Features
- 3"x2" miniature size
- Universal AC input / Full range
- Class II (without FG) installations
- No load power consumption <0.1W
- High efficiency up to 91%
- For 1U applications
- Protections: Short circuit / Overload / Over voltage
- Cooling by free air convection
- -30~70℃ wide range of operating temperature
- Operating altitude up to 5000 meters
- LED indicator for power on
- 3 years warranty
Applications
- Industrial electrical equipment
- Mechanical equipment
- Factory automation equipment
- Handheld electronic device
Description
The EPS-65S is a 65W highly reliable green PCB type industrial power supply with a high power density on the 3" by 2" footprint. It accepts 80~264VAC input and offers various output voltages between 3.3V and 48V. The working efficiency is up to 91% and the extremely low no load power consumption is down below 0.1W. The EPS-65S is suitable for Class II (no FG) system design.
Model Encoding
The model number follows the format: EPS-65S-XX, where 'XX' denotes the specific output voltage.
Example: EPS-65S-3.3 indicates a 65W power supply with a 3.3V output.
Components of the model name:
- EPS-65S: Series name and wattage
- -XX: Output voltage (e.g., 3.3, 5, 7.5, 12, 15, 24, 48)
Specifications
ORDER NO. | EPS-65S-3.3 | EPS-65S-5 | EPS-65S-7.5 | EPS-65S-12 | EPS-65S-15 | EPS-65S-24 | EPS-65S-48 |
---|---|---|---|---|---|---|---|
DC VOLTAGE | 3.3V | 5V | 7.5V | 12V | 15V | 24V | 48V |
RATED CURRENT | 10A | 10A | 8A | 5.42A | 4.34A | 2.71A | 1.36A |
CURRENT RANGE | 0~11A | 0~11A | 0~8.8A | 0~5.96A | 0~4.77A | 0~2.98A | 0~1.49A |
RATED POWER | 33W | 50W | 60W | 65W | 65.1W | 65W | 65.3W |
OUTPUT PEAK LOAD(10sec.) Note.2 | 36.3W | 55W | 66W | 71.5W | 71.6W | 71.5W | 71.5W |
RIPPLE & NOISE (max.) Note.3 | 80mVp-p | 80mVp-p | 80mVp-p | 120mVp-p | 150mVp-p | 240mVp-p | 300mVp-p |
VOLTAGE ADJ.RANGE | 2.9~3.6V | 4.7~5.5V | 7.12~8.3V | 11.4~13.2V | 13.5~16.5V | 22.8~27.6V | 45.6~52.8V |
VOLTAGE TOLERANCE Note.4 | ±2.0% | ±2.0% | ±2.0% | ±2.0% | ±1.0% | ±1.0% | ±1.0% |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% | ±0.5% |
LOAD REGULATION | ±2.0% | ±2.0% | ±2.0% | ±2.0% | ±1.0% | ±1.0% | ±1.0% |
SETUP, RISE TIME | 500ms, 30ms/230VAC; 500ms, 30ms/115VAC at full load | ||||||
HOLD UP TIME (Typ.) | 30ms/230VAC; 12ms/115VAC at full load | ||||||
VOLTAGE RANGE Note.5 | 80~264VAC | ||||||
FREQUENCY RANGE | 47~63Hz | ||||||
EFFICIENCY (Typ.) | 80% | 84% | 85% | 88% | 89% | 90% | 91% |
AC CURRENT (Typ.) | 1.5A/115VAC; 1A/230VAC | ||||||
INRUSH CURRENT (Typ.) | COLD STAR 30A/115VAC; 50A/230VAC | ||||||
LEAKAGE CURRENT (max.) | 0.25mA/264VAC | ||||||
OVERLOAD PROTECTION | 115~150% rated output power. Protection type: Hiccup mode, recovers automatically after fault condition is removed. | ||||||
OVER VOLTAGE PROTECTION | 3.8~4.46V | 5.75~6.75V | 8.62~11.3V | 13.8~16.2V | 17.25~20.25V | 27.6~32.4V | 55.2~64.8V |
WORKING TEMP. | -30 ~ +70°C (Refer to "Derating Curve") | ||||||
WORKING HUMIDITY | 20% ~ 90% RH non-condensing | ||||||
STORAGE TEMP., HUMIDITY | -40 ~ +85°C, 10 ~ 95% RH | ||||||
TEMP. COEFFICIENT | ±0.03% / °C (0 ~ 50°C) | ||||||
OPERATING ALTITUDE Note.6 | 5000 meters | ||||||
VIBRATION | 10~500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes | ||||||
SAFETY STANDARDS | UL62368-1, TUV BS EN/EN62368-1, BS EN/EN60335-1, CCC GB4943.1, EAC TP TC 004 approved | ||||||
SAFETY & WITHSTAND VOLTAGE | I/P-O/P: 3KVAC | ||||||
EMC ISOLATION RESISTANCE (Note. 7) | I/P-O/P:100M Ohms / 500VDC / 25°C/70% RH | ||||||
EMC EMISSION | Compliance to BS EN/EN55032(CISPR32) Class B, BS EN/EN61000-3-2,3, GB9254.1 Class B, GB17625 Class A, EAC TP TC 020 | ||||||
EMC IMMUNITY | Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, Heavy industry Level, EAC TP TC 020 | ||||||
MTBF | 3334.3K hrs min. Telcordia SR-332 (Bellcore); 706.6K hrs min. MIL-HDBK-217F (25°C) | ||||||
DIMENSION | 76.2*50.8*24mm or 3" * 2" *0.945" inch (L*W*H) | ||||||
PACKING | 0.11Kg; 120pcs/14.2Kg/0.94CUFT |
Block Diagram
The block diagram outlines the internal signal processing of the power supply. It begins with the input stage (I/P), which includes an EMI Filter & Rectifier, followed by Rectifiers & Filter. The core of the supply is the Power Switching stage, managed by a Control unit. Protection circuits such as Overload Protection (O.L.P.) and Over Voltage Protection (O.V.P.) are integrated. The output stage consists of Rectifiers & Filter, delivering the regulated output voltage (+V, -V) at a switching frequency (fosc) of 65KHz.
Derating Curve
The derating curve illustrates the relationship between ambient temperature and the permissible load percentage. The power supply operates at 100% load capacity from -30°C up to approximately 50°C. Above 50°C, the load capacity gradually decreases (derates) linearly, reaching 0% load at 70°C ambient temperature.
Static Characteristics
The static characteristics graph depicts the load percentage as a function of input voltage. The EPS-65S series maintains its full 100% load capacity across the entire specified input voltage range, from 80VAC to 264VAC at 60Hz.
Mechanical Specification
Dimensions: 76.2mm (Length) x 50.8mm (Width) x 24mm (Height) (3" x 2" x 0.945").
AC Input Connector (CN1): JST B3P-VH or equivalent
- Pin 1: AC/N
- Pin 2: No Pin
- Pin 3: AC/L
DC Output Connector (CN2): JST B4P-VH or equivalent
- Pin 1: +V
- Pin 2: +V
- Pin 3: -V
- Pin 4: -V
Internal AC Fuse: T2.5A/250V (FS1)
Installation Manual
For detailed installation instructions, please refer to the user's manual available at: https://www.meanwell.com/manual.html
Notes
- 1. All parameters not specially mentioned are measured at 230VAC input, rated load, and 25°C of ambient temperature.
- 2. 33% Duty cycle maximum within every 30 seconds. Average output power should not exceed the rated power.
- 3. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uF & 47uF parallel capacitor.
- 4. Tolerance: includes set up tolerance, line regulation, and load regulation.
- 5. Derating may be needed under low input voltages. Please check the derating curve for more details.
- 6. The ambient temperature derating of 3.5°C/1000m for fanless models and 5°C/1000m for fan models for operating altitude higher than 2000m (6500ft).
- 7. The power supply is considered a component that will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to "EMI testing of component power" (as available on http://www.meanwell.com).
GTIN CODE
MW Search: ? https://www.meanwell.com/serviceGTIN.aspx
Product Liability Disclaimer