Goodman FTXNG-A Series Inverter Split Unit Air Conditioner Engineering Data
Brand: Goodman
Product Type: Air Conditioner
Model Series: FTXNG-A
Description: This document provides comprehensive engineering data for the Goodman FTXNG-A Series Wall Mounted Inverter Split Unit Air Conditioner Heatpump operating at 60Hz. It includes detailed specifications, functions, dimensions, wiring and piping diagrams, capacity tables, operation limits, sound level information, and electrical characteristics for various models.
Introduction
Model Name and Power Supply
Indoor Unit | Outdoor Unit | Power Supply |
---|---|---|
FTXNG09AXVJU | RXNG09AXVJU | 1Phase, 208/230V, 60Hz |
FTXNG12AXVJU | RXNG12AXVJU | |
FTXNG18AXVJU | RXNG18AXVJU |
Nomenclature
Indoor Unit
Definition | Description |
---|---|
Unit Category | F : Air-Cooled Split Indoor Unit |
Product Type | T : Wall Mounted |
System | X : Inverter, Heatpump |
Grade | N : R410A, Internet Model |
Brand | G : Goodman Brand |
Capacity Indication* | 09 : 9,000 Btu/h |
Major Design Category | A : A Series |
Factory Origin | X : Malaysia |
Power Supply | VJ : 208/230V / 1Phase / 60Hz |
Country | U : United States |
Remark: *Capacity value under Nomenclature is an indication. Please refer to Specifications Data for exact capacity value.
Outdoor Unit
Definition | Description |
---|---|
Unit Category | R : Air-Cooled Split Outdoor Unit |
System | X : Inverter, Heatpump |
Grade | N : R410A, Internet Model |
Brand | G : Goodman Brand |
Capacity Indication* | 09 : 9,000 Btu/h |
Major Design Category | A : A Series |
Factory Origin | X : Malaysia |
Power Supply | VJ : 208/230V / 1Phase / 60Hz |
Country | U : United States |
Functions
Category | Functions | FTXNG09/12A RXNG09/12A | FTXNG18A RXNG18A |
---|---|---|---|
Inverter Basic Function | Operation Limit for Cooling (°CDB)(O/D) | 10 - 46 | 10 - 46 |
Operation Limit for Cooling (°FDB)(O/D) | 50 - 114.8 | 50 - 114.8 | |
Operation Limit for Heating (°CWB)(O/D) | -15 - 18 | -15 - 18 | |
Operation Limit for Heating (°FWB)(O/D) | 5 - 64.4 | 5 - 64.4 | |
Compressor | Scroll Compressor | • | • |
Swing Compressor | - | - | |
Rotary Compressor | • | • | |
Comfortable Airflow | Power-airflow Flap | • | • |
Power-airflow Dual Flaps | • | • | |
Power-airflow Diffuser | • | • | |
Wide Angle Louvers | • | • | |
Vertical Auto-Swing (Up and Down) | • | • | |
Horizontal Auto-Swing (Right and Left) | • | • | |
3D Airflow | • | • | |
Comfort Control | Breeze Airflow | • | • |
Auto Fan Speed | • | • | |
Indoor Unit Quiet Operation | • | • | |
Intelligent Eye Operation | • | • | |
Automatic Defrosting | • | • | |
Operation | Automatic Operation | • | • |
Programme Dry Function | • | • | |
Fan Only | • | • | |
Powerful Operation (Non Inverter) | • | • | |
Inverter Powerful Operation | • | • | |
Lifestyle Convenience | Energy Saving Function | • | • |
Sleep Mode | • | • | |
Indoor Unit ON/OFF Button | • | • | |
Remote Control | R/C with Backlight | • | • |
Signal Receiving Sign (R/C) | • | • | |
Set Temperature Display (R/C) | • | • | |
WIFI Connectivity | * | * | |
Health & Clean | Saranet Filter | • | • |
Anti-virus Filter / Gin-ION Filter | - | - | |
Catechin Filter / Green Tea Filter | • | • | |
Titanium Apatite Air-Purifying Filter | • | • | |
PM 2.5 Filter | - | - | |
Streamer | • | • | |
Plasma | • | • | |
Wipe Clean Flat Panel | • | • | |
Timer | Weekly Timer Operation (Wired R/C) | • | • |
24-hour ON/OFF Timer (R/C) | • | • | |
Countdown ON/OFF Timer (R/C) | • | • | |
Worry Free (Reliability & Durability) | Auto Restart (after Power Failure) | • | • |
Self-diagnosis | • | • | |
Anti-corrosion Treatment of Outdoor Heat Exchanger | Blue Fin | Blue Fin | |
Flexibility | Pre-charged Piping Length | 32-13/16 ft | 32-13/16 ft |
Either Side Drain (Right or Left) | • | • | |
BAG Connectivity | * | * | |
DIII-NET Connectivity | * | * | |
Remote Controller | Wireless | BRC52B67 | BRC52B67 |
Wired | - | - |
Note: •: Available, -: Not Available, *: Optional (Refer to DAMA Spare Part team for more details on optional items.)
Specifications
The following tables detail the specifications for the Goodman FTXNG-A Series Inverter Split Unit Air Conditioner models.
FTXNG09A / RXNG09A
MODEL | INDOOR UNIT OUTDOOR UNIT | Cooling | Heating | |||
---|---|---|---|---|---|---|
kW | Btu/h | kW | Btu/h | |||
Rated Capacity (Min. ~ Max.) | 2.57 (1.30 - 3.00) | 8800 (4400 - 10200) | 2.75 (1.30 - 3.80) | 9400 (4400 - 13000) | ||
Moisture Removal | gal/h | 0.09 | ||||
Rated Running Current | A | 3.82 | 3.70 | |||
Rated Power Consumption | W | 800 | 774 | |||
EER2 | Btu/h/W | 11.0 | 18.0 | |||
SEER2 | N/A | N/A | ||||
COP | W/W | N/A | 3.56 | |||
HSPF2 | N/A | 9.0 | ||||
Power Factor (Rated) | N/A | N/A | ||||
Piping Connections | Liquid | inch (mm) | 1/4" (6.35) | 1/4" (6.35) | ||
Gas | inch (mm) | 3/8" (9.52) | 3/8" (9.52) | |||
Refrigerant Type | R410A | |||||
Charge | lbs (kg) | 1.54 (0.7) | 1.54 (0.7) | |||
Max. Interunit Piping Length | ft (m) | 65-5/8 (20) | 65-5/8 (20) | |||
Max. Interunit Height Difference | ft (m) | 32-13/16 (10) | 32-13/16 (10) | |||
Chargeless | ft (m) | 32-13/16 (10) | 32-13/16 (10) | |||
Amount of Additional Charge of Refrigerant | oz/ft (g/m) | 0.21 (20) | 0.21 (20) | |||
Drawing No. | 3D143694C | |||||
INDOOR UNIT | ||||||
Front Panel Colour | WHITE | |||||
Airflow Rate | Turbo | CFM | 466 | 402 | ||
High | CFM | 431 | ||||
Medium | CFM | 322 | ||||
Low | CFM | 249 | ||||
Quiet | CFM | |||||
Sound Pressure Level (H/M/L/Q) | dBA | 43/36/29/19 | 42/35/29/25 | |||
Fan | Type | CROSS FLOW | ||||
Drive | DIRECT | |||||
Speed | 3 STEPS, QUIET, AUTO, TURBO | |||||
Type | DIRECT CURRENT | |||||
Fan Motor | Motor Output | W | 22 | |||
Running Current (Rated) | A | 0.10 | ||||
Power Consumption (Rated) | W | 29 | ||||
Air Direction Control | UP, DOWN, LEFT, RIGHT | |||||
Air Filter | CATECHIN | |||||
Dimensions (H x W x D) | inch (mm) | 11-1/3 x 30-5/16 x 9-3/16 (288 x 770 x 234) | ||||
Packaged Dimensions (H x W x D) | inch (mm) | 13-7/8 x 32-3/4 x 12-3/8 (350 x 830 x 314) | ||||
Weight | lbs (kg) | 20.3 (9.2) | ||||
Gross Weight | lbs (kg) | 24.7 (11.2) | ||||
Condensate Drain Size | inch (mm) | 5/8 (16) | ||||
Document No. | 3D143550B | |||||
OUTDOOR UNIT | ||||||
Casing Colour | IVORY WHITE | |||||
Airflow Rate High | CFM | 1083 | 1103 | |||
Sound Pressure Level | dBA | 46 | 48 | |||
Fan | Type | PROPELLER | ||||
Drive | DIRECT | |||||
Type | DIRECT CURRENT | |||||
Index of protection (IP) | 24 | |||||
Insulation Grade | E | |||||
Fan Motor | Running Current (Rated) | A | 0.60 | 0.61 | ||
Power Consumption (Rated) | W | 32 | 46 | |||
Motor Output | W | 26 | 26 | |||
Poles | 8 | |||||
Compressor | Type | HERMETIC SWING | ||||
Model | 1YC23AUXDA | |||||
Oil type | DAPHNE FVC50K | |||||
Oil amount | oz (cm3) | 12.4 (375) | ||||
Heat Exchanger Type | FIN TUBE | |||||
Dimensions (H x W x D) | inch (mm) | 21-11/16 x 26-1/2 x 11-3/16 (550 x 675 x 284) | ||||
Packaged Dimensions (H x W x D) | inch (mm) | 24-1/64 x 31-3/8 x 15-1/8 (610 x 801 x 384) | ||||
Weight | lbs (kg) | 55 (25) | ||||
Gross Weight | lbs (kg) | 62 (28) | ||||
Document No. | 3D143595A |
Note: 1) ALL UNITS ARE BEING TESTED ACCORDING TO AHRI 210/240 STANDARD. 2) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Cooling Conditions: Indoor: 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB), Outdoor: 95°FDB (35°CDB)
Heating Conditions: Indoor: 70°FDB (21.1°CDB), Outdoor: 47°FDB (8.3°CDB) / 43°FWB(6.1°CWB)
FTXNG12A / RXNG12A
MODEL | INDOOR UNIT OUTDOOR UNIT | Cooling | Heating | |||
---|---|---|---|---|---|---|
kW | Btu/h | kW | Btu/h | |||
Rated Capacity (Min. ~ Max.) | 3.22 (1.30 - 3.90) | 11000 (4400 - 13300) | 3.31 (1.30 - 4.81) | 11300 (4400 - 16400) | ||
Moisture Removal | gal/h | 0.18 | ||||
Rated Running Current | A | 3.22 | 4.55 | |||
Rated Power Consumption | W | 1294 | 1004 | |||
EER2 | Btu/h/W | 8.5 | N/A | |||
SEER2 | N/A | N/A | ||||
COP | W/W | N/A | 3.30 | |||
HSPF2 | N/A | 9.0 | ||||
Power Factor (Rated) | N/A | N/A | ||||
Piping Connections | Liquid | inch (mm) | 1/4" (6.35) | 1/4" (6.35) | ||
Gas | inch (mm) | 3/8" (9.52) | 3/8" (9.52) | |||
Refrigerant Type | R410A | |||||
Charge | lbs (kg) | 2.09 (0.95) | 2.09 (0.95) | |||
Max. Interunit Piping Length | ft (m) | 65-5/8 (20) | 65-5/8 (20) | |||
Max. Interunit Height Difference | ft (m) | 32-13/16 (10) | 32-13/16 (10) | |||
Chargeless | ft (m) | 32-13/16 (10) | 32-13/16 (10) | |||
Amount of Additional Charge of Refrigerant | oz/ft (g/m) | 0.21 (20) | 0.21 (20) | |||
Drawing No. | 3D143694C | |||||
INDOOR UNIT | ||||||
Front Panel Colour | WHITE | |||||
Airflow Rate | Turbo | CFM | 473 | 412 | ||
High | CFM | 436 | ||||
Medium | CFM | 316 | ||||
Low | CFM | 247 | ||||
Quiet | CFM | 132 | 210 | |||
Sound Pressure Level (H/M/L/Q) | dBA | 45/37/31/19 | 43/36/30/26 | |||
Fan | Type | CROSS FLOW | ||||
Drive | DIRECT | |||||
Speed | 3 STEPS, QUIET, AUTO, TURBO | |||||
Type | DIRECT CURRENT | |||||
Fan Motor | Motor Output | W | 22 | |||
Running Current (Rated) | A | 0.10 | ||||
Power Consumption (Rated) | W | 29 | ||||
Air Direction Control | UP, DOWN, LEFT, RIGHT | |||||
Air Filter | CATECHIN | |||||
Dimensions (H x W x D) | inch (mm) | 11-1/3 x 30-5/16 x 9-3/16 (288 x 770 x 234) | ||||
Packaged Dimensions (H x W x D) | inch (mm) | 13-7/8 x 32-3/4 x 12-3/8 (350 x 830 x 314) | ||||
Weight | lbs (kg) | 21.4 (9.7) | ||||
Gross Weight | lbs (kg) | 25.8 (11.7) | ||||
Condensate Drain Size | inch (mm) | 5/8 (16) | ||||
Document No. | 3D143550B | |||||
OUTDOOR UNIT | ||||||
Casing Colour | IVORY WHITE | |||||
Airflow Rate High | CFM | 1051 | 966 | |||
Sound Pressure Level | dBA | 48 | 48 | |||
Fan | Type | PROPELLER | ||||
Drive | DIRECT | |||||
Type | DIRECT CURRENT | |||||
Index of protection (IP) | 24 | |||||
Insulation Grade | E | |||||
Fan Motor | Running Current (Rated) | A | 0.61 | 0.61 | ||
Power Consumption (Rated) | W | 46 | 46 | |||
Motor Output | W | 26 | 26 | |||
Poles | 8 | |||||
Compressor | Type | HERMETIC SWING | ||||
Model | 1YC23AUXDA | |||||
Oil type | DAPHNE FVC50K | |||||
Oil amount | oz (cm3) | 12.4 (375) | ||||
Heat Exchanger Type | FIN TUBE | |||||
Dimensions (H x W x D) | inch (mm) | 21-11/16 x 26-1/2 x 11-3/16 (550 x 675 x 284) | ||||
Packaged Dimensions (H x W x D) | inch (mm) | 24-1/64 x 31-3/8 x 15-1/8 (610 x 801 x 384) | ||||
Weight | lbs (kg) | 62 (28) | ||||
Gross Weight | lbs (kg) | 68 (31) | ||||
Document No. | 3D143595A |
Note: 1) ALL UNITS ARE BEING TESTED ACCORDING TO AHRI 210/240 STANDARD. 2) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Cooling Conditions: Indoor: 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB), Outdoor: 95°FDB (35°CDB)
Heating Conditions: Indoor: 70°FDB (21.1°CDB), Outdoor: 47°FDB (8.3°CDB) / 43°FWB(6.1°CWB)
FTXNG18A / RXNG18A
MODEL | INDOOR UNIT OUTDOOR UNIT | Cooling | Heating | |||
---|---|---|---|---|---|---|
kW | Btu/h | kW | Btu/h | |||
Rated Capacity (Min. ~ Max.) | 5.27 (1.96 - 5.86) | 18000 (6700 - 20000) | 5.24 (1.70 - 6.60) | 17900 (5800 - 22500) | ||
Moisture Removal | gal/h | 0.41 | ||||
Rated Running Current | A | 7.53 | 6.98 | |||
Rated Power Consumption | W | 1714 | 1590 | |||
EER2 | Btu/h/W | 10.5 | N/A | |||
SEER2 | N/A | N/A | ||||
COP | W/W | N/A | 3.30 | |||
HSPF2 | N/A | 8.5 | ||||
Power Factor (Rated) | N/A | N/A | ||||
Piping Connections | Liquid | inch (mm) | 1/4" (6.35) | 1/2" (12.70) | ||
Gas | inch (mm) | 1/2" (12.70) | 1/2" (12.70) | |||
Refrigerant Type | R410A | |||||
Charge | lbs (kg) | 3.20 (1.45) | 3.20 (1.45) | |||
Max. Interunit Piping Length | ft (m) | 98-1/2 (30) | 98-1/2 (30) | |||
Max. Interunit Height Difference | ft (m) | 32-13/16 (10) | 32-13/16 (10) | |||
Chargeless | ft (m) | 32-13/16 (10) | 32-13/16 (10) | |||
Amount of Additional Charge of Refrigerant | oz/ft (g/m) | 0.21 (20) | 0.21 (20) | |||
Drawing No. | 3D143694C | |||||
INDOOR UNIT | ||||||
Front Panel Colour | WHITE | |||||
Airflow Rate | Turbo | CFM | 754 | 395 | ||
High | CFM | 716 | ||||
Medium | CFM | 605 | ||||
Low | CFM | 467 | ||||
Quiet | CFM | |||||
Sound Pressure Level (H/M/L/Q) | dBA | 48/43/37/33 | 46/41/36/33 | |||
Fan | Type | CROSS FLOW | ||||
Drive | DIRECT | |||||
Speed | 3 STEPS, QUIET, AUTO, TURBO | |||||
Type | DIRECT CURRENT | |||||
Fan Motor | Motor Output | W | 39 | |||
Running Current (Rated) | A | 0.17 | ||||
Power Consumption (Rated) | W | 54 | ||||
Air Direction Control | UP, DOWN, LEFT, RIGHT | |||||
Air Filter | CATECHIN | |||||
Dimensions (H x W x D) | inch (mm) | 11-11/16 x 39-9/16 x 10-3/4 (297 x 990 x 273) | ||||
Packaged Dimensions (H x W x D) | inch (mm) | 14-1/4 x 42-1/4 x 14-1/8 (362 x 1073 x 358) | ||||
Weight | lbs (kg) | 31 (14) | ||||
Gross Weight | lbs (kg) | 36 (16.5) | ||||
Condensate Drain Size | inch (mm) | 5/8 (16) | ||||
Document No. | 3D143550B | |||||
OUTDOOR UNIT | ||||||
Casing Colour | IVORY WHITE | |||||
Airflow Rate High | CFM | 1987 | 1952 | |||
Sound Pressure Level | dBA | 53 | 53 | |||
Fan | Type | PROPELLER | ||||
Drive | DIRECT | |||||
Type | DIRECT CURRENT | |||||
Index of protection (IP) | 23 | |||||
Insulation Grade | E | |||||
Fan Motor | Running Current (Rated) | A | 1.30 | 1.30 | ||
Power Consumption (Rated) | W | 85 | 85 | |||
Motor Output | W | 55 | 55 | |||
Poles | 8 | |||||
Compressor | Type | HERMETIC SWING | ||||
Model | 2Y147AKCX2A | |||||
Oil type | DAPHNE FVC50K | |||||
Oil amount | oz (cm3) | 21.5 (650) | ||||
Heat Exchanger Type | FIN TUBE | |||||
Dimensions (H x W x D) | inch (mm) | 27-13/32 x 36-5/8 x 13-13/16 (696 x 930 x 351) | ||||
Packaged Dimensions (H x W x D) | inch (mm) | 29-7/8 x 42-3/8 x 18-7/8 (760 x 1075 x 480) | ||||
Weight | lbs (kg) | 97 (44) | ||||
Gross Weight | lbs (kg) | 106 (48) | ||||
Document No. | 3D143595A |
Note: 1) ALL UNITS ARE BEING TESTED ACCORDING TO AHRI 210/240 STANDARD. 2) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
Cooling Conditions: Indoor: 80°FDB (26.7°CDB) / 67°FWB (19.4°CWB), Outdoor: 95°FDB (35°CDB)
Heating Conditions: Indoor: 70°FDB (21.1°CDB), Outdoor: 47°FDB (8.3°CDB) / 43°FWB(6.1°CWB)
Dimensions
The following sections describe the physical dimensions of the indoor and outdoor units. Detailed diagrams are provided in the original document.
Indoor Unit Dimensions
Model: FTXNG09/12A
Diagrams illustrate the front, rear, and bottom views of the indoor unit, showing dimensions for width, height, and depth. Key dimensions include:
- Width: 30-5/16" (770 mm)
- Height: 11-1/3" (288 mm)
- Depth: 9-3/16" (234 mm)
Model: FTXNG18A
Diagrams illustrate the front, rear, and bottom views of the indoor unit, showing dimensions for width, height, and depth. Key dimensions include:
- Width: 39-9/16" (990 mm)
- Height: 11-11/16" (297 mm)
- Depth: 10-3/4" (273 mm)
Wiring Diagrams
Wiring diagrams are provided for both indoor and outdoor units to illustrate electrical connections.
Indoor Unit Wiring Diagram (Model: FTXNG-A)
This diagram shows connections for the fan motor (MF), air swing motor (MS), indoor coil thermistor (TH1), room thermistor (TH2), and control board connections (CN_SW_LR, CN_DSP, CN_COIL, CN_SW_UD, CN S21, CN_NS). It also indicates power supply lines (LIVE, NEUTRAL) and field wiring connections. Optional WIFI ADAPTER and WIRED ACCESSORY connections are also noted.
Outdoor Unit Wiring Diagrams
Model: RXNG09/12A
The diagram illustrates connections for the four-way valve (4WV), fan motor (MF), compressor motor (MC), overload protector (OLP), fuses (FU2, FU3), electronic expansion valve (EXV), and terminal block (TB). It details power supply connections, wiring to sensors (Outdoor Air Sensor, Heat Exchanger Sensor, Discharge Sensor), and connections to the indoor unit. Notation includes wire colors (BLUE, YELLOW, RED, BLACK, ORANGE, WHITE, GREEN) and terminal designations.
Model: RXNG18A
This diagram shows similar components including the compressor motor (MC), fan motor (MF), electronic expansion valve (EXV), overload protector (OLP), fuses (FU1, FU2, FU3), and terminal block (TB). It details power supply, sensor connections, and connections to the indoor unit, using wire colors and terminal designations.
Piping Diagrams
Piping diagrams illustrate the refrigerant flow and connections for the air conditioning systems.
Indoor Unit Piping Diagrams
Model: FTXNG09A
Diagram shows the indoor unit's heat exchanger, cross flow fan, and fan motor. It indicates field piping connections (1/4" CuT and 3/8" CuT) to a single union joint, and refrigerant flow for cooling and heating.
Model: FTXNG12A
Similar to FTXNG09A, this diagram shows the indoor unit's heat exchanger, cross flow fan, and fan motor, with field piping connections (1/4" CuT and 3/8" CuT) to a single union joint, and refrigerant flow for cooling and heating.
Model: FTXNG18A
This diagram shows the indoor unit's heat exchanger, distributor, cross flow fan, and fan motor. It indicates field piping connections (1/4" CuT and 1/2" CuT) and refrigerant flow for cooling and heating.
Outdoor Unit Piping Diagrams
Model: RXNG09A
Diagram illustrates the outdoor unit's components including the heat exchanger, compressor, propeller fan, four-way valve, motor operated valve, strainers, and mufflers. It shows field piping connections (3/8" CuT, 5/16" CuT, 1/4" CuT) and refrigerant flow for cooling and heating.
Model: RXNG12A
This diagram shows the outdoor unit's heat exchanger, compressor, propeller fan, four-way valve, motor operated valve, strainers, and mufflers. It indicates field piping connections (3/8" CuT, 5/16" CuT, 1/4" CuT) and refrigerant flow for cooling and heating.
Model: RXNG18A
This diagram shows the outdoor unit's heat exchanger, compressor, propeller fan, four-way valve, electronic expansion valve, strainers, and mufflers. It indicates field piping connections (1/2" CuT, 3/8" CuT, 1/4" CuT) and refrigerant flow for cooling and heating.
Capacity Tables
The following tables provide detailed capacity information (Total Capacity - TC, Sensible Heat Capacity - SHC, Power Input - PI) for various operating conditions.
Capacity Data for FTXNG09A - RXNG09A
Tables show Cooling and Heating capacities based on Indoor and Outdoor temperatures (°C and °F). Units for TC/SHC are kBtu/h or kW, and PI is in kW.
Capacity Data for FTXNG12A - RXNG12A
Tables show Cooling and Heating capacities based on Indoor and Outdoor temperatures (°C and °F). Units for TC/SHC are kBtu/h or kW, and PI is in kW.
Capacity Data for FTXNG18A - RXNG18A
Tables show Cooling and Heating capacities based on Indoor and Outdoor temperatures (°C and °F). Units for TC/SHC are kBtu/h or kW, and PI is in kW.
Capacity Correction Factor by Length of Refrigerant Piping
Graphs illustrate the capacity correction factor as a function of refrigerant piping length (in meters and feet) for both cooling and heating operations for different model series (FTXNG09A/RXNG09A, FTXNG12A/RXNG12A, and FTXNG18A/RXNG18A). The graphs show that the correction factor decreases as piping length increases. Notes explain that the correction ratio is the same for different installation heights and that capacity is calculated as engineering data multiplied by the capacity correction factor. The actual unit piping length must not exceed the maximum shown.
Operation Limit
Graphs display the operational limits for the air conditioning units based on indoor and outdoor temperatures.
Cooling Operation Limits:
The graph plots Outdoor Temperature (°FDB) against Indoor Temperature (°FWB). It defines regions for "Continuous operation" and "Pull-down period". For example, continuous operation is possible within a range of approximately 50°F to 86°F outdoor temperature and 50°F to 86°F indoor wet-bulb temperature.
Heating Operation Limits:
The graph plots Outdoor Temperature (°FWB) against Indoor Temperature (°FDB). It indicates the range for "Continuous operation". For example, continuous operation is possible from approximately 14°F to 86°F outdoor wet-bulb temperature and 50°F to 86°F indoor dry-bulb temperature.
Sound Level
Measuring Location
A diagram shows the standard measuring location for sound level tests: 1.0 meter horizontally and 0.8 meters vertically from the unit, in an anechoic chamber.
Sound Pressure Level
Tables provide the 1/1 Octave A-weighted Sound Pressure Level (dB, ref 20µPa) for different models (FTXNG09A, FTXNG12A, FTXNG18A) at various speeds (High, Med, Low, Quiet) for both Cooling and Heating modes. The data includes levels for different frequency bands (63Hz to 8kHz) and an Overall Noise level (dBA).
NC Curve
NC (Noise Criteria) curves are presented graphically, plotting Octave Band Sound Pressure Level (dB) against Octave Band Center Frequency (Hz). The curves represent different noise criteria levels (NC-20 to NC-70) and show how the sound output of the units at different speeds (Quiet, Low, Medium, High, Turbo) compares to these criteria. The note clarifies that SILENT (SL) is equivalent to QUIET (Q).
Electric Characteristic
The table below summarizes the electrical characteristics for the unit combinations.
Unit Combination | Power Supply | COMP | OFM | IFM | ||||||
---|---|---|---|---|---|---|---|---|---|---|
Voltage Range | MCA | MOP | RHz | A | kW | MOC | kW | MOC | ||
FTXNG09A RXNG09A | 60Hz-208V, 60Hz-230V | MAX. 60Hz 253V MIN. 60Hz 187V | 12.35 | 15 | 88 | 4.34 | 0.026 | 0.60 | 0.022 | 0.35 |
FTXNG12A RXNG12A | 60Hz-208V, 60Hz-230V | MAX. 60Hz 253V MIN. 60Hz 187V | 12.40 | 15 | 96 | 5.57 | 0.026 | 0.61 | 0.022 | 0.40 |
FTXNG18A RXNG18A | 60Hz-208V, 60Hz-230V | MAX. 60Hz 253V MIN. 60Hz 187V | 16.55 | 20 | 90 | 8.17 | 0.055 | 1.30 | 0.039 | 0.55 |
Symbols:
- MCA: Minimum Circuit Amps (A)
- MOP: Maximum Overcurrent Protection (A)
- COMP: Compressor
- RHz: Rated Operating Frequency (Hz)
- A: Compressor Input Current (A)
- OFM: Outdoor Fan Motor
- IFM: Indoor Fan Motor
- kW: Fan Motor Rated Output (kW)
- MOC: Maximum Operating Current (A)
Notes:
- RHz is the max frequency that occurs in cooling and heating operation.
- RLA is the max current that occurs in cooling and heating operation.
- Maximum allowable voltage unbalance between phases is 2%.
- Select wire size based on the larger value of MCA.
- Use circuit breaker instead of fuse.