Honeywell Optimizer Advanced Controller
Introduction
The Advanced controllers are a family of next-generation integration and plant controllers incorporating the Niagara Framework® and powered by an IMX8 64-bit quad-core processor. These freely programmable IP devices feature a dedicated suite of IO modules for flexible control options. Leveraging the Niagara Framework®, they offer both Ethernet and Serial integration and are native profile BACnet™ Building Controllers (“B-BC”). The Advanced controller is an ISA/IEC 62443-4-2 SL2 Certified Component device, ensuring adherence to cyber security best practices.
The N-ADV-133-H-BWA, N-ADV-133-H-BWE, N-ADV-133-H-BWW, N-ADV-133-H, N-ADV-134-H, and N-ADV-112-H Advanced controllers are designed for a wide variety of complex applications. These devices feature RS-485 ports for BACnet™ MS/TP, Panel Bus, Modbus RTU, M-Bus, and IO module devices, and Ethernet ports for BACnet™ IP devices. They also include an RJ11 port for HMI devices. Controllers are equipped with touch flakes for connecting multiple IOs in series and a USB Type-C interface for serial communication with a computer. They can be mounted on a DIN rail or wall-mounted, horizontally or vertically.
Textual description of controller image: The image shows the Honeywell Optimizer Advanced Controller, a compact, black electronic device with various ports and indicators on its front and top panels. Key visible elements include Ethernet ports, RS-485 ports, USB Type-C ports, status LEDs, and branding.
Features and Highlights
Simple and Flexible Engineering
- N-ADV-112-H, N-ADV-133-H, N-ADV-134-H controllers offer multiple RS-485 ports and Ethernet ports, including one isolated IP port and multiple switched IP ports. Refer to the "Ordering Information" on page 2.
- N-ADV-133-H-BW series controllers feature three RS-485 ports and four Ethernet ports: one isolated IP port, three switched IP ports with Bluetooth™, and Wi-Fi communication.
- RJ11 port for connecting to an HMI device for field operations.
- Touch flakes support RS-485 IO module devices.
- Switched IP ports on the 133 & 134 models support Daisy chain operation and RSTP (Rapid Span Tree Protocol) for fault-tolerant networks.
- Built-in RSTP switch for loop-free forwarding network topology.
- Powered by an i.MX 8M Plus, quad Arm® Cortex®-A53 processor, designed for long-life industrial applications, operating at 1.2 GHz.
- Supports BACnet™/SC configuration within the Niagara Framework®.
- Conforms to BACnet™ Standard ANSI/ASHRAE 135 protocol version 1.15 (ISO 16484-5).
Efficiency and Safety on Site
- ISA/IEC 62443-4-2 Security Level 2 Certified Component, supporting cyber security best practices.
- Multi-color LEDs indicate operational status for isolated RS-485 communications, HMI device, Ethernet connection, and controller service state.
- Built-in advanced diagnostics software aids troubleshooting for IP and MS/TP devices.
- Protective end covers shield the touch flakes.
- Ferroelectric RAM (FRAM) stores live data and retains last known values upon power loss.
- Supports UTF-8 and UCS-2 character encoding formats.
- Runs on Ubuntu Core OS with snap container-based modular software design for enhanced security.
- Supports 802.1x network authentication protocol as a client (supplicant), requiring Niagara N4.12 or later for IT-standard security.
- Features a Neural Net Accelerator for future development of low-latency AI/ML algorithms at the edge.
Easy Upgrade
- All RS-485 ports support Panel Bus, BACnet™ MS/TP, Modbus RTU, and M-Bus.
- Features removable terminal blocks with screw (factory installed) or Push-in terminals.
- Includes a built-in Web server with HTML5 for graphics support.
Ordering Information
Controller Part Numbers Description
The controller part number structure (N-ADV-1X-X-H-BWX-C) defines key features:
- NIAGARA: Indicates Niagara Framework compatibility.
- ADVANCED: Denotes the Advanced controller series.
- 1 ISOLATED ETHERNET PORT: Specifies one isolated Ethernet port.
- NUMBER OF SWITCHED ETHERNET PORTS: Indicates the quantity of switched Ethernet ports.
- NUMBER OF RS-485 PORTS: Specifies the count of RS-485 ports.
- WI-FI REGION CODE: (A = AMERICA, E = EUROPE, W = REST OF THE WORLD) denotes the wireless region.
- BLUETOOTH™: Indicates Bluetooth connectivity.
- HMI PORT: Denotes the presence of an HMI port.
Wi-Fi Region Code and Countries
WI-FI REGION CODE | COUNTRIES |
---|---|
A = AMERICA | Anguilla, Antigua and Barbuda, Barbados, Belize, Bahamas, Bermuda, Canada, Costa Rica, Dominica, Dominican Republic, El Salvador, Guatemala, Grenada, Haiti, Honduras, Jamaica, Mexico: MX, Nicaragua, Panama, Puerto Rico, Saint Kitts and Nevis, Saint Lucia, Saint Vincent and the Grenadines, Trinidad and Tobago, and United States of America |
E = EUROPE | Austria, Belgium, Bulgaria, Croatia, Republic of Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Greenland, Hungary, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Poland, Portugal, Romania, Switzerland, Norway, Slovakia, Slovenia, Spain, Sweden, and United Kingdom |
W = REST OF THE WORLD | Morocco, Macao, Malaysia, Moldova, Mongolia, Monaco, Montenegro, Myanmar, Mauritius, Maldives, Namibia, Nepal, New Zealand, Nigeria, Oman, Pakistan, Paraguay, Peru, Philippines, Papua New Guinea, Qatar, Rwanda, Russia, Saudi Arabia, Serbia, Singapore, Senegal, South Africa, Sri Lanka, Taiwan, Thailand, Togo, Tunisia, Turkey, Ukraine, United Arab Emirates, Uzbekistan, Uruguay, Venezuela, Vietnam, Yemen, and Zimbabwe |
Note:
- Region 'A' adheres to FCC regulations (equivalent to ISED in Canada).
- Region 'E' adheres to ETSI/RED regulations (including the UK).
- Region 'W' follows FCC or ETSI regulations or a subset thereof.
Advanced Controller Part Numbers
PART NUMBER | ISOLATED ETHERNET PORTS | SWITCHED IP PORTS | HMI PORTS | RS-485 PORTS | TOUCH FLAKE (RS-485-R) | BLUETOOTH | WI-FI |
---|---|---|---|---|---|---|---|
N-ADV-134-H-C | 1 | 3 | Yes | 4 | Yes | No | No |
N-ADV-133-H-BWA-C* | 1 | 3 | Yes | 3 | Yes | Yes | Yes |
N-ADV-133-H-BWE-C* | 1 | 3 | Yes | 3 | Yes | Yes | Yes |
N-ADV-133-H-BWW-C* | 1 | 3 | Yes | 3 | Yes | No | No |
N-ADV-133-H-C | 1 | 3 | Yes | 3 | Yes | No | No |
N-ADV-112-H-C | 1 | 1 | Yes | 2 | Yes | No | No |
Note: For example, a customer wishing to buy an Advanced controller with 1 isolated Ethernet port, 3 Switched ports, and 3 serial RS-485 ports would order using part number N-ADV-133-H-C.
* Wi-Fi models have a region code. Building automation products with RF interfaces like Wi-Fi and Bluetooth™ Low Energy (BLE) require RF certification for each country or region. Major certification regions include USA (FCC), European Union (ETSI), Canada (ISED), China (SRRC), Japan (MIC), South Korea (KCC), and Taiwan (NCC). Most other countries follow these regulations.
Accessories or Replacement Parts
PART NUMBER | DESCRIPTION | AVAILABILITY |
---|---|---|
HMI-DN | Touch screen HMI (DIN rail mount) | Sold Separately |
HMI-WL | Touch screen HMI with Panel Door/Wall Base | Sold Separately |
HMI-ACC-DN | DIN Rail base accessory | Spare Part |
HMI-ACC-WL | Door/Wall base accessory | Spare Part |
HMI-CABLE-S | 0.82 ft. (0.25 m) length HMI cable, short | Spare Part |
HMI-CABLE-L | 9.84 ft. (3 m) length HMI cable, long | Spare Part |
ENDCOVER-10 | Protective end covers, pack of 10 | Spare Part |
TCVR-140-10 | Terminal covers 5.5 inches (140 mm), pack of 10 | Spare Part |
SCRW-TB-3-BLK-50 | Black 3 way screw terminals, pack of 50 | Spare Part |
SCRW-TB-3-GRY-50 | Grey 3 way screw terminals, pack of 50 | Spare Part |
PUSH-TB-3-BLK-50 | Black 3 way push terminals, pack of 50 | Sold Separately |
PUSH-TB-3-GRY-50 | Grey 3 way push terminals, pack of 50 | Sold Separately |
DIN-CLIP-10 | Din rail clip, pack of 10 | Spare Part |
REMOTE-ANT-KIT* | Wi-Fi Antenna kit | Spare Part |
IO-ADPT-S-2 | Wiring adapters, Power & Comms, Serial, pack of 2 | Sold Separately |
Note: Parts indicated as "Spare Parts" are included with the Controller or HMI.
Antenna Part Number
PART NUMBER | 2.4G | GAIN | 5G | |
---|---|---|---|---|
REMOTE-ANT-KIT | 2400 - 2483.5 MHz | 2.94 dBi | 5170 - 5250 MHz 5250 - 5330 MHz 5490 - 5710 MHz 5735 - 5835 MHz | 2.65 dBi 2.65 dBi 1.7 dBi 1.62 dBi |
Note: Only the Wireless controller is supplied with the Antenna kit.
Software Licenses and Upgrades
Advanced Controller Niagara Core Licenses
A Niagara license is required to connect with the Niagara Framework®. Select one of the licenses from the table below.
PART NUMBER | DESCRIPTION |
---|---|
N-ADV-00050-100PC * | Advanced core license for 3 Devices¹, 50 global points, 100 Panel Bus points and 18 month initial SMA |
N-ADV-00100-255PC * | Advanced core license for 5 Devices¹, 100 global points, 255 Panel Bus points and 18 month initial SMA |
N-ADV-00500-100PC * | Advanced core license for 10 Devices¹, 500 global points, 100 Panel Bus points and 18 month initial SMA |
N-ADV-01250-255PC * | Advanced core license for 25 Devices¹, 1250 global points, 255 Panel Bus points and 18 month initial SMA |
N-ADV-05000-255PC * | Advanced core license for 100 Devices¹, 5000 global points, 255 Panel Bus points and 18 month initial SMA |
N-ADV-10000-255PC * | Advanced core license for 200 Devices¹, 10000 global points, 255 Panel Bus points and 18 month initial SMA |
¹ Device limit applies only outside of Europe. Panel Bus IOs do not count towards the device limit.
Note: * To reference your region for ordering. 'A' is for America and rest of the world. 'E' is for Europe. Please contact your Honeywell Sales Representative if you have any questions.
Example for USA: A customer wishing to buy a 500 global point controller with 100 Panel Bus points in the USA where device and point count limits apply, would order using part number N-ADV-00500-100PCA.
Example for Europe: A customer wishing to buy a 500 global point controller with 100 Panel Bus points in Europe where only the point count limits apply, would order using part number N-ADV-00500-100PCE.
Advanced Controller Panel Bus Point Upgrade Licenses
Advanced Controller core licenses can be upgraded with any of the following upgrade licenses.
PART NUMBER | DESCRIPTION |
---|---|
N-ADV-0100P-UP | Upgrade License for 100 Panel Bus points |
N-ADV-0255P-UP | Upgrade License for 255 Panel Bus points |
Advanced Controller Global Capacity Point Upgrade Licenses
Advanced Controller core global points capacity licenses can be upgraded with any of the following upgrade licenses.
PART NUMBER | DESCRIPTION |
---|---|
PIN-DEV-1 | Additional 1 Device**, 50 global points capacity. |
PIN-DEV-2 | Additional 2 Device**, 100 global points capacity. |
PIN-DEV-10 | Additional 10 Device**, 500 global points capacity. |
PIN-DEV-25 | Additional 25 Device**, 1250 global points capacity. |
PIN-DEV-50 | Additional 50 Device**, 2500 global points capacity. |
** Device limit applies outside of Europe only. Panel Bus IO module points do not count towards the device limit.
Advanced Controller SMA Licenses
The Advanced Controller core licenses can be upgraded with the following SMA licenses.
PART NUMBER | DESCRIPTION |
---|---|
SMA-0001-1YR | 1 year maintenance for up to 99 global points. |
SMA-0001-3YR | 3 year maintenance for up to 99 global points. |
SMA-0001-5YR | 5 year maintenance for up to 99 global points. |
SMA-0002-1YR | 1 year maintenance for up to 499 global points. |
SMA-0002-3YR | 3 year maintenance for up to 499 global points. |
SMA-0002-5YR | 5 year maintenance for up to 499 global points. |
SMA-0010-1YR | 1 year maintenance for up to 1249 global points. |
SMA-0010-3YR | 3 year maintenance for up to 1249 global points. |
SMA-0010-5YR | 5 year maintenance for up to 1249 global points. |
SMA-0025-1YR | 1 year maintenance for up to 4999 global points. |
SMA-0025-3YR | 3 year maintenance for up to 4999 global points. |
SMA-0025-5YR | 5 year maintenance for up to 4999 global points. |
SMA-0100-1YR | 1 year maintenance for up to 9999 global points. |
SMA-0100-3YR | 3 year maintenance for up to 9999 global points. |
SMA-0100-5YR | 5 year maintenance for up to 9999 global points. |
SMA-0200-1YR | 1 year maintenance for up to 10000 or more global points. |
SMA-0200-3YR | 3 year maintenance for up to 10000 or more global points. |
SMA-0200-5YR | 5 year maintenance for up to 10000 or more global points. |
Note: The number of global points is considered at the moment of licensing. If a valid SMA is upgraded with more global points than the SMA covers, licenses will run until the SMA expires. Extending an SMA after expiration requires purchasing the SMA associated with the new number of global points.
Dimensions
Advanced Controller Dimensions
Textual description of controller dimensions: The controller measures 5.69 inches (144.52 mm) in width, 4.7 inches (119.4 mm) in height, and 2.36 inches (60 mm) in depth. Specific port locations are indicated: RS-485 ports (1-3) are isolated, with an RS-485 (4) indicator. There is an isolated Ethernet port and a switched Ethernet port. The illustration shows the N-ADV-134-H model.
Wiring Adapter Dimensions
Textual description of wiring adapter dimensions: The wiring adapter measures 0.87 inches (22.1 mm) in width, 1.92 inches (48.7 mm) in height, and 4.70 inches (119.4 mm) in depth. It is shown without protective covers.
Dimensions Summary
PARAMETER | SPECIFICATION |
---|---|
Controller Dimensions | 5.69 x 2.36 x 4.7 inches (150.2 x 60 x 119.4 mm) |
Mounting | DIN rail or wall mounted |
Wiring Adapter Dimensions | 0.87 x 1.92 x 4.7 inches (22.1 x 48.7 x 119.4 mm) |
Hardware Overview
N-ADV-133-H-BWA, N-ADV-133-H-BWE, N-ADV-133-H-BWW
Textual description of hardware layout:
- Top View: Shows RS485-2 (+/- GND), RS485-1 (+/- GND), RS485 (1-3) Indicator, Service Button, C Type USB 1, HMI Device Operational Status.
- Side View (Left/Right): Indicates RS485-3 (+/- GND), Terminal Switch Resistor, Ground, Power Supply Common, 24 VAC Power, Wi-Fi Operational Status, Bluetooth Operational Status, Controller Service Status, Controller Operational Status, T1L Indicator, RS485 Indicator. The right side also shows Touch Flake Power to IO (Power Supply/Common/Ground).
- Bottom View: Features Antenna Port (Wi-Fi 1), Isolated Ethernet Port 1, C Type USB 2 (for LON communication), HMI Port (Communication and 5VDC Power Supply Interface), Antenna Port (Wi-Fi 2), Switched Port (Port 1, Port 2, Port 3), and Touch Flake Communication to IO (T1L (+/-), RS485-R (+/-)).
System Overview
Textual description of system overview diagram: The diagram illustrates a network architecture connecting various Honeywell building automation components. It shows the Optimizer Workbench and Optimizer Supervisor (both powered by Niagara Framework) communicating with an Optimizer Advanced controller (with HMI and IO Module). This controller connects to an IT Hub and a Remote Building Manager via a Firewall. The system also includes Optimizer Unitary, Optimizer VAV, Compact VAV, and Wall modules, DALI64, and edge devices, all interconnected via different bus types. The legend indicates connections for Panel Bus, IP Ethernet, M-bus, C-Bus, LonWorks, BACnet™ MS/TP, T1L (BACnet IP), Sylk™ Bus, and Modbus RTU.
Ports and Bus Connections
Ethernet Ports
The Advanced controller can connect to a computer via Ethernet crossover cables for uploading, downloading, and debugging applications using Niagara workbench. These connections also provide Internet connectivity. The controller can be operated via a standard browser, with an integrated webserver offering all operation pages for browser-based access without interruption.
Port locations: Isolated Ethernet Port 1, Switched Ports (Port 1, Port 2, Port 3).
USB Ports (USB 2.0 Host Ports)
The controller has two USB Type-C ports for connecting computers and mobile/tablet devices via USB cable for monitoring and troubleshooting. USB port 2 can connect to an IF-LON2 gateway interface, enabling connection to a LON network.
Port labels: C TYPE USB 2 (USED FOR LON COMMUNICATION).
USB Ports (USB 2.0 Device Ports)
The USB 1 device port, located at the front, provides an Ethernet over USB connection with a permanent IP address of 192.168.255.241. This interface facilitates connection with Niagara workbench for programming and operation.
Port label: C TYPE USB 1.
Interfaces and Bus Connections
Wiring Adapter
The wiring adapter is used to extend power and communication bus to the next DIN rail of IO modules or for remotely mounted IO modules. It features a reversible cover for wiring flexibility and provides terminals for power and the RS-485 communication bus, transferred via Touch flake connections. The adapter includes removable factory-installed screw terminal blocks and shares electrical ratings, environmental ratings, DIN standards, and IP protection with IO modules.
RS-485-R Terminal and T1L Touch Flakes
- RS-485 Terminals: Touch flake connections extend RS-485 communications from the Advanced Controller to IO modules.
- T1L Touch flakes: Extend T1L communications to future T1L IO modules and communication modules, allowing RS-485 and T1L modules to coexist on the same DIN rail.
Wiring Adapter Interface
Textual description of wiring adapter interface:
- Top View: Shows Power Supply Common (24 VO), Ground, Power Supply (24 VAC/VDC), RS485 (-), RS485 (+), and GRND terminals. It also highlights Touch Flakes.
- Side View: Displays the Honeywell wiring adapter with labeled Touch Flakes.
Product Specification
Hardware
PARAMETER | SPECIFICATION |
---|---|
Ferroelectric RAM (FRAM) | 768 KB |
LPDDR4 | 2 GB |
EMMC | 8 GB |
CPU | i.MX 8M Plus, quad Arm® Cortex®-A53 processor, long life industrial grade, Frequency: 1.2 GHz |
Operating System | LINUX 64-bit |
Real-Time Clock Timekeeping Accuracy | +/- 3 ppm: +/- 1.57 minutes per year (+/- 0.26 seconds per day) |
Real-Time Clock Retention | Buffered for 72 hours by gold capacitor (3 day retention) |
Electrical
PARAMETER | SPECIFICATION |
---|---|
Operating Voltage (AC) | 24 VAC (+/-20 %) = 19 to 29 VAC 50/60 Hz |
Operating Voltage (DC) | 24 VDC (+/-20 %) = 20 to 30 VDC |
Overvoltage Protection | Protected against overvoltage of max. 29 VAC or 40 VDC. Terminals protected against short-circuiting. |
Power Consumption
CONTROLLER | POWER CONSUMPTION 24 VAC | POWER CONSUMPTION 24 VDC | CURRENT CONSUMPTION 24 VAC | CURRENT CONSUMPTION 24 VDC |
---|---|---|---|---|
N-ADV-134-H | Max. 36 VA | Max. 13 W | 1500 mA | 540 mA |
N-ADV-133-H-BWA, N-ADV-133-H-BWE, N-ADV-133-H-BWW | Max. 38 VA | Max. 14 W | 1600 mA | 580 mA |
N-ADV-133-H | Max. 34 VA | Max. 12.5 W | 1420 mA | 520 mA |
N-ADV-112-H | Max. 34 VA | Max. 12.5 W | 1420 mA | 520 mA |
Operational Environment
PARAMETER | SPECIFICATION |
---|---|
Storage Temperature | -20 to 158 °F (-28.9 to +70 °C) |
Operating temperature | -13 to 140 °F (-25 to 60 °C) |
Humidity | 5 to 95 % relative humidity (non-condensing) |
Vibration Under Operation | 0.024" double amplitude (2 to 30 Hz), 0.6 g (30 to 300 Hz) |
Dust, Vibration Protection | According to EN60730-1 |
Protection | IP20 with optional terminal covers |
Pollution Level | 2 |
Altitude | 13123 ft (4000 m) |
Standards and Certifications
PARAMETER | SPECIFICATION |
---|---|
Protection Class | IP20 |
Product Standards | UL60730-1, UL60730-2-9, UL916, IEC/EN60730-1, Energy Management Equipment, IEC/EN60730-2-9, CAN/CSA-E60730-1:02, IEC/EN61326-1, and IEC/EN61010. |
Testing Electrical Components | IEC68 |
Certification | UL60730-1, UL916, CE, BTL B-BC, BACnet™ Standard 135 version 1.14, ISO 16484-5, AMEV AS-B, FCC Part15, WEEE, C-tick RCM, Subpart B, CAN ICES-3 (B)/NMB-3(B), RCM, EAC, RoHS II, Ethernet Protocol version IEEEC 802.3, EN-1434-3, EN-13757-3, and ISA/IEC 62443-4-2 SL2 Certified. |
Energy Performance | EN12098-1:2022 and EN ISO 52120-1:2022 |
System Transformer | The system transformer(s) must be safety isolating transformers according to IEC 61558-2-6. In the U.S.A. and Canada, NEC Class 2 transformers must be used. |
Product Specification - Connection to Buses
PROTOCOLS | MAX. NO. OF DEVICES PER CHANNEL | RS-485-1 | RS-485-2 | RS-485-3 | RS-485-4 | RS-485-R (WIRING ADAPTER) |
---|---|---|---|---|---|---|
Panel Bus# | 64 | Yes | Yes | Yes | Yes | Yes |
BACnet™ MS/TP# | 64 | Yes | Yes | Yes | Yes | Yes |
Modbus RTU | 32 | Yes | Yes | Yes | Yes | Yes |
M-Bus* | 60 | Yes | Yes | Yes | Yes | Yes |
Note:
- The communication rate across each interface depends on the given communication protocol.
- # Panel BUS addressing supports up to 64 I/O modules per channel (BUS), with a max of 16 devices of each I/O module type allowed up to the maximum of 64 devices on a bus. The recommended maximum total number of Panel BUS points in the Advanced control across all busses is 510 max total. Performance is also dependent on poll rate and station configuration. It is important for the design engineer to review the station design and performance required for the application.
- * The controller can function as an M-Bus Master, using a standard-level converter (e.g., PW60) to connect to M-Bus devices.
- A wiring adapter is required for communication and power supply over RS-485-R (default channel). The default channel must be closed with a protective cover if not used.
Product Specification - Standard Protocol
The Advanced controller runs the N4 Niagara Framework® and supports standard protocols and drivers available in the core framework.
PROTOCOLS | DRIVER NAME | CONNECTION DETAILS TYPE | DETAILS |
---|---|---|---|
BACnet™ | BACnet™ MSTP | Serial | RS-485 serial communication |
BACnet™ Ethernet | Ethernet | Ethernet communication | |
BACnet™ IP | IP | IP based communication using unencrypted UDP packets | |
BACnet™ SC | IP | Encrypted communication via HTTPS over Transport Security Layer 1.3 (TLSv1.3). Requires Niagara Framework® N4.11 or higher. | |
EIB/KNX | EIB/KNX Driver | IP | Connectivity to EIBNET/IP devices |
LON | ILON Driver | IP | Yes |
LON FTT10 Driver | USB-C (2) to IFLON2 (FTT10) | Requires the IF-LON2 interface connected to the Advanced controller USB-C port (2) and provides connectivity to FTT10 LON bus. | |
M-Bus | M-Bus Driver | RS-485 to PW60 | Requires the PW60 M-BUS converter connected to the Advanced controller RS-485 and provides M-BUS Master communications to M-Bus devices. |
Modbus | Modbus RTU Driver | Serial | Connectivity to Modbus RTU Devices |
Modbus RTU Slave Driver | Serial | Enables Advanced Controller Station to function as a Modbus RTU Slave Device. | |
Modbus TCP Driver | IP | Connectivity to Modbus TCP Devices | |
Modbus TCP Slave Driver | IP | Enables Advanced Controller Station to function as a Modbus TCP Client Device. | |
MQTT (Message Queuing Telemetry Transport) | MQTT Client | IP | Allows connection to MQTT Broker for data exchange. Uses JSON toolkit for simplified MQTT engineering. |
IP to LORAWAN Sensor | IP to LORAWAN | Connects to LORAWAN wireless sensors via an IP to LORAWAN gateway using the honMqttDriver-rt.jar driver. | |
oBIX (Open Building Information Exchange) | oBIX Driver | IP | Enables communication to oBIX servers (XML standard for building information exchange). |
OPC UA (Unified Architecture) | OPC UA Client | IP | OPC UA support for Advanced Controller. |
OPC UA Server | IP | OPC UA support for Advanced Controller. | |
SNMP | SNMP Network | IP | Supports communications to SNMP Devices (SNMPv1, SNMPv2 and SNMPv3). |
Panel Bus IPv4 & v6 | Panelbus Network | Serial | Supports connection for Panel bus I/O modules from Honeywell. |
S-BUS | SBCIP Network | IP | Supports IP v4 & IPv6 addressing. |
C-BUS | C-BUS | IP | Supports RS-485 communication. Requires a converter to connect with C-Bus. |
Note: Drivers developed by Tridium & Honeywell are tested within the Niagara Framework® and are compliant with Niagara Driver development compliance. Drivers running on IP protocol should specify "IP interface" and "vlan2". Drivers on standard serial services must select RS485_x interfaces. For third-party drivers, specific testing is recommended. Additional drivers (Niagara Analytics, E-Signature, JSON toolkit, serial driver) are available.
Product Specification - Communication
Communication Parameters
PARAMETER | SPECIFICATION |
---|---|
Ethernet Connection Speed | 10/100/1000 Mbps, RJ45 |
IP Addressing Modes | DHCP - Dynamic Static |
Communication Baud Rates
PARAMETER | SPECIFICATION |
---|---|
M-Bus | 0.3 to 19.2 Kbps |
HMI Port | 5 VDC power output and RS-485-R |
Modbus RTU | 0.3 to 115.2 Kbps |
BACnet™ MS/TP | 9.6, 19.2, 38.4, 76.8, and 115.2 Kbps |
Panel Bus | 115.2 Kbps |
Wireless Power and Frequency Range
CONNECTIVITY MEDIUM | FREQUENCY RANGE | MAXIMUM POWER OUTPUT FOR CE | MAXIMUM POWER OUTPUT FOR FCC/IC |
---|---|---|---|
Bluetooth™ | 2400 MHz-2483.5 MHz | 10 mW | 10 mW |
Wi-Fi 2.4G | 2400 MHz-2483.5 MHz | 100 mW | 100 mW |
Wi-Fi 5G | 5150 MHz-5250 MHz 5250 MHz-5350 MHz 5470 MHz-5725 MHz 5725 MHz-5850 MHz | 100 mW 100 mW 100 mW 25 mW | 100 mW 100 mW 100 mW 100 mW |
Advanced Controller - Interface
Textual description of controller interfaces:
- N-ADV-134-H: Features 1-3 isolated RS-485 ports, an RS-485 (4) indicator, an isolated Ethernet port, and a switched Ethernet port. It also shows Power Supply Input, Touch Flake (Power Supply/Common/Ground), Service Status of the Controller, and Touch Flake Communication (Non-Isolated) for a 4 RS-485 port (Non-Isolated).
- N-ADV-133-H: Features 3 isolated RS-485 ports, an isolated Ethernet port, and a switched Ethernet port. It shows Power Supply Input, Touch Flake (Power Supply/Common/Ground), Service Status of the Controller, and Touch Flake Communication (Non-Isolated).
- N-ADV-112-H: Features 2 isolated RS-485 ports, an isolated Ethernet port, and a switched Ethernet port. It shows Power Supply Input, Touch Flake (Power Supply/Common/Ground), Service Status of the Controller, and Touch Flake Communication (Non-Isolated).
Certifications and Disclaimer
The Honeywell Optimizer Advanced Controller is certified with:
- BACnet™
- CE
- UL
- CUL
- US LISTED
By using this Honeywell literature, users agree that Honeywell will have no liability for any damages arising out of their use or modification of the literature. Users will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys' fees, arising out of, or resulting from, any modification to the literature by the user.
Honeywell | Building Automation
715 Peachtree Street, N.E.,
Atlanta, Georgia, 30308, United States.
https://buildings.honeywell.com/us/en
®U.S. Registered Trademark
©2024 Honeywell International Inc.
31-00631-03 | Rev. 12-24