Potter PAD100-DUCT Analog Addressable Duct Detector Installation Manual

Brand: Potter Electric Signal Company, LLC

Notice to the Installer

This manual provides an overview and the installation instructions for the PAD100-DUCT module. This module is only compatible with addressable fire systems that utilize the PAD Addressable Protocol.

All terminals are power limited and should be wired in accordance with the requirements of NFPA 70 (NEC) and NFPA 72 (National Fire Alarm Code). Failure to follow the wiring diagrams in the following pages will cause the system to not operate as intended. For further information, refer to the control panel installation instructions.

The module shall only be installed with listed control panels. Refer to the control panel installation manual for proper system operation.

1. Description

The PAD100-DUCT duct smoke detector provides early detection of smoke and products of combustion present in the air moving through HVAC ducts in commercial, industrial and residential applications. The PAD100-DUCT is designed and built to meet all local requirements, as well as the NFPA regulations regarding duct smoke detectors.

Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7") is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined, the air intake sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths: 2.5 ft., 5 ft., and 10 ft. and cut to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws.

2. Setting the Address

All PAD protocol detectors and modules require an address prior to connection to the panel's SLC loop. Each PAD device's address (i.e., detector and/or module) is set by changing the dip switches located on the device. PAD device addresses are comprised of a seven (7) position dip switch used to program each device with an address ranging from 1–127.

Figure 1. PAD Device Dip Switch Addresses Table (Addresses 1–127)

Figure 1 displays a grid designed to help set the address for PAD devices. It features seven columns representing the dip switch positions: 1, 2, 4, 8, 16, 32, and 64. Each row corresponds to a specific address from 1 to 127. A 'gray' box in a cell indicates that the corresponding dip switch should be in the 'On' position for that address, while a 'white' box indicates the switch should be 'Off'. For example, to set address 1, only the '1' switch is 'On'. To set address 42, switches #2, #8, and #32 are set to 'On'.

Note: Each "gray" box indicates that the dip switch is "On," and each "white" box indicates "Off."

3. Technical Specifications

Figure 2. Examples of PAD Device Showing Default Dip Switch Setting (Unaddressed) & Addressed PAD Device

The examples shown below illustrate a PAD device's dip switch settings: the 1st example shows a device not addressed where all dip switch settings are in the default "Off" position, the 2nd illustrates an addressed PAD device via the dip switch settings.

AttributeValue
Duct Detector Model #PAD100-DUCT
Operating Voltage24.0V
Current Draw300μΑ
Detector Head ModelPAD100-DD
Detector Head TypePhotoelectric
Sensitivity Test MethodSelf diagnostic test
Air Velocity100 to 4000 ft./min.
Ambient Temperature32° to 120° F (0° to 49° C)
Humidity10% to 85% Relative humidity (non-condensing)
Housing MaterialPlastic backbox, clear plastic cover
FinishGray backbox with clear cover
Dimensions13 1/2" L x 4 1/2" W x 2 1/4" D
Maximum Net Weight2 lbs.
Sampling Tubes2.5 ft., 5 ft., or 10 ft.
Sampling Tube Part Numbers2.5' = 1000274, 5' = 1000275, 10' = 1000276

Before connecting a device to the SLC loop, take the following precautions to prevent potential damage to the SLC or device:

4. Wiring Diagram

Figure 3. Example of Wiring a PAD100-DUCT Duct Detector

Figure 3 illustrates the wiring for the PAD100-DUCT duct detector. It shows connections for the Signaling Line Circuit (SLC) loop, labeled '+SLC' and '-SLC', which can connect to the next module or originate from the FACP (Fire Alarm Control Panel) or a previous module. It also shows terminals L1, L2, +R, and -R. Notes indicate that SLC wiring supports Class A, X, and B styles, is power-limited and supervised. Wiring gauge should be between #12 (max) and #22 (min). Wire preparation requires stripping 1/4 inch of insulation.

Notes:

5. Mechanical Installation Instructions

LOCATION PREREQUISITES

This guideline contains general information on the PAD100-DUCT duct smoke detector installation, but does not preclude the NFPA and/or ICC documents listed. Potter Electric Signal Company assumes no responsibility for improperly installed duct detectors. To determine the correct installation position for a PAD100-DUCT duct smoke detector, the following factors must be considered.

A. A uniform non-turbulent (laminar) airflow between 100 ft/min. to 4,000 ft/min. must be present in the HVAC duct. To determine duct velocities, examine the engineering specifications that define the expected velocities or use an Alnor model 6000AP velocity meter (or equivalent).

B. To minimize the impact of air turbulence and stratification on performance, a duct smoke detector should be located as far as possible downstream from any obstruction (i.e. deflector plates, elbows, dampers, etc.). In all situations, confirmation of velocity and pressure differential within specifications is required. The pressure differential between the input sampling (high pressure) tube and exhaust (low pressure) tube for the PAD100-DUCT duct smoke detector should be greater than 0.01 inches of water and less than 1.2 inches of water.

C. Identify a code compliant location (supply or return side, or both) for the installation of the duct unit that will permit easy access for viewing and serviceability.

D. When installing on the return side, install duct units prior to the air being exhausted from the building or diluted with outside "fresh" air.

E. When installing duct smoke units downstream of filters, fires occurring in the filters will be detected, but if the filters become blocked, insufficient air flow through the duct unit will prevent the correct operation of the duct detector. Duct units installed in the supply air side may monitor upstream equipment and/or filters.

F. Where possible, install duct detectors upstream of air humidifiers and downstream of dehumidifiers.

G. To prevent false alarms, the duct detector should not be mounted in areas of extreme high or low temperatures, in areas where high humidity exists, or in areas where the duct may contain gases or excessive dust.

SAMPLING TUBE ASSEMBLY

The PAD100-DUCT duct smoke detectors employ a specially notched sampling tube, which may be ordered separately in one of four (4) standard lengths.

Standard sampling tubes are steel tubes with air intake holes located the entire length of the tube. These tubes must be cut to length and should span the entire width of the duct. Sampling tubes over 3.0' must be supported on the opposite side of the duct. To ensure the correct operation of the sensing tube, the red end cap (red stopper in installation kit) must be inserted in the end of the air intake sampling tube. For custom duct widths, always use the next longest standard size and cut down to the exact requirement.

"NO-TOOLS" TUBE INSTALLATION

The PAD100-DUCT duct smoke detector provides a unique, patented mechanism for installation and/or removal of the sampling and exhaust tubes from either the front or rear of the detector housing. Once the airflow direction has been determined, insert the inlet and exhaust tubes into the duct smoke detector. If the cover is in place, the tubes may be inserted into the back of the detector via the key-slots provided. Simply push the tube into place against the spring loaded retainer, and turn into the correct position, allowing the key to "lock" the tube in the desired orientation. For front side installation, simply rotate the tube retainer until the tube may be inserted and oriented properly. Once the tube is installed, rotate the retainer back into place to lock down the tube. Ensure air intake sampling tube is positioned so that the inlet holes are directly facing the airflow.

Figure 4. Example of the PAD100-DUCT Duct Detector Placement

Figure 4 shows the placement of the PAD100-DUCT duct detector within an HVAC duct. It depicts the duct width, airflow direction, the inlet sampling tube with its holes facing the airflow (requiring a red stopper at the end), and the exhaust tube installed downstream of the airflow. The diagram notes that tube support holes are provided for ducts wider than 3 feet and that the detector can be mounted on the side, bottom, or top of the duct, provided proper tube operation and performance are maintained.

6. Operational Testing

When DUCT and DUCTR are under normal conditions in standby mode, the alarm indicator LEDs on the detector head will pulse approximately once every 4 seconds.

Note: When a panel is configured to not flash LEDs, the LEDs on the detectors will not flash at any time.

7. Functional Testing

Note: Be sure to dis-engage all alarm signal services, releasing devices and extinguishing systems, prior to performing the following test, except automatic testing by the FACP. Be sure to re-engage these systems when all testing is complete.

8. Walk Test

The FACP must be placed into Walk Test Mode and follow the steps below. Use the appropriate steps outlined below for the detector that is to be tested.

Notes:

9. Maintenance

The detector should be cleaned as needed. Detectors installed in environments more prone to dust may need cleaning based on build-up of dust. Clean unit by removing cover and using soft cloth, vacuum or dry compressed air. Clean sensing tubes as needed to allow for the free flow of air through both inlet and exhaust tubes.

Consult your local code and AHJ requirements for required maintenance schedules.

General Information & Contact

These instructions do not purport to cover all the details or variations in the equipment described, nor provide for every possible contingency to be met in connection with installation, operation and maintenance.

Specifications subject to change without prior notification.

For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.

Actual performance is based on proper application of the product by a qualified professional. Should further information be desired or should particular problems arise, which are not covered sufficiently for the purchaser's purpose, the matter should be referred to a distributor in your region.

Manufacturer: Potter Electric Signal Company, LLC, St. Louis, MO

Website: www.pottersignal.com

Document Number: 5406322-A 05/16

Models: PAD100-DUCT Analog Addressable Duct Detector, PAD100-DUCT, Analog Addressable Duct Detector, Addressable Duct Detector, Duct Detector, Detector

File Info : application/pdf, 4 Pages, 881.50KB

PDF preview unavailable. Download the PDF instead.

?tmstv=1676664367

References

Adobe PDF Library 10.0.1

Related Documents

Preview Potter PAD100-TRTI Installation Manual: Two Relay Two Input Module
Installation guide for the Potter PAD100-TRTI addressable fire alarm module. Covers module description, address setting via dip switches, technical specifications, and wiring diagrams for Class A and Class B circuits.
Preview Potter PAD100-DRTS Duct Remote Test Switch | Technical Specifications & Installation Guide
Discover the Potter PAD100-DRTS Duct Remote Test Switch, a supervised remote test switch designed for use with Potter duct detectors. This document details its features, technical specifications, application, and installation.
Preview Potter AFC-50 Fire Alarm Control Panel: Features, Specifications, and Accessories
A comprehensive overview of the Potter AFC-50 analog/addressable Fire Alarm Control Panel, detailing its key features, technical specifications, SLC loop accessories, modules, user interface, connectivity options, and ordering information. Designed for clarity, accessibility, and SEO.
Preview Potter PAD100 Series Detector Testing Guide
A guide to functionally testing Potter PAD100 Series smoke and carbon monoxide detectors, including recommended test methods and compliance with NFPA 72.
Preview Potter PFC-4064 Conventional Fire Alarm Control Panel - Technical Specifications and Features
Detailed information on the Potter PFC-4064 Conventional Fire Alarm Control Panel, including features, technical specifications, detector compatibility, user interface, and ordering information.
Preview Potter PS-24H Photoelectric Smoke/Heat Detector - Technical Specifications and Features
Detailed information on the Potter PS-24H photoelectric smoke and heat detector, including features, technical specifications, application, and installation guidelines. Learn about its sensitivity test feature and ordering information.
Preview Potter VSR-S (EU) Vane Type Waterflow Alarm Switch - Technical Specifications and Installation Guide
Comprehensive guide to the Potter VSR-S (EU) vane type waterflow alarm switch for small pipe sprinkler systems. Includes detailed specifications, installation procedures, testing protocols, maintenance advice, and safety precautions, covering certifications, pipe size compatibility, and operational requirements.
Preview Potter VSR-ST Vane Type Waterflow Alarm Switch: Installation and Specifications
Comprehensive guide to the Potter VSR-ST Vane Type Waterflow Alarm Switch, detailing its specifications, installation procedures, testing requirements, maintenance, and removal for small pipe fire sprinkler systems.