Roth Touchline® PL Controller Installation
Overview
The Roth Touchline® PL Controller is an advanced 8-channel control unit designed for heating systems, including underfloor heating. This document provides installation instructions for the 230V model.
The controller features a digital display showing current time, date, temperature settings, and operational status indicators.
Safety Warnings ⚠️
WARNING: Risk of fatal electric shock from touching live connections. Before working on the controller, always switch off the 230V power supply and prevent it from being accidentally switched on. Ensure no voltage is present before proceeding.
Mounting
The controller must be mounted on a flat surface or using a DIN rail (not included). Use screws with a maximum diameter of 3 mm.
Diagram Description: Illustrates mounting options for the controller, showing it can be attached to a flat surface or a standard DIN rail.
Electrical Connections
Actuator Connections
Connect actuators using the "brown" wire to L (Live) and the "blue" wire to N (Neutral). Use Roth Project actuators (230V, 1 Watt). The maximum number of actuators supported is 22, configurable as 3 zones of 4 actuators and 5 zones of 2 actuators.
Diagram Description: The controller features terminal blocks labeled CH1 through CH8. Each channel has connections for N (neutral) and L (live) for 230VAC power. Specific Roth Project actuators with part numbers/HVAC references are listed.
Pump Output (A) ?
This is a 230V pump output with a maximum load of 0.5 A. Cables must be secured with strain relief. The output includes an integrated pump stop function.
Diagram Description: Terminal A is designated for the 230V pump output.
Boiler/Heat Supply Output (B) ?
This is a potential-free relay output for a boiler or heat supply, with a maximum load capacity of 1 A.
Diagram Description: Terminal B is designated for the boiler/heat supply relay output.
Powering Up and Sensor Pairing ?
Connect the 230V power supply. The controller is now ready for pairing with room thermostats/sensors. Please refer to the thermostat/sensor operation manual for pairing instructions.
Diagram Description: Shows the process of connecting the 230V power supply to the Roth Touchline® PL Controller.
Fuse Replacement ?️
The controller uses a glass fuse WT 6.3A (5 x 20mm). Turn off the 230V power supply before changing the fuse.
Diagram Description: Shows the fuse holder and specifies the fuse type and size.