Operation Details
(1) The Function of Main Control
1. Time Delay Safety Control
- Compressor is ceased for 3 minutes to balance pressure in the refrigeration cycle (Protection of compressor).
- Indoor fan is ceased for 2 seconds to prevent relay noise (Protection of fan relay and micro chip).
- 4-way valve is ceased for 30 seconds to prevent refrigerant-gas abnormal noise when Heating operation is OFF or switched to another mode.
2. Airflow Direction Control
This function allows the louver to swing automatically up and down and be set at the desired position.
Procedure:
- Press the ON/OFF Button to operate the product.
- Press the Airflow Direction Control Button to swing the louver up and down automatically.
- Repress the Airflow Direction Control Button to set the louver at the desired position.
Operating Mode | Louver Position | |
---|---|---|
Start | 2 | |
Cooling | Auto. Swing | 1-4 |
Start | 3 | |
Heating | Auto. Swing | 3-6 |
Horizontal Louver Position Diagram: Shows angles from 0° to 8° (Close) for Cooling (approx. 32°) and Heating (approx. 32°).
3. Cooling Mode Operation
When selecting the Cooling Mode, the unit operates according to the remote controller settings. The operation diagram is as follows:
4. Cooling or Heating Mode with Sleep Mode Auto Operation
When selecting Cooling or Heating combined with Sleep Mode Auto Operation, the operation diagram is as follows.
Cooling Mode with the Sleep Mode
The setting temperature is raised by 1°C after 30 minutes and by 2°C after 1 hour. The operation will be stopped after 1, 2, 3, 4, 5, 6, or 7 hours.
Heating Mode with the Sleep Mode
The operation will be stopped after 1, 2, 3, 4, 5, 6, or 7 hours.
5. Fuzzy Operation
The operation procedure is as follows:
- Press Start/Stop Button
- Select Fuzzy Operation Mode
- Check the Room temperature
Operation mode, indoor fan speed, and setting temperature are automatically decided by Fuzzy rule.
Intake-air temperature | Operation Mode |
---|---|
below 21 °C | Heating |
Over 21 °C ~ below 24°C | Soft Dry |
Over 24°C | Cooling |
* If initial mode is decided, that mode is continued despite of the room temperature changing.
Fuzzy Operation for Cooling
Operation condition | Intake-air Temperature | Setting Temperature | Fan speed | Air Direction Control |
---|---|---|---|---|
When Fuzzy Operation initial start | Over 26 °C | 25°C | 1/f rhythm | Controlled by Fuzzy logic |
Over 24°C~below 26 °C | Intake air -1 °C | |||
Over 22°C~below 24 °C | Intake air -0.5°C | |||
Over 20°C~below 22 °C | Intake air temperature | |||
When Switch to Fuzzy Operation | below 20 °C | 20°C | Fuzzy control | - |
Over 20°C~below 30°C | 20°C | |||
over 30°C | 30°C |
Fuzzy Operation for Soft Dry
The Setting temperature is set to match the current intake-air temperature.
- Compressor ON temperature: Setting temperature +1 °C
- Compressor OFF temperature: Setting temperature -0.5°C
Fuzzy Operation for Heating
Intake Air temp. | Setting temp. |
---|---|
Below 20°C | 20°C |
Over 20°C~below 21°C | Intake air temperature +0.5°C |
6. Heating Mode Operation
The unit operates according to the remote controller settings. The operation diagram is shown as following.
7. Hot- Start Control
The indoor fan stops until the evaporator piping temperature reaches 28°C (BY TEMPERATURE).
8. Deice Control
Deicing operation is controlled by timer and sensing the indoor pipe temperature.
- Temperature difference ΔT1 between indoor pipe temperature and indoor intake air temperature is checked after 25 minutes of heating operation.
- Temperature difference ΔT2 between indoor pipe temperature and indoor intake air temperature is checked after 60 minutes of heating operation.
- Deicing time is controlled by difference ΔTd of ΔT1 and ΔT2.
- The deicing time and operation diagram are as follows.
ΔT1-ΔT2=ΔTd | Over 3.5°C | 3.0~3.5°C | 2.5~3.0℃ | 2.0~2.5°C | below 2.0°C |
---|---|---|---|---|---|
Deicing Time | 12 mins | 11 mins | 10 mins | 9 mins | Heating Operation |
9. Soft Dry Operation
During Soft Dry Operation, the compressor ON temperature is the setting temperature plus 1°C, and the compressor OFF temperature is the setting temperature minus 0.5°C.
- When the room temperature rises over the compressor ON temperature, the operation mode switches to Cooling mode.
- When the room temperature falls between the compressor ON and OFF temperatures, the operation mode switches to Soft Dry Operation.
In this temperature range, the operation repeats 10min. Dry Operation, 5.5min operation OFF, 1.5min. fan-only operation. During the 10min Dry operation, even if the room temperature falls below the compressor OFF temperature, the 10min(MAX) Compressor ON period includes 4 min. Compressor ON operation below the compressor OFF temperature.
In micom dehumidify mode, fan speed control is as follows:
10. Forced Operation
If the wireless remote controller is lost, the unit can be operated using the forced operation switch.
The standard conditions are as follows:
Operation Mode | Cooling Model | Heat pump Model | ||
---|---|---|---|---|
Room Temp ≥ 24°C | 21°C ≤ Room Temp < 24 °C | Room temp < 21 °C | ||
Operation Mode | Cooling | Cooling | Soft Dry | Heating |
FAN Speed | High | High | Low | High |
Setting Temp. | 24 °C | 24°C | Room Temp. | 22°C |