Honeywell Sylk™ I/O Devices

Product Data, Specifications, and Installation Guide

Application

The Sylk IO devices are part of the Spyder family. The three IO devices are designed to seamlessly integrate with Spyder with relay controllers using only Sylk™ for communication. These devices expand the footprint of a single Spyder, increasing the controller's ability to be applied in applications that require a large amount of physical I/O. The Sylk IO devices are programmable using existing Spyder wire sheets through the Niagara Framework® software. Since the Sylk IO devices are extensions of the Spyder LON and Spyder BACnet controllers, the same Spyder feature will be leveraged in the WebPro workbench tool and the WEBs-AX JACE controller. To utilize the Sylk IO devices, the Spyder with Relay models, PUL6438SR (for LON) or PUB6438SR (for BACnet), need to be selected.

The Sylk IO devices are intended for use in HVAC applications that require a programmable controller where the IO count is more than the full sized Spyder point count. All devices provide flexible, universal inputs for external sensors while SIO6042 and SIO4022 provide a combination of analog and digital outputs.

Features

Description

The Sylk IO devices are available in three models, as described in Table 1.

DevicesUI (Universal Input)DI (Digital Input)AO (Analog Output)DO (Digital Output)
SI060426042
SI040224022
SI01200012000

Each device is programmable because the user chooses which function blocks to use and how to connect them. It is configurable because each function block has user-defined behavior.

Specifications

General Specifications

Electrical

Rated Voltage: 20-30 Vac; 50/60 Hz

Power Consumption:

Environmental

Operating & Storage Temperature Ambient Rating: Minimum -40° F (-40° C); Maximum 150° F (65.5° C)

Relative Humidity: 5% to 95% non-condensing

Digital Triac Output (DO) Circuits

Voltage Rating: 20 to 30 Vac @ 50/60Hz

Current Rating: 25 mA to 500 mA continuous, and 800 mA (AC rms) for 60 milliseconds

Analog Output (AO) Circuits

Analog outputs can be individually configured for current or voltage.

ANALOG CURRENT OUTPUTS:

Current Output Range: 4.0 to 20.0 mA

Output Load Resistance: 550 Ohms maximum

ANALOG VOLTAGE OUTPUTS:

Voltage Output Range: 0 to 10.0 Vdc

Maximum Output Current: 10.0 mA

Analog outputs may be configured as digital outputs and operate as follows:

Universal Input (UI) Circuits

See Table 2 for the UI circuit specifications.

Input TypeSensor TypeOperating Range
Room/Zone Discharge Air Outdoor Air Temperature20K Ohm NTC-40° F to 199° F (-40° C to 93° C)
Outdoor Air TemperatureC7031Ga-40° to 120°F (-40° to 49°C)
C7041Fa-40° to 250°F (-40° to 121°C)
PT1000 (IEC751 3850)-40° F to 199° F (-40° C to 93° C)
TR23 Setpoint Potentiometer500 Ohm to 10,500 Ohm-4° DDC to 4° DDC (-8° DDF to 7° DDF) or 50° F to 90° F (10° C to 32° C)
Resistive InputGeneric100 Ohms to 100K Ohms
Voltage InputTransducer, Controller0 - 10 Vdc
Discrete InputDry Contact closureOpen Circuit ≥ 3000Ohms Closed Circuit < 3000Ohms

a C7031G and C7041F are recommended for use with these controllers, due to improved resolution and accuracy when compared to the PT1000.

Before Installation

The device is available in three models (see Table 1).

Review the power, input, and output specifications on page 2 before installing the device.

WARNING: Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring or making wiring connections to prevent electrical shock or equipment damage.

Installation

The device must be mounted in a position that allows clearance for wiring, servicing, and removal.

The device may be mounted in any orientation.

IMPORTANT: Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of the controller, or in areas where escaping gas or other explosive vapors are present. See Fig. 1 for mounting dimensions.

Mount Device

NOTE: The device may be wired before mounting to a panel or DIN rail.

Terminal blocks are used to make all wiring connections to the device. Attach all wiring to the appropriate terminal blocks (see "Wiring" on page 5).

See Fig. 1 for panel mounting dimensions. See Fig. 2 on page 3 for DIN rail mounting.

[Description of Fig. 1: Device dimensions in inches (mm) showing panel mounting holes and overall dimensions.]

Panel Mounting

The device enclosure is constructed of a plastic base plate and a plastic factory-snap-on cover.

NOTE: The device is designed so that the cover does not need to be removed from the base plate for either mounting or wiring.

The device mounts using four screws inserted through the corners of the base plate. Fasten securely with four No. 6 or No. 8 machine or sheet metal screws.

The device can be mounted in any orientation. Ventilation openings are designed into the cover to allow proper heat dissipation, regardless of the mounting orientation.

DIN Rail Mounting

To mount the SIO12000, SIO4022, or SIO6042 device on a DIN rail [standard EN50022; 1-3/8 in. x 9/32 in. (7.5 mm x 35 mm)], refer to Fig. 2 and perform the following steps:

  1. Holding the device with its top tilted in towards the DIN rail, hook the two top tabs on the back of the device onto the top of the DIN rail.
  2. Push down and in to snap the two bottom flex connectors of the device onto the DIN rail.

IMPORTANT: To remove the device from the DIN rail, perform the following:

  1. Push straight up from the bottom to release the top tabs.
  2. Rotate the top of the device out towards you and pull the controller down and away from the DIN rail to release the bottom flex connectors.

[Description of Fig. 2: Illustration of controller DIN rail mounting for Sylk I/O devices.]

Power

Before wiring the controller and device, determine the input and output device requirements for each controller and device used in the system. Select input and output devices compatible with the controller, device, and the application. Consider the operating range, wiring requirements, and the environment conditions when selecting input/output devices. When selecting actuators for modulating applications consider using floating control. In direct digital control applications, floating actuators will generally provide control action equal to or better than an analog input actuator for lower cost.

Determine the location of controllers, sensors, actuators and other input/output devices and create wiring diagrams.

The application engineer must review the control job requirements. This includes the sequences of operation for the controller, and for the system as a whole. Usually, there are variables that must be passed between controllers that are required for optimum system-wide operation. Typical examples are the TOD, Occ/Unocc signal, the outdoor air temperature, the demand limit control signal, and the smoke control mode signal.

It is important to understand these interrelationships early in the job engineering process, to ensure proper implementation when configuring the controllers.

Power Budget

A power budget must be calculated for each device to determine the required transformer size for proper operation. A power budget is simply the summing of the maximum power draw ratings (in VA) of all the devices to be controlled. This includes the controller itself and any devices powered from the controller, such as equipment actuators (ML6161 or other motors) and various contactors and transducers.

DeviceVA InformationObtained From
PUL6438SR5.0Spyder LON Product Data Sheet
SIO60425.0aSee "Specifications" on page 2.
R8242A Contactor fan rating21.0TRADELINE® Catalog inrush rating
D/X Stages0.0For example, assume cooling stage outputs are wired into a compressor control circuit and have no impact on the budget.
M6410A Steam Heating Coil Valve0.7TRADELINE® Catalog, 0.32A 24 Vac
TOTAL31.7

a Excludes the use of digital Triac outputs.

The system example above requires 31.7 VA of peak power. Therefore, a 100 VA AT92A transformer could be used to power one controller and device of this type. Because the total peak power is less than 33 VA, this same transformer could be used to power this configuration and meet NEC Class 2 restrictions (no greater than 100 VA).

See Fig. 4–Fig. 6 beginning on page 6 for illustrations of controller power wiring. See Table 4 for VA ratings of various devices.

DeviceDescriptionVA
PVL0000AS, PVL4022AS, and PVL6436AS controllers and Series 60 Floating Damper ActuatorController and Actuatora9.0
PUL1012S, PUL4024S, PUL6438S, PVL4024NS, or PVL6438NSControllera5.0
SIO12000IO Devicea3.0
SIO40224.0
SIO6425.0
ML684Versadrive Valve Actuator12.0
ML6161Damper Actuator, 35 lb-in.2.2
ML6185Damper Actuator SR 50 lb-in12.0
ML6464Damper Actuator, 66 lb-in.3.0
ML6474Damper Actuator, 132 lb-in.3.0
R6410AValve Actuator0.7
R8242AContactor21.0

a When used, each digital Triac output can add an additional 22 VA (peak) and 12 VA long-term.

For contactors and similar devices, the in-rush power ratings should be used as the worst case values when performing power budget calculations. Also, the application engineer must consider the possible combinations of simultaneously energized outputs and calculate the VA ratings accordingly. The worst case, which uses the largest possible VA load, should be determined when sizing the transformer.

Each device requires 24 Vac power from an energy-limited Class II power source. To conform to Class II restrictions (U.S. only), transformers must not be larger than 100 VA. A single transformer can power more than one device.

Guidelines for Power Wiring

GUIDELINES FOR POWER WIRING ARE AS FOLLOWS:

Line-Loss

Devices must receive a minimum supply voltage of 20 Vac. If long power or output wire runs are required, a voltage drop due to Ohms Law (I x R) line-loss must be considered. This line-loss can result in a significant increase in total power required and thereby affect transformer sizing. The following example is an I x R line-loss calculation for a 200 ft. (61m) run from the transformer to a device drawing 37 VA and using two 18 AWG (1.0 sq mm) wires.

The formula is:

Loss = [length of round-trip wire run (ft.)] x [resistance in wire (ohms per ft.)] x [current in wire (amperes)]

From specification data: 18 AWG twisted pair wire has a resistance of 6.52 ohms per 1000 feet.

Loss = [(400 ft.) x (6.52/1000 ohms per ft.)] x [(37 VA)/(24V)] = 4.02 volts

This means that four volts are going to be lost between the transformer and the device. To assure the device receives at least 20 volts, the transformer must output more than 24 volts. Because all transformer output voltage levels depend on the size of the connected load, a larger transformer outputs a higher voltage than a smaller one for a given load. Fig. 3 shows this voltage load dependence.

In the preceding I x R loss example, even though the device load is only 37 VA, a standard 40 VA transformer is not sufficient due to the line-loss. Looking at Fig. 3, a 40 VA transformer is just under 100 percent loaded (for the 37 VA controller) and has a secondary voltage of 22.9 volts. (Use the lower edge of the shaded zone in Fig. 3 that represents the worst case conditions.) When the I x R loss of four volts is subtracted, only 18.9 volts reaches the device. This is not enough voltage for proper operation.

In this situation, the engineer has three alternatives:

  1. Use a larger transformer. For example, if an 80 VA model is used, an output of 24.4 volts, minus the four volt line-loss, supplies 20.4V to the device (see Fig. 3). Although acceptable, the four-volt line-loss in this example is higher than recommended.

IMPORTANT: No installation should be designed where the line-loss is greater than two volts. This allows for nominal operation if the primary voltage drops to 102 Vac (120 Vac minus 15 percent).

  1. Use heavier gauge wire for the power run. 14 AWG (2.0 sq mm) wire has a resistance of 2.57 ohms per 1,000 ft. Using the preceding formula results in a line-loss of only 1.58 volts (compared with 4.02 volts). This would allow a 40 VA transformer to be used. 14 AWG (2.0 sq mm) wire is the recommended wire size for 24 Vac wiring.
  2. Locate the transformer closer to the device. This reduces the length of the wire run, and the line-loss.

The issue of line-loss is also important in the case of the output wiring connected to the Triac digital outputs. The same formula and method are used. Keep all power and output wire runs as short as practical. When necessary, use heavier gauge wire, a bigger transformer, or install the transformer closer to the controller.

To meet the National Electrical Manufacturers Association (NEMA) standards, a transformer must stay within the NEMA limits. The chart in Fig. 3 shows the required limits at various loads.

With 100 percent load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard. When a purchased transformer meets the NEMA standard DC20-1986, the transformer voltage regulating ability can be considered reliable. Compliance with the NEMA standard is voluntary.

[Description of Fig. 3: Graph showing NEMA Class 2 transformer secondary voltage output limits versus percentage of load.]

Transformer TypeVA Rating
AT40A40
AT72D40
AT87A50
AK3310 Assembly100

NOTE: The AT88A and AT92A transformers do not meet the voluntary NEMA standard DC20-1986.

Wiring

All wiring must comply with applicable electrical codes and ordinances, or as specified on installation wiring diagrams. Device wiring is terminated to the screw terminal blocks located on the top and the bottom of the device.

WARNING: Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring or making wiring connections, to prevent electrical shock or equipment damage.

NOTES:

The 24 Vac power from an energy limited Class II power source must be provided to the controller and device. To conform to Class II restrictions (U.S. only), the transformer must not be larger than 100 VA.

[Description of Fig. 4: Wiring diagram illustrating power connections for a single controller powered by one transformer.]

[Description of Fig. 5: Wiring diagram showing transformer power connections for a controller used in UL 1995 equipment with primary power over 150 volts.]

More than one controller and device can be powered by a single transformer. Fig. 6 shows power wiring details for multiple controllers.

[Description of Fig. 6: Wiring diagram illustrating power connections for multiple controllers and devices powered by a single transformer.]

Communications

Sylk™ Bus

Sylk is a two wire, polarity insensitive bus that provides both 18 VDC power and communications between a Sylk-enabled sensor, Sylk-enabled device, and a Sylk-enabled controller. Using Sylk-enabled sensors and devices saves I/O on the controller and is faster and cheaper to install since only two wires are needed and the bus is polarity insensitive. Sylk sensors and devices are configured using the latest release of the Spyder Tool for WEBPro and WEBStation. Using 18 AWG wire, the maximum wire length for Sylk is 200 ft.

For Spyders and Sylk IO devices, use the Resource Usage View in the Spyder tool to determine the maximum number of devices.

Setting the Device Bus Address Dial

Each device on a Sylk bus must use a different bus address, and there may be multiple Sylk IOs wired on a single Sylk bus. To change the bus address of a device, adjust the address dipswitches to match that of the desired bus address (1–15). Use the bus address label, shown in Fig. 7, as a reference. The default address for Sylk IOs is 1. The address on the device must match the address in the configuration tool.

[Description of Fig. 7: Illustration of Sylk I/O device bus address dipswitch settings.]

Wiring Method

WARNING: Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning wiring, or making wiring connections, to prevent electrical shock or equipment damage.

NOTE: When attaching two or more wires to the same terminal, other than 14 AWG (2.0 sq mm), be sure to twist them together. Deviation from this rule can result in improper electrical contact (see Fig. 8).

Each terminal can accommodate the following gauges of wire:

Prepare wiring for the terminal blocks, as follows:

  1. Strip 1/2 in. (13 mm) insulation from the conductor.
  2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the required terminal location and tighten the screw.
  3. If two or more wires are being inserted into one terminal location, twist the wires together a minimum of three turns before inserting them (see Fig. 8).
  4. Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the screw.
  5. Pull on each wire in all terminals to check for good mechanical connection.

[Description of Fig. 8: Diagram showing how to prepare and attach wires to terminal blocks, including twisting multiple wires.]

Wiring Details

Each device is shipped with the digital outputs, which switch the 24 Vac to the load (High Side).

The analog outputs (AO) are used to control modulating heating, cooling and economizer equipment. Any AO may be used as a digital output, as follows:

SIO4022 TerminalsLabelConnection
124VAC24VAC Power
224VAC COM24VAC-COMMON
3EGNDChassis/Earth Ground
4N/ANot Applicable
5S-BUSSylk
6S-BUSSylk
7N/ANot Applicable
8N/ANot Applicable
9N/ANot Applicable
10DO-1Discrete Triac Output
11COMDO COMMON
12DO-2Discrete Triac Output
13N/ANot Applicable
14N/ANot Applicable
15N/ANot Applicable
16AO-2Analog Output
17COMAO COMMON
18AO-1Analog Output
19UI-4Universal Input
20COMUI COMMON
21UI-3Universal Input
22UI-2Universal Input
23COMUI COMMON
24UI-1Universal Input
SIO12000 TerminalsLabelConnection
124VAC24VAC Power
224VAC COM24VAC-COMMON
3EGNDChassis/Earth Ground
4N/ANot Applicable
5S-BUSSylk
6S-BUSSylk
7UI-1Universal Input
8COMUI COMMON
9UI-2Universal Input
10UI-3Universal Input
11COMUI COMMON
12UI-4Universal Input
13UI-12Universal Input
14COMUI COMMON
15UI-11Universal Input
16UI-10Universal Input
17COMUI COMMON
18UI-9Universal Input
19UI-8Universal Input
20COMUI COMMON
21UI-7Universal Input
22UI-6Universal Input
23COMUI COMMON
24UI-5Universal Input
SIO6042 TerminalsLabelConnection
124VAC24VAC Power
224VAC COM24VAC-COMMON
3EGNDChassis/Earth Ground
4N/ANot Applicable
5S-BUSSylk
6S-BUSSylk
7UI-1Universal Input
8COMUI COMMON
9UI-2Universal Input
10DO-1Discrete Triac Output
11COMDO COMMON
12DO-2Discrete Triac Output
13AO-4Analog Output
14COMAO COMMON
15AO-3Analog Output
16AO-2Analog Output
17COMAO COMMON
18AO-1Analog Output
19UI-6Universal Input
20COMUI COMMON
21UI-5Universal Input
22UI-4Universal Input
23COMUI COMMON
24UI-3Universal Input

IMPORTANT: If the device is not connected to a good earth ground, the device's internal transient protection circuitry is compromised and the function of protecting the device from noise and power line spikes cannot be fulfilled. This could result in a damaged circuit board and require replacement of the device. Refer to installation diagrams for specific wiring.

Checkout

Step 1. Check Installation and Wiring

Inspect all wiring connections at the device terminals, and verify compliance with installation wiring diagrams. If any wiring changes are required, first be sure to remove power from the controller before starting work. Pay particular attention to:

NOTE: All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams.

For guidelines for wiring run lengths and power budget, see "Power" on page 3.

Step 2. Startup

[Description of Fig. 9: Diagram showing the location of the LED, service pin, and network connection on the Sylk I/O device.]

LED StateBlink RateStatus or Condition
OFFnot applicableNo power to processor, LED damaged, low voltage to board, first second of power up, or loader damaged.
ONON steady; not blinkingProcessor not operating. Application Program CRC being checked. This takes 1-2 seconds and occurs on each restart (power up, reset and reflash, and following configuration file download).
Very Slow Blink (continuous)1 second ON, 1 second OFFDevice is operating normally.
Slow Blink (continuous)0.5 second ON, 0.5 second OFFDevice alarm is active or device in process of configuration file download.

Step 3. Checkout Completion

At this point the device is installed and powered. To complete the checkout, the NIAGARA FRAMEWORK® application (run on a PC) is used to configure the I/O and functions of the controller and device.

Device Replacement

There are no serviceable or repairable parts inside the device.

WARNING: Fire, Explosion, or Electrical Shock Hazard. Can cause severe injury, death or property damage. Do not attempt to modify the physical or electrical characteristics of this device in any way. Replace the device if troubleshooting indicates a malfunction.

WARNING: Electrical Shock Hazard. Can cause severe injury, death or property damage. Disconnect power supply before beginning device replacement to prevent electrical shock or equipment damage.

Terminal Block Removal

To simplify device replacement, all terminal blocks are designed to be removed with the wiring connections intact and then re-installed on the new device. See Fig. 10 and refer to the following procedure:

IMPORTANT: To prevent bending or breaking the alignment pins on longer terminal blocks, insert the screwdriver at several points to evenly and gradually lift up the terminal block.

Insert the screwdriver blade no more than 1/8 in. (3 mm) to prevent damage to the terminal block alignment pins on the device circuit board.

[Description of Fig. 10: Illustration of how to remove terminal blocks from the Sylk I/O device using a screwdriver.]

Device Replacement (SIO12000, SIO4022, and SIO6042)

Perform the following to replace the SIO12000, SIO4022, and SIO6042 devices:

  1. Remove all power from the device.
  2. Remove the terminal blocks (See "Terminal Block Removal" on page 10.).
  3. Remove the old device from its mounting.

IMPORTANT (FOR DEVICES MOUNTED TO A DIN RAIL):

  1. Push straight up from the bottom to release the top pins.
  2. Rotate the top of the device outwards to release the bottom flex connectors (see Fig. 2 on page 3).
  1. Mount the new device (See "Installation" on page 2.).
  2. Replace the terminal blocks:
    • Insert each terminal block onto its alignment pins.
    • Press straight down to firmly seat it.
    • Repeat for each terminal block.
  3. Restore power to the device.
  4. Perform "Checkout" on page 9.

PDF preview unavailable. Download the PDF instead.

31-00028 Acrobat Distiller 15.0 (Windows)

Related Documents

Preview Honeywell CIPer Model 30 Controller and Expansion IO Product Data Sheet
Comprehensive product data sheet detailing the Honeywell CIPer Model 30 IP-based EDGE controllers and Expansion IO modules, covering features, specifications, ordering information, system overview, and safety standards.
Preview Novar ES1 Mounting and Wiring Guide
Comprehensive guide for mounting and wiring the Novar ES1 controller, detailing installation, connections, status indicators, and environmental considerations for building automation systems.
Preview Honeywell WEBs-N4 Installation Guide - Version 4.9.0.198
Comprehensive installation guide for Honeywell WEBs-N4 software, version 4.9.0.198. Covers system requirements, software dependencies, installation procedures, and configuration.
Preview Honeywell TB3026B Configuration Wizard Guide: HVAC Control Setup
Comprehensive guide to configuring Honeywell TB3026B and TB3026B-W BACnet controllers using the WEBStation-N4 software. Learn setup, applications, and online operations for efficient building automation.
Preview Honeywell JADE™ W7220 Economizer Module Installation Instructions
Comprehensive installation and setup guide for the Honeywell JADE™ W7220 Economizer Module, covering product description, specifications, wiring, interface overview, and troubleshooting.
Preview Honeywell Optimizer Advanced Controller Product Datasheet
Detailed specifications, features, and ordering information for the Honeywell Optimizer Advanced Controller series, featuring Niagara Framework, IMX8 processor, BACnet compliance, and advanced cybersecurity capabilities for building automation.
Preview Honeywell Optimizer Unitary Controller Datasheet
Datasheet for Honeywell 230 VAC Optimizer Unitary Controllers, detailing features, specifications, part numbers, dimensions, and communication protocols for advanced building automation systems.
Preview Honeywell TR21, TR22, TR23, TR24 Wall Modules: Installation and Specifications
Comprehensive guide to installing and configuring Honeywell TR21, TR22, TR23, and TR24 wall modules, covering features, specifications, wiring, and DIP switch settings for HVAC systems.