Operation Details

(1) The Function of Main Control

1. Time Delay Safety Control

  • Compressor is ceased for 3 minutes to balance pressure in the refrigeration cycle (Protection of compressor).
  • Indoor fan is ceased for 2 seconds to prevent relay noise (Protection of fan relay and micro chip).
  • 4-way valve is ceased for 30 seconds to prevent refrigerant-gas abnormal noise when Heating operation is OFF or switched to another mode.

2. Airflow Direction Control

This function allows the louver to swing automatically up and down and be set at the desired position.

Procedure:

  1. Press the ON/OFF Button to operate the product.
  2. Press the Airflow Direction Control Button to swing the louver up and down automatically.
  3. Repress the Airflow Direction Control Button to set the louver at the desired position.
Operating Mode Louver Position
Start 2
Cooling Auto. Swing 1-4
Start 3
Heating Auto. Swing 3-6

Horizontal Louver Position Diagram: Shows angles from 0° to 8° (Close) for Cooling (approx. 32°) and Heating (approx. 32°).

3. Cooling Mode Operation

When selecting the Cooling Mode, the unit operates according to the remote controller settings. The operation diagram is as follows:

Cooling Mode Operation Diagram: Shows Intake Air temperature fluctuations relative to COMP. ON (SET TEMP. +0.5°C) and COMP. OFF (SET TEMP. -0.5°C). INDOOR FAN operates at 'Selecting fan speed' or 'Low'. COMPRESSOR cycles ON and OFF. Mentions 'More than 3 minutes' for compressor off periods.

4. Cooling or Heating Mode with Sleep Mode Auto Operation

When selecting Cooling or Heating combined with Sleep Mode Auto Operation, the operation diagram is as follows.

Cooling Mode with the Sleep Mode

The setting temperature is raised by 1°C after 30 minutes and by 2°C after 1 hour. The operation will be stopped after 1, 2, 3, 4, 5, 6, or 7 hours.

Cooling Mode with Sleep Mode Diagram: Illustrates Intake Air temperature changes over time, showing periods of COMP. ON and COMP. OFF, with INDOOR FAN set to Low. Includes 30-minute intervals and temperature increments of 1°C and 2°C.

Heating Mode with the Sleep Mode

The operation will be stopped after 1, 2, 3, 4, 5, 6, or 7 hours.

Heating Mode with Sleep Mode Diagram: Shows temperature cycles with Setting Temp. +3°C (Compressor OFF) and Setting Temp. (Compressor ON). INDOOR FAN is set to 'Med.', and COMPRESSOR cycles ON and OFF.

5. Fuzzy Operation

The operation procedure is as follows:

  1. Press Start/Stop Button
  2. Select Fuzzy Operation Mode
  3. Check the Room temperature

Operation mode, indoor fan speed, and setting temperature are automatically decided by Fuzzy rule.

Intake-air temperature Operation Mode
below 21 °C Heating
Over 21 °C ~ below 24°C Soft Dry
Over 24°C Cooling

* If initial mode is decided, that mode is continued despite of the room temperature changing.

Fuzzy Operation for Cooling

Operation condition Intake-air Temperature Setting Temperature Fan speed Air Direction Control
When Fuzzy Operation initial start Over 26 °C 25°C 1/f rhythm Controlled by Fuzzy logic
Over 24°C~below 26 °C Intake air -1 °C
Over 22°C~below 24 °C Intake air -0.5°C
Over 20°C~below 22 °C Intake air temperature
When Switch to Fuzzy Operation below 20 °C 20°C Fuzzy control -
Over 20°C~below 30°C 20°C
over 30°C 30°C
Fuzzy Operation for Cooling Diagram: Illustrates Intake-Air temp. fluctuations relative to Setting Temp. +0.5°C (Compressor OFF) and Setting Temp. -0.5°C (Compressor ON). INDOOR FAN operates at 'Fuzzy Speed', and COMPRESSOR cycles ON and OFF.

Fuzzy Operation for Soft Dry

The Setting temperature is set to match the current intake-air temperature.

  • Compressor ON temperature: Setting temperature +1 °C
  • Compressor OFF temperature: Setting temperature -0.5°C

Fuzzy Operation for Heating

Intake Air temp. Setting temp.
Below 20°C 20°C
Over 20°C~below 21°C Intake air temperature +0.5°C
Fuzzy Operation for Heating Diagram: A graph showing Setting temp. (21°C) and Intake air temp. (+5°C) relative to Intake-Air temp. on the x-axis (18°C to 21°C). Shows operational states at different temperature points.

6. Heating Mode Operation

The unit operates according to the remote controller settings. The operation diagram is shown as following.

Heating Mode Operation Diagram: Illustrates Intake Air temp. changes relative to SETTING TEMP. +3°C (Compressor OFF) and Setting temp. (Compressor ON). INDOOR FAN cycles through OFF, Selecting fan speed, and LOW. COMPRESSOR cycles ON and OFF. Points A and B are defined: A point - indoor pipe temperature to be 35°C; B point - indoor pipe temperature to be 35°C. Indoor fan operates minimum 10sec. even if falls lower than 35°C.

7. Hot- Start Control

The indoor fan stops until the evaporator piping temperature reaches 28°C (BY TEMPERATURE).

Hot-Start Control Diagram: Shows PIPE TEMP. 28°C. INDOOR FAN cycles through OFF, LOW, and SELECTING FAN SPEED. COMPRESSOR is ON. Includes a 60-second duration marker.

8. Deice Control

Deicing operation is controlled by timer and sensing the indoor pipe temperature.

Deicing Diagram: A graph showing TEMP °C over time, illustrating Heating, Deicing, and Hot Start phases. It plots Pipe Tmp. and Intake Air Temp. and indicates durations of 25mins and 60mins. A table shows COMPRESSOR, 4-WAY VALVE, OUTDOOR FAN, INDOOR FAN, and DEICE LED states during these phases.
ΔT1-ΔT2=ΔTd Over 3.5°C 3.0~3.5°C 2.5~3.0℃ 2.0~2.5°C below 2.0°C
Deicing Time 12 mins 11 mins 10 mins 9 mins Heating Operation

9. Soft Dry Operation

During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, and the compressor OFF temperature is the setting temperature minus 0.5°C.

In this temperature range, the operation repeats 10min. Dry Operation, 5.5min operation OFF, 1.5min. fan-only operation. During the 10min Dry operation, even if the room temperature falls below the compressor OFF temperature, the 10min(MAX) Compressor ON period includes 4 min. Compressor ON operation below the compressor OFF temperature.

In micom dehumidify mode, fan speed control is as follows:

Soft Dry Operation Diagram: Illustrates ROOM TEMP. fluctuations relative to SETTING TEMP. +1 °C (COMP. ON) and SETTING TEMP. -5°C (COMP. OFF). INDOOR FAN cycles through Selecting fan speed, OFF, and LOW. COMPRESSOR cycles ON and OFF. Includes time markers for operation and off periods (e.g., 1 minute, 10 minutes, 5.5 minutes, 2 minutes, 1.5 minutes, maximum 4 minutes, maximum 10 minutes).

10. Forced Operation

If the wireless remote controller is lost, the unit can be operated using the forced operation switch.

The standard conditions are as follows:

Operation Mode Cooling Model Heat pump Model
Room Temp ≥ 24°C 21°C ≤ Room Temp < 24 °C Room temp < 21 °C
Operation Mode Cooling Cooling Soft Dry Heating
FAN Speed High High Low High
Setting Temp. 24 °C 24°C Room Temp. 22°C
Models: AG4AH12BWF01 9K, AG4AH12BWF01 9K Air Conditioner Dualsplit, AG4AH12BWF01 9K, Air Conditioner Dualsplit, Conditioner Dualsplit, Dualsplit

File Info : application/pdf, 8 Pages, 567.99KB

PDF preview unavailable. Download the PDF instead.

125853-1

References

FPDF 1.86 AFP

Related Documents

Preview LG HMC018KD Air Conditioner Owner's Manual - Operation and Parts
This owner's manual provides detailed operational information and control functions for the LG HMC018KD air conditioner, including cooling, heating, and auto modes, as well as defrost and sleep modes. It also covers forced operation and crank case heater control.
Preview LG Energy Recovery Ventilators (ERV): High Efficiency, Smart Control, and Clean Air Supply
Explore LG's range of Energy Recovery Ventilators (ERV) designed for high efficiency, smart control, and improved indoor air quality. Featuring advanced heat exchangers, CO2 monitoring, UVnano technology, and easy maintenance for residential and commercial applications.
Preview LG Air Conditioner Owner's Manual
Comprehensive owner's manual for LG Floor Standing Air Conditioners, covering installation, operation, safety instructions, and maintenance. Includes detailed guides on various modes, airflow settings, timers, and troubleshooting.
Preview LG Air Conditioner Owner's Manual - Model MFL69781202
Comprehensive owner's manual for the LG Wall Mounted Air Conditioner (Model MFL69781202), covering safety precautions, operation, smart functions, maintenance, and troubleshooting.
Preview LG R5206 Air Conditioner Owner's Manual and Installation Guide
Comprehensive owner's manual and installation guide for the LG R5206 air conditioner, providing setup instructions, troubleshooting tips, and electrical data.
Preview LG Air Conditioner Installation Manual - Dry Contact for Setback
Comprehensive installation manual for LG Air Conditioners featuring the Dry Contact for Setback module. This guide provides detailed instructions on setup, wiring, and operational modes for controlling air conditioning units via external signals.
Preview LG LED LCD TV Owner's Manual
Comprehensive owner's manual for LG LED LCD TVs, covering safety instructions, installation, unpacking, parts, and operation. Learn how to set up and use your LG TV.
Preview LG PWLSSB21H Wireless Remote Controller Specifications and Features
Detailed information on the LG PWLSSB21H Wireless Remote Controller, including unit data, electrical specifications, temperature settings, and a comprehensive list of standard features and button functions.