface with an LCD screen and several indicator lights, along with the Notifier by Honeywell branding.
Features
- Listed to Standard ULC-S527-11.
- FM Approved.
- Designed for agent releasing standards NFPA 12, 12A, 12B, and 2001.
- Meets International Building Code (IBC) seismic requirements.
- Disable/Enable control per input zone and output zone.
- Extensive transient protection.
- Dual hazard operation.
- Adjustable pre-discharge, discharge, and waterflow delay timers.
- Cross-zone (double-interlock) capability.
- Six programmable Style B (Class B) IDCs (Initiating Device Circuits).
- System Sensor i³ series detector compatible.
- Four programmable Style Y (Class B) output circuits (special application power).
- Strobe synchronization compatibility with System Sensor, Wheelock, Gentex, Faraday, and Amseco devices.
- Three programmable Form-C relays.
- 7.0 amps total 24 VDC output current.
- Resettable and non-resettable output power.
- Built-in Programmer.
- ANN-BUS for connection to optional devices (up to 8 total, including N-ANN-80, N-ANN-I/O, N-ANN-S/PG, N-ANN-RLY, N-ANN-LED).
- 80-character backlit LCD display.
- Real-time clock/calendar with automatic daylight savings time control.
- History log with 256 event storage.
- Piezo sounder for alarm, trouble, and supervisory signals.
- 24 volt operation.
- Low AC voltage sense.
- Outputs programmable for Releasing Circuits or NACs.
- NACs programmable for Silence Inhibit, Strobe Synchronization, Selective Silence (horn-strobe mute), Temporal or Steady Signal, Silenceable or Non-silenceable, Release Stage Sounder.
- Automatic battery charger with charger supervision.
- Optional Trim Ring TR-CE (red) for semi-flush mounting.
- Optional N-CAC-5X Class A Converter Module for Outputs and IDCs.
- Optional 4XTM Municipal Box Transmitter Module.
- Optional Digital Alarm Communicators (411, 411UD, 411UDAC).
Programming and Software
- Custom English labels can be manually entered or selected from an internal library file for each point.
- Programmable Abort operation.
- Three programmable Form-C relay outputs.
- Pre-programmed and custom application templates available.
- Continuous fire protection is maintained during online programming at the front panel.
- Program Check feature automatically identifies common errors not linked to specific zones or input points.
User Interface
- Integral 80-character LCD display with backlighting.
- Real-time clock/calendar with automatic daylight savings adjustments.
- ANN-Bus for connection to annunciators or remote indicators.
- Audible or silent walk test capabilities.
- Piezo sounder for alarm, trouble, and supervisory signals.
Controls and Indicators
LED Indicators
- FIRE ALARM (red)
- SUPERVISORY (yellow)
- TROUBLE (yellow)
- AC POWER (green)
- ALARM SILENCED (yellow)
- DISCHARGED (red)
- PRE-DISCHARGE (red indicator)
- ABORT (yellow indicator)
Control Buttons
- ACKNOWLEDGE
- SIGNAL SILENCE
- SYSTEM RESET (lamp test)
- ALARM SIGNAL
Terminal Block Specifications
AC Power - TB1
- RP-2002C: 120 VAC, 60 Hz, 3.66 amps.
- Wire size: minimum #14 AWG (2.0 mm²) with 600V insulation, supervised, nonpower-limited.
Battery (sealed lead acid only) – J12
- Maximum Charging Circuit - Normal Flat Charge: 27.6 VDC @ 1.4 amp. Supervised, nonpower-limited.
- Maximum Charger Capacity: 18 Amp Hour battery (two 18 Amp Hour batteries can be housed in the FACP cabinet; larger batteries require a separate battery box like the BB-26 or NFS-LBBR).
- Minimum Battery Size: 12 Amp Hour.
Initiating Device Circuits - TB4 and TB6
- Zones 1-5 on TB4.
- Zone 6 on TB6.
- Supervised and power-limited circuitry.
- Style B (Class B) wiring with Style D (Class A) option.
- Normal Operating Voltage: Nominal 20 VDC.
- Alarm Current: 15 mA minimum.
- Short Circuit Current: 40 mA max.
- Maximum Loop Resistance: 100 Ohms.
- End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
- Standby Current: 4 mA.
- Refer to the Notifier Device Compatibility Document for listed compatible devices.
Notification Appliance and Releasing Circuit(s) - TB5 and TB7
- Four Output Circuits.
- Style Y (Class B) or Style Z (Class A) with optional converter module.
- Special Application power.
- Supervised and power-limited circuitry.
- Normal Operating Voltage: Nominal 24 VDC.
- Maximum Signaling Current: 7.0 amps (3.0 amps special application, 300 mA regulated maximum per NAC).
- End-of-Line Resistor: 4.7K Ohms, 1/2 watt (PN 71252).
- Max. Wiring Voltage Drop: 2 VDC.
- Refer to the Notifier Device Compatibility Document for compatible listed devices.
Form-C Relays - Programmable - TB8
- Relay 1: factory default programmed as Alarm Relay.
- Relay 2: factory default programmed as fail-safe Trouble Relay.
- Relay 3: factory default programmed as Supervisory Relay.
- Relay Contact Ratings: 2 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive).
Auxiliary Trouble Input – J6
The Auxiliary Trouble Input is an open collector circuit used to monitor external devices for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, that is compatible with open collector circuits.
Special Application Resettable Power - TB9
- Operating Voltage: Nominal 24 VDC.
- Maximum Available Current: 500 mA, appropriate for powering 4-wire smoke detectors (see note).
- Power-limited Circuitry.
- Refer to the Notifier Device Compatibility Document for compatible listed devices.
NOTE: Total current for resettable power, nonresettable power, and Output Circuits must not exceed 7.0 amps.
Special Application Resettable or Nonresettable Power TB9
- Operating Voltage: Nominal 24 VDC.
- Maximum Available Current: 500 mA (see note 1).
- Power-limited Circuitry.
- Jumper selectable by JP31 for resettable or nonresettable power.
- Refer to the Notifier Device Compatibility Document for compatible listed devices.
System Specifications
System Capacity
Annunciators: 2
Electrical Specifications
- RP-2002C (FLPS-7 Power Supply): 120 VAC, 60 Hz, 3.66 amps.
- Wire size: minimum 14 AWG (2.0 mm²) with 600 V insulation, supervised, nonpower-limited.
Cabinet Specifications
- Door: 19.26" (48.92 cm) high x 16.82" (42.73 cm) wide x 0.72" (1.82 cm) deep.
- Backbox: 19.00" (48.26 cm) high x 16.65" (42.29 cm) wide x 5.25" (13.34 cm) deep.
- Trim Ring (TR-CE): 22.00" (55.88 cm) high x 19.65" (49.91 cm) wide.
Shipping Specifications
- Dimensions: Height 20.00" (50.80cm), Width 22.50" (57.15cm), Depth 8.50" (21.59cm).
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 - 49°C and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C. However, extreme temperature ranges and humidity can adversely affect the useful life of standby batteries and electronic components. Installation in an environment with a normal room temperature of 15 - 27°C is recommended.
NFPA Standards
The RP-2002C complies with the following NFPA 72 Fire Alarm Systems requirements:
- NFPA 12 CO2 Extinguishing Systems
- NFPA 12A Halon 1301 Extinguishing Systems
- NFPA 12B Halon 1211 Extinguishing Systems
- NFPA 72 National Fire Alarm Code for Local Fire Alarm Systems and Remote Station Fire Alarm Systems (requires an optional Remote Station Output Module).
- NFPA 2001 Clean Agent Fire Extinguishing Systems
Agency Listings and Approvals
The following apply to the basic RP-2002C control panel. Consult factory for latest listing status, as some modules may not be listed by all agencies or may be in process.
- ULC: S635
- Seismic Listing: Reference certificate of compliance VMA - 45894-01 by the VMC Group.
- FM approved.
Product Line Information
RP-2002C: Six-zone, 24 volt Agent Release Control Panel (includes backbox, power supply, technical manual, and a frame & post operating instruction sheet) for single and dual hazard agent releasing applications.
N-CAC-5X: Class A Converter Module. Converts Style B (Class B) Initiating Device Circuits to Style D (Class A) and Style Y (Class B) Output Circuits to Style Z (Class A). Note: Two modules are required to convert all four Output Circuits and six Initiating Device Circuits.
4XTM: Transmitter Module. Provides a supervised output for local energy municipal box transmitter and alarm/trouble reverse polarity. Includes a disable switch and disable trouble LED.
N-ANN-80C: Remote LCD indicator that mimics the FACP LCD display but does not allow panel control. Recommended wire type is unshielded.
N-ANN-LED: Built-in Annunciator Module. Provides three LEDs per zone: Alarm, Trouble, and Supervisory. Ships with red or black enclosure (see DN-60242).
N-ANN-RLY: Relay Module. Mountable inside or outside the cabinet, provides 10 programmable Form-C relays (See DN-7107).
N-ANN-S/PG: Serial/Parallel Printer Gateway module for connecting a serial or parallel printer (See DN-7103).
N-ANN-I/O: LED Driver Module. Provides connections for a user-supplied graphic annunciator (See DN-7105).
ANN-SEC: Optional card for a secondary ANN-BUS (See #53944).
N-BG-12LR(A): Agent Release Pull Stations designed for use with Notifier Fire Alarm Control Panels with releasing capabilities.
TR-CE: Trim-ring (red) for semi-flush mounting of the cabinet.
BB-26: Battery box, holds up to two 26 Amp Hour batteries and CHG-75.
NFS-LBBR: Battery box, houses two 55 Amp Hour batteries (red).
SEISKIT-COMMENC: Seismic mounting kit, required for seismic-certified installations.
BAT Series Batteries: Refer to DN-6933.
PRN-6F: UL-listed compatible event printer. Dot-matrix, tractor-fed paper, 120 VAC.
PRN-7: UL-listed compatible event printer. Dot-matrix, tractor-fed paper, 120 VAC.
PRT-PK-CABLE: Programming cable for updating FACP flash firmware (requires an RS485 to RS232 converter).