Potter PFC-4064 Conventional Fire Alarm Control Panel

Features

Description

The PFC-4064 Conventional Fire Panel is a compact, expandable panel designed to monitor all facets of a fire alarm system and communicate the status to a monitoring station. The PFC-4064 panel is a listed and approved microprocessor based conventional fire panel and complies with UL-864, NFPA-70, and NFPA-72. The panel is provided with six (6) inputs and four (4) 24VDC, 3.0 Amp Notification Appliance Circuits (NAC) with strobe synchronization. The 5.0 Amp power supply provides ample power to meet any jurisdictions requirements and will charge up to two (2) 55 amp/hour batteries. In addition, the panel has the Potter P-Link for connection to system accessories. The panel also has a 1.0 Amp auxiliary power output for controlling ancillary fire alarm functions.

The control panel is in a metal cabinet with a key lock and lexan window for viewing the system status. The printed circuit assembly is mounted for quick removal and installation to allow the cabinet to be installed with minimal effort. The cabinet houses up to two (2) 7 AH or two (2) 12 AH batteries.

The display is an eighty (80) character LCD with system status LEDs. The system status is clearly displayed and the panel includes a history buffer for past events. The key pad allows navigation into the system menu, limited programming and system control. The condition and events on the panel are clearly displayed to allow the user and installer to determine the system status.

The panel will support up to thirty-one (31) system accessories.

Technical Specifications

Dimensions 18 1/2" H x 14 1/4" W x 4 3/4" D
Enclosure 18 gauge cold rolled steel with removable locked door with Lexan viewing window
AC Mains 5.0 amp @ 120 VAC 60 Hz
2.0 amp @ 240 VAC 50 Hz
Battery 70 mA Standby
235 mA Alarm
Temperature and Humidity Range 32° to 120° (0°C to 49°C) with a maximum humidity of 93% non-condensing.
Standards NFPA 70, 72

2-Wire Smoke Detector Compatibility

SYSTEM SENSOR (Brk) (Max. No. Of Detectors Per Zone Is 20)

Detector Model Identifier Base Model Identifier
1400 A N/A N/A
2400 A N/A N/A
2400TH A N/A N/A
2W-B A N/A N/A
2WT-B A N/A N/A

DETECTION SYSTEM (Max. No. Of Detectors Per Zone Is 25)

Detector Model Identifier Base Model Identifier
DS250 A MB2W/MB2WL A
DS250TH A MB2W/MB2WL A

ESL (Max. No. Of Detectors Per Zone Is 25)

Detector Model Identifier Base Model Identifier
611U S10 601U S00
611UD S10 601U S00
611UT S10 601U S00
612U S10 601U S00
612UD S10 601U S00
613U5 S10 601U S00
611UD S10 609U10 S00
612UD S10 609U10 S00
425C S10 N/A N/A
425CT S10 N/A N/A

HOCHIKI (Max. No. Of Detectors Per Zone Is 25)

Detector Model Identifier Base Model Identifier
SLR-24 HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
NS6-220 HB-3
SLR-24H HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221
SIJ-24 HD-3 HSC-221R HB-71
HSB-221 HB-54
HSB-221N HB-54
NS6-221
NS4-221

Detector Compatibility (Continued)

FENWAL (Max. No. Of Detectors Per Zone Is 25)

Detector Model Identifier Base Model Identifier
CPD-7051 151FE1 2-WIRE FE51A
PSD-7155 P55FE1 2WRLT FE52A
PSD-7156 P56FE1 2WRB FE55A

All of the above Fenwal detectors and bases can be used in any combination.

Retrofit Base Adaptor 70-501000-003, Identifier MAFE1 (for series 70-201000 Bases, Models -001, -002, -003, and -005). Duct Housing with Detector Base DH-51, Identifier DH22FE5 (for CPD-7051 and PSD-7155 detectors only).

POTTER (Max. No. Of Detectors Per Zone Is 25)

Detector Model Description Identifier Base Model Identifier
CPS-24 HD-3 (HOCHIKI) SB-46 HB-4 (HOCHIKI)
SB-93 HB-3 (HOCHIKI)
PS-24H HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)
IS-24 HD-3 (HOCHIKI) SB-46 HB-71 (HOCHIKI)
HB-54 (HOCHIKI)

NOTE: If using a mix of System Sensor and other smoke detectors, a maximum of 20 detectors shall be permitted.

User Interface

The fire alarm control panel has a 4 x 20 LCD display to provide information to the system status. The keypad has navigation keys to allow manipulation of the Menu on board the panel. The panel is shipped standard with the following LEDs:

The common buttons include a Silence, Reset, Acknowledge, and Drill. All of the buttons are accessible once the locked door is opened.

P-Link

The PFC-4064 has a proprietary communication protocol that communicates through a RS-485 connection to field devices. Up to 31 devices may be connected to a single P-Link connection. The P-Link includes the communication terminals and regulated 24 VDC connection for the field devices. The field devices may be any of the following:

Ethernet/I.P. Connection

The PFC-4064 is shipped standard with an Ethernet connection. This connection is the programming port and may be connected to a building Wide Area Network (WAN) or Local Area Network (LAN). Once connected to the Internet, the panel may be selectively programmed to e-mail alarm conditions, trouble conditions, supervisory conditions, test, Event History and detector status. An e-mail may be sent to the panel and the panel will e-mail the event history, detector status, configuration file or server status to an authorized E-mail account. In addition, reminders may be set to send an e-mail for service, testing or other conditions.

In addition, the Ethernet connection is UL listed as an IP communicator. The IP communicator is listed to report to the UL listed Sur-Gard III IP receiver. The IP communicator replaces the traditional less reliable alarm communicator transmitter that utilized telephone lines. The IP communicator is an active method of connection and communication to the monitoring station.

The FIB-1000, FCB-1000 and the SPG-1000 may be installed in the stacker bracket or ordered with the optional rack mount enclosure.

MC-1000 Multi-Connect allows up to sixty-three panels to share a single reporting technology.

Dimensions

A diagram showing the dimensions of the PFC-4064 control panel is provided. The dimensions are:

Ordering Information

Model Description Stock No.
PFC-4064 Fire Alarm Control Panel 3992360
Replacement Board 3992363

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 800-325-3936 • www.pottersignal.com

Models: PFC-4064 Conventional Fire Alarm Control Panel, PFC-4064, Conventional Fire Alarm Control Panel, Fire Alarm Control Panel, Alarm Control Panel

File Info : application/pdf, 5 Pages, 1.06MB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676759119

References

Adobe PDF Library 10.0.1 Adobe InDesign CS6 (Windows)

Related Documents

Preview Potter PFC-3005T Five Zone Fire Alarm Control Panel - Technical Specifications and Features
Comprehensive details on the Potter PFC-3005T Five Zone Fire Alarm Control Panel, including features, technical specifications, wiring instructions, and ordering information for commercial and industrial fire safety systems.
Preview Potter IPA-60 Fire Alarm Control Panel: Features, Specifications, and Accessories
Detailed overview of the Potter IPA-60 analog/addressable releasing fire alarm control panel, covering its features, technical specifications, SLC loop accessories, modules, user interface, connectivity options, dimensions, and ordering information.
Preview Potter PAD100-TRTI Installation Manual: Two Relay Two Input Module
Installation guide for the Potter PAD100-TRTI addressable fire alarm module. Covers module description, address setting via dip switches, technical specifications, and wiring diagrams for Class A and Class B circuits.
Preview Potter VSR-S Vane Type Waterflow Alarm Switch with Retard Installation and Operation Manual
This document provides detailed instructions for the installation, operation, and maintenance of the Potter VSR-S Vane Type Waterflow Alarm Switch with Retard. It covers features, technical specifications, electrical connections, testing procedures, and replacement parts for the VSR-S model.
Preview Potter UD-1000 Digital Alarm Communicator Transmitter - Features, Specifications, and Installation
Comprehensive overview of the Potter UD-1000 Digital Alarm Communicator Transmitter (DACT), detailing its features, technical specifications, and installation procedures for fire alarm control panels.
Preview Potter PAD100-DUCT Analog Addressable Duct Detector Installation Manual
Comprehensive installation manual for the Potter PAD100-DUCT Analog Addressable Duct Detector. Covers product description, technical specifications, setting addresses via dip switches, wiring diagrams, mechanical installation procedures, operational and functional testing, and maintenance guidelines.
Preview Potter VSR-S (EU) Vane Type Waterflow Alarm Switch - Technical Specifications and Installation Guide
Comprehensive guide to the Potter VSR-S (EU) vane type waterflow alarm switch for small pipe sprinkler systems. Includes detailed specifications, installation procedures, testing protocols, maintenance advice, and safety precautions, covering certifications, pipe size compatibility, and operational requirements.
Preview Potter FIB-1000 Fiber Interface Bridge | RS-485 to Fiber Optic Converter
Discover the Potter FIB-1000 Fiber Interface Bridge, a key component for converting RS-485 (P-Link) circuits to fiber optic cable in fire alarm systems. Features include Class A/B operation, ST connectors, rack-mount options, and a 5-year warranty.