Pixsys 2000.35.031 Converter / Convertitore TC-RTD > 4..20mA
User manual - Manuale d'uso
Introduction / Introduzione
Thanks for choosing a Pixsys device. The Signal converter code 2000.35.031 converts a signal obtained from temperature sensors PT100, PT1000 or NI100 (with a 2, 3 or 4 wires connection) into a current signal for 4..20mA loop (2 wires).
Main features:
- High accuracy;
- 16bit conversion;
- Programmable by RFid (NFC);
- Input -10..+70 mV
- 2624 Word non-volatile memory (circular buffer) for data-logging with sampling time selectable by the user;
- Possibility to rescale the output 4..20mA compared to temperature input value;
- Field calibration to compensate eventual errors (Gain and Offset);
- Compact dimensions;
The software RF Programmer (available for download on Pixsys website) and the RF Programmer allow:
- Complete configurability of the device;
- Download on PC of logged data;
- Visualization/printing of the temperature - time trend
(Italian translation of the above features is also provided in the original document)
Safety guide lines / Norme di sicurezza
Read carefully the safety guidelines and programming instructions contained in this manual before using/connecting the device.
Only qualified personnel should be allowed to use the device and/or service it and in accordance with technical data and environmental conditions listed in this manual.
Do not dispose of electric tools together with household waste material. In observance of European Directive 2002/96/EC on waste electrical and electronic equipment and its implementation in accordance with national law, electric tools that have reached the end of their life must be collected separately and returned to an environmentally compatible recycling facility.
(Italian translation of the safety guidelines is also provided in the original document)
Dimensions and installation / Dimensioni e installazione
The device has a circular shape with a diameter of 45 mm and a height of 23 mm.
Connections:
- Supply: 6...32 Vdc
- Output: 4...20mA (2 wires)
- Input terminals: A1, B1 for supply, TC/RTD input terminals, MA for output.
(Diagrams showing dimensions and connection terminals are present in the original document)
Technical Data / Dati tecnici
3.1 General data / Caratteristiche generali
Parameter | Value |
---|---|
Operating range | 6-32 Vdc |
Current output | 4..20 mA (2 wires) |
Functional insulation | 1K Vac |
Output resolution | 2 μΑ |
Upper Linearity Limit | f.s. + 5°C |
Lower Linearity Limit | f.s. -5°C |
Failure output | Selectable 21mA, 3.8mA or none |
Current output protection | 30 mA approx. |
Rejection (50-60 Hz) | 50-60 Hz |
Max transmission error | Greater between 0.1% f.s. or 0.2°C |
EMI | < 0.5% |
Cable resistance | Max 200 Ω |
Temperature coefficient | < 100 ppm/°C |
Response time (10..90%) | approx. 600 ms |
Sampling time | 300 ms |
Sealing | IP 20 |
Conformity | CE, EN 61000-6-4, EN 61000-6-2 |
3.2 Thermo-mechanic features / Caratteristiche termomeccaniche
Parameter | Value |
---|---|
Operating temperature | -40..+85 °C |
Humidity | 30-90% @ 40°C (non condensing) |
Storage temperature | -40..+105°C |
Connections | Screw pins |
Conductors section | 1 mm² |
Wires strip | 8 mm |
Enclosure | Nylon (PA66) |
Dimensions | 23 mm, Ø 45 mm |
Configuration / Configurazione
To configure this signal converter, it is necessary to use a RF Programmer and the configuration software RFID_Programmer, available on the download area of www.pixsys.net. After connecting the RF Programmer via USB and activating the software, it is possible in "EDIT" mode to configure the device selecting the type of sensor, measuring range, output for error signal, and sampling frequency for the registration. The keys "WRITE" and "READ" allow to write and read data on the devices quickly and easily.
On the lower side of the display, a list of all programmed devices is shown; it can be printed to confirm that the programming has been completed successfully.
(The original document includes screenshots of the software interface and programming options.)
Input options:
- PT100: Measuring range: -200..+600°C (2, 3, 4 wires)
- Ni100: Measuring range: -60..+180°C (2, 3, 4 wires)
- TC K: Measuring range: -260..+1360°C
- TC S: Measuring range: -40..+1760°C
- TC R: Measuring range: -40..+1760°C
- TC J: Measuring range: -200..+1200°C
- TC T: Measuring range: -260..+400°C
- TC N: Measuring range: -260..+1280°C
- TC B: Measuring range: +40..+1820°C
- TC E: Measuring range: -260..+940°C
- Input mV: Measuring range: -10..+70mV
Data Logger
This signal converter is provided with a datalogging function for the input signal. By setting the sampling time (selectable between 1 and 3600 seconds), each time the 4..20mA loop powers the device up, it will store the input value into a non-volatile memory. Through the RF Programmer, it is possible to download, display, or print all data.
(A graph illustrating the data logging trend is present in the original document.)
Connections / Connessioni
Cable colors according to IEC60751.
RTD 2 WIRE: Pt100 / Ni100 to 4...20mA. Connections: WHITE, RED wires.
RTD 3 WIRE: Pt100 / Ni100 to 4...20mA. Connections: RED, WHITE, RED wires.
RTD 4 WIRE: Pt100 / Ni100 to 4...20mA. Connections: RED, WHITE, RED, WHITE wires.
TC: Thermocouple input to 4...20mA. Connections: RED (positive), BLACK (negative).
Supply: 6...32Vdc. Connections: RED (++), BLACK (--).
(Wiring diagrams illustrating these connections are present in the original document.)