Notifier RP-2002(E) Agent Release Control Panel

Manufacturer: Honeywell

Product Type: Conventional Releasing Panels

General

The RP-2002 is a six-zone FACP for single and dual hazard agent releasing applications. It provides reliable fire detection, signaling, and protection for commercial, industrial, and institutional buildings requiring agent-based releasing. The RP-2002 is compatible with System Sensor's i³ detectors, which are conventional smoke detectors that can transmit a maintenance trouble signal to the FACP indicating the need for cleaning and a supervisory 'freeze' signal when the ambient temperature falls below the detector rating of approximately 45°F (7.22°C). In addition, the control panel is compatible with conventional input devices such as two-wire smoke detectors, four-wire smoke detectors, pull stations, waterflow devices, tamper switches, and other normally-open contact devices. Refer to the Notifier Device Compatibility Document for a complete listing of compatible devices.

Four outputs are programmable as NACs (Notification Appliance Circuits) or releasing circuits. Three programmable Form-C relays (factory programmed for Alarm, Trouble, and Supervisory) and 24 VDC special application resettable and non-resettable power outputs are also included on the main circuit board. The RP-2002 supervises all wiring, AC voltage, battery charger, and battery level.

Activation of a compatible smoke detector or any normally-open fire alarm initiating device will activate audible and visual signaling devices, illuminate an indicator, display alarm information on the panel's LCD, sound the piezo sounder at the FACP, activate the FACP alarm relay, and operate an optional module used to notify a remote station or initiate an auxiliary control function.

The RP-2002E offers the same features as the RP-2002 but allows connection to 220/240 VAC. Unless otherwise specified, the information in this data sheet applies to both the 110/120 VAC and 220/240 VAC versions of the panels.

Features

RP-2002 Components and Capabilities

Programming and Software

User Interface

Controls and Indicators

LED Indicators

Control Buttons

Electrical Specifications

Battery

Initiating Device Circuits - TB4 and TB6

Notification Appliance and Releasing Circuit(s) - TB5 and TB7

Form-C Relays - Programmable - TB8

Auxiliary Trouble Input – J6

The Auxiliary Trouble Input is an open collector circuit which can be used to monitor external devices for trouble conditions. It can be connected to the trouble bus of a peripheral, such as a power supply, which is compatible with open collector circuits.

Special Application Resettable Power - TB9

Special Application Resettable or Nonresettable Power - TB9

NOTE: Total current for resettable power, nonresettable power, and Output Circuits must not exceed 7.0 amps.

Product Line Information

System Capacity

Annunciators: 8

Cabinet Specifications

Shipping Specifications

Temperature and Humidity Ranges

This system meets NFPA requirements for operation at 0 - 49°C/32 - 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 - 27°C/60 – 80°F.

NFPA Standards

The RP-2002(E) complies with the following NFPA 72 Fire Alarm Systems requirements:

Agency Listings and Approvals

The listings and approvals below apply to the basic RP-2002(E) control panels. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.

NOTE: For ULC-listed model, see DN-60444.

Models: RP-2002-E, RP-2002-E Agent Release Control Panel, Agent Release Control Panel, Release Control Panel, Control Panel

File Info : application/pdf, 4 Pages, 806.35KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676770424

References

Acrobat Distiller 9.0.0 (Windows)

Related Documents

Preview Notifier RP-2002C Agent Release Control Panel | Fire Alarm System Specifications
Comprehensive details on the Notifier RP-2002C Agent Release Control Panel, including its features, technical specifications, compatibility, and compliance with fire safety standards for commercial and industrial applications.
Preview Notifier NFW-50X Intelligent Addressable FACP with Communicator Datasheet
Datasheet for the Notifier NFW-50X Intelligent Addressable Fire Alarm Control Panel (FACP). This panel features a pre-installed communicator, supports up to 50 addressable devices, and offers dual POTS/IP communication capabilities, along with compliance to NFPA standards.
Preview NOTIFIER FireVoice-25/50ZS Voice Evacuation Control Panel - Technical Specifications
Detailed information and specifications for the NOTIFIER FireVoice-25/50ZS Zoned System Voice Evacuation Control Panel, including features, capabilities, and system requirements.
Preview Notifier NFS2-640 Intelligent Addressable Fire Alarm Control Panel - Technical Specifications and Features
Comprehensive overview of the Notifier NFS2-640 Intelligent Addressable Fire Alarm Control Panel, detailing its features, FlashScan protocol, ONYX intelligent sensing, system capacity, specifications, agency listings, and compatible devices.
Preview Notifier FireWarden-100-2 Installation, Operations & Programming Manual
Comprehensive guide for the Notifier FireWarden-100-2 Fire Alarm Control Panel (FACP), detailing installation, operation, and programming procedures. Covers system limitations, safety precautions, specifications, and advanced features for fire protection systems.
Preview Notifier LCD-160 Manual: Installation and Operation Guide
Comprehensive manual for the Notifier LCD-160, detailing its features, specifications, installation, wiring, and operation for fire alarm and emergency communication systems. Includes important safety precautions and compliance information.
Preview NOTIFIER NFS2-640/E Installation Manual
Installation manual for the NOTIFIER NFS2-640/E Fire Alarm Control Panel, detailing system overview, components, installation procedures, applications, testing, and electrical specifications.
Preview NOTIFIER Intelligent Control Panel SLC Wiring Manual
Comprehensive wiring manual for NOTIFIER Intelligent Control Panel SLC devices, covering installation, circuit configurations (Class A, B, X), module types, and system compatibility. Essential guide for fire alarm system installers.