User Guide for Honeywell models including: CIPer Model 30 Controller And Expansion IO

CIPer Model 30 Product Data Sheet

2021

Honeywell Building Technologies Technical Communications

CIPer Model 30 Data Sheet - Honeywell | Digital Assets

Controller Part Numbers The CIPer Model 30 controller is compatible with two expansion or external I/O models—WEB-O9056H and WEB-O3022H. The WEB-O9056H module is a large expansion module which adds 20 additional I/O points, and the

CIPer Model 30 Product Data Sheet - Honeywell

23 mar 2022 — Expansion IO can be directly connected to the CIPer Model 30 controller or remotely mounted up to 100 ft away. The CIPer Model 30 supports up to 8.


File Info : application/pdf, 7 Pages, 1.89MB

PDF preview unavailable. Download the PDF instead.

HBT-BMS-CIPer Model 30 Product Data 31-00236 ?download=false
CIPer Model 30

CONTROLLER AND

EXPANSION IO

CIPer Model 30 controllers are available in two models WEB-C3036EPUBNH and WEBC3036EPVBNH.
Expansion IO modules, WEB-O3022H, and WEB-O9056H are exclusively utilized with the CIPer Model 30 controller.

CONTROLLER
These are Internet Protocol (IP) based "EDGE" controllers that can be used for VAV, unitary, equipment, and plant applications. Each controller is programmable and configurable using the open Niagara 4 Framework.

Each controller is equipped with a four-port Gigabit network switch, that can integrate with broader IP peripheral devices including cameras, variable frequency drives, utility meters, lighting systems, etc. The CIPer Model 30 controllers can communicate over TCP/ IP (FOXS), BACnet, and Modbus protocols. These controllers can be used to aggregate information (including real-time data, alarms, trends, and history) and integrate this data to maximize the efficiency and lifespan of expensive facility equipment (assets) while helping prevent unplanned downtown. Additional physical I/O points are available using Expansion IO modules WEB-O9056H and WEB-O3022H.
EXPANSION IO
Expansion IO can be directly connected to the CIPer Model 30 controller or remotely mounted up to 100 ft away. The CIPer Model 30 supports up to 8 Expansion IO modules (WEB-O9056H and WEB-O3022H). The WEB-O9056H module is a large Expansion module that adds 20 additional I/O points, and the WEB-O3022H module is a small Expansion module that adds 7 additional I/O points. You can mix the small WEB-O3022H and the large WEB-O9056H in any combination to meet specific project I/O requirements.

The Expansion IO modules feature removable terminal blocks, Hand-Off-Auto switches, and indicator LEDs. They can be powered by the CIPer Model 30 controller.

ORDERING PART NUMBERS

MODEL WEB-C3036EPUBNH
WEB-C3036EPVBNH
FOC-EDGE-CONV
WEB-O9056H WEB-O3022H

DESCRIPTION
CIPer IP Unitary Controller, Niagara N4 license for BACnet, 150 Points, 3 Devices, SMA included
CIPer IP VAV Controller, Niagara N4 license for BACnet, 150 Points, 3 Devices, SMA included
Software license conversion to BACnet, Modbus, 100 Points, 3 devices, SMA included
CIPer IP Large Expansion Module, 20 I/O Points (9-UI, 6-BO, 5-UIO)
CIPer IP Small Expansion Module, 7 I/O Points (3-UI, 2-BO, 2-UIO)

EXPANDABLE LICENSE UPGRADE

PIN-EDGE-UPG

Upgrade existing CIPer Model 30 to expandable license for 100 points and 5 devices. SMA required and sold separately.

PIN-DEV-UP-1

1 Device & 50 Point Upgrade. Only available with expandable license.

PIN-DEV-UP-2

2 Device & 100 Point Upgrade. Only available with expandable license.

SMA-0002-xYR

Software Maintenance Agreement ­ available in 1,3, or 5-year increments.

CIPer Model 30 controller WEB-O9056H WEB-O3022H

CONTROLLER PART NUMBERS DESCRIPTION
WEB - C 3 0 3 6 E P U/V B N H
BRAND IDENTIFIER CONTROLLER ANALOG INPUT

HAND OFF AUTO NO ACTUATOR

DIGITAL INPUT ANALOG OUTPUT DIGITAL OUTPUT

BACNET
U - UNITARY & V- VAV PROGRAMMABLE ETHERNET

FEATURES AND HIGHLIGHTS

CONTROLLER
· Full Niagara 4 stack with 12 points of onboard I/O expandable up to 172 channels (including 9 monitored Hand-Off-Auto).
· 1Gbps 4-Port IP switch integrates demanding IP peripheral devices (like color cameras) 1000 times faster than serial MSTP.
· Full Niagara N4 license includes,
· 150 points (including data sharing points from the third-party BACnet devices) and 3 devices.
· The CIPer Model 30 supports up to 8 Expansion IO modules.
· Rapid Spanning Tree Protocol (IEEE 802.1w) supports 120 controllers on a daisy chain bus with fewer home runs for faster and lower cost wiring.

· Supports Star network topology.
· Spyder program and Venom conversion application standard.
· BACnet B-BC listed product.
· The CIPer Model 30 controller features a SylkTM bus interface that facilitates the connection of room sensor, SylkTM actuator, and display devices (e.g. the TR40 and TR42 series).
· Direct supervisor connectivity (Cloud or on-premise); simplifying system architecture and reducing program ming, commissioning & installation time.
· Niagara 4 Framework eliminates the extra cost, proprietary software, and tools.

· Up to 40 controllers can be connected in a ring or loop, to provide high resilience to network failure.

· SSL encrypted communications (FOXS PKI Certificate) protect the facility's expensive assets and infrastructure with

world-class cyber-security.
· FIPS 140-2 Level 1 compliance for critical high-risk facilities.
· Industry-standard TCP/IP connectivity, enabling the use of CAT5 or CAT6 Ethernet cables.
· 16-bit A/D conversion resolution for accurate measurement.
· VAV model includes an on-board airflow sensor.
· Live "real-time" programming; no time-consuming downloads.
· Solid State Relay (SSR) outputs reduce the need for external relays.
· Ready to use open-protocol Niagara 4 wire-sheet, alarming, history, schedules, web server, HTML graphics, standard tools and palettes, pre-configured common application macro library, analytic points, and Haystack Tagging.

EXPANSION IO
· Plug-and-play functionality for each installation and maintenance.
· All wiring connections are made to removable terminal blocks to simplify device installation and replacement.
· Wide range of supported sensors such as 20 KNTC, PT1000, and other resistive sensors.
· 16-bit A/D conversion resolution for accurate measurement.

· Indication LEDs for all Digital and Analog Outputs (DO & AO).
· HOA (Hand-Off-Auto) switches on DOs and AOs. HOA is configurable and can be monitored.
· Compact size for small installation housings.
· Field configuration and programming for Expansion IO input and output functions can be performed using the

CIPer Model 30 programming tool.
· The CIPer Model 30 supports up to 8 Expansion IO modules (WEB-O9056H and WEB-O3022H).

CIPer Model 30 and Expansion IO - Product Data Sheet | www.honeywell.com | 2

DIMENSIONS
Fig. 1 Different views of CIPer Model 30 controller

Fig. 2 WEB-O3022H

Fig. 3 WEB-O9056H

Fig. 4 Dimensional view of stacked Controller and Expansion IO modules CIPer Model 30 and Expansion IO - Product Data Sheet | www.honeywell.com | 3

SYSTEM OVERVIEW
CIPer Model 30 and Expansion IO - Product Data Sheet | www.honeywell.com | 4

PRODUCT SPECIFICATION

HARDWARE SPECIFICATION

MRAM

512 KB

RAM

1 GB

FLASH RAM

4 GB

CPU

Cortex A9 32-bit processor 1 GHz, Cortex-M4 227 MHz

Operating system

QNX based

Real-Time clock timekeeping accuracy

24-hour, 365-day, multi-year calendar including the day of week and configuration for automatic daylight savings time adjustment to occur at 2:00 a.m. local time on configured start and stop dates. Minimum 48 hours backup.

Power failure memory backup

24-hours at 32 °F to 100 °F (0 °C to 38 °C), 22-hours at 100 °F to 122 °F (38 °C to 50 °C)

Time accuracy

±1 minute per month at 77 °F (25 °C)

ELECTRICAL

Rated input voltage

24 VAC (20 to 30 VAC) 50/60 Hz

Rated impulse voltage 330 VAC for Category I (SELV)

Rated output voltage 20 to 30 VAC @ 50/60 Hz

Rated output type

Solid-State Relay, 1.5 A Continuous, 3.5 A inrush for 100 ms.

CIPer Model 30 Controller

100 VA maximum for controller and all connected loads 50 VA maximum for controller only load

Power consumption* WEB-O9056H

207 VA maximum for I/O module with all connected loads 35 VA maximum for I/O module without any load

WEB-O3022H

87 VA maximum for I/O module with all connected loads 15 VA maximum for I/O module without any load

* Power consumption is based on the sum of the VA rating for each controller and should not exceed 100 VA. In case it exceeds 100 VA, use a separate transformer to power up the modules.

OPERATING ENVIRONMENT

Ambient temperature* - 4 °F to 131 °F (-20 °C to 55 °C)

Storage temperature - 4 °F to 150 °F (-20 °C to 65 °C)

Humidity

5% to 95% RH non-condensing

Protection

IP20

* When utilizing differential pressure transducer, operating temperature ambient rating: 32 °F to 122 °F (0 °C to 50 °C).

DIFFERENTIAL PRESSURE SENSOR (VAV MODEL)

Media type

Air, N2, O2 (non-condensing)

Media temperature

32 °F to 122 °F (0 °C to 55 °C)

Pressure range

WEB-C3036EPVBNH : ±2" WC (±500 Pa) Expansion IO : ±2" WC (±374 Pa)

SUPPORTED SYLK DEVICES

Wall modules sensors

TR40, TR40-H, TR40-CO2, TR40-H-CO2, TR42, TR42-H, TR42-CO2, TR42-H-CO2, TR71, TR71-H, TR75, TR75-H, TR120, TR120-H

Sensors

C7400S SylkTM Sensor

Sylk Actuator

MS3103, MS3105, MS4103, MS4105, MS7403, MS7405, MS7503, MS7505, MS8103, MS8105 spring return Direct Coupled Actuators (DCA) are used within heating, ventilating, and air-conditioning (HVAC) systems. They can drive a variety of quarter-turn; final control elements requiring spring return fail-safe operation.

CONTROLLER AND EXPANSION IO UNIVERSAL INPUT/OUTPUT DETAILS

CONTROLLER

CONTROLLER TYPE

UI

WEB-C3036EPUBNH

Unitary

3

WEB-C3036EPVBNH

VAV

3

WEB-O3022H

IO module

3

WEB-O9056H

IO module

9

UIO

UIO

3

6

3

6

2

2

5

6

CIPer Model 30 and Expansion IO - Product Data Sheet | www.honeywell.com | 5

INPUT/OUTPUT SPECIFICATION

INPUTS AND OUTPUTS

UNIVERSAL INPUTS (UI)

UNIVERSAL INPUT/OUTPUT (UIO) DIGITAL OUTPUTS (DO)

Function

Voltage, current, resistive or digital input

Voltage, current, resistive or digital input, or analogue (voltage/current) output

Direct (on/off); Slow PWM

Resolution

16 bit (65536 steps)

NA

Pulse inputs

Frequency: 100 Hz max, minimum duty cycle: 5 mS ON / 5 mS OFF

NA

Voltage Input

Input range: 0 to 10 VDC, Input resistance: 189 k, Accuracy: 5% of full-scale (i.e. As per supply voltage (20 - 30 VAC)

±50 mV

Output Type solid state relays.

Current Input

Input range: 0 to 20 mA, Current source: Internal (loop power) or external PSU, Input resistance: 500 .w, Accuracy: ±0.5% of full-scale (i.e. 100 A)

1.5 A continuous, 3.5 A (100 ms inrush)

Resistive Resistance Input range: 0 to 300 k, Accuracy: Not specified, Bridge resistor: 10

Input

k, Bridge supply: 3.3 V

Digital Input

Voltage (open circuit): 3.3 V, Wetting current: 330 A (3.3 V / 10 k)

Voltage mode Range: 0 to 10 VDC (source 10 mA max,

NA

Analogue Output

sink 1 mA max, load 1kW)

NA

Accuracy: ±0.5% of full-scale (i.e. 50 mV)

Current mode

Range: 0 to 20 mA (load 550 W)

Accuracy: ±1% of full-scale (i.e. ±200 A)

Slow PWM Mode

NA

Duty cycle: 0.1 to 3276.7s (in 0.1s increments) Total cycle: 0.1 to 3276.7s (in 0.1s increments)

UNIVERSAL INPUTS SPECIFICATIONS FOR EXPANSION IO

INPUT TYPE

SENSOR TYPE

Room/Zone Discharge Air Outdoor Air Temperature

20K ohm NTC

C7031G

Outdoor Air Temperature

C7041F

PT1000 (IEC751 3850)

TR23 Setpoint Potentiometer

500 Ohm to 10,500 Ohm

Resistive Input

Generic

Voltage Input

Transducer, Controller

Discrete Input

Dry Contact closure

OPERATING RANGE
-40 °F to 199 °F ( -40 °C to 97.77 °C)
-40 °F to 120 °F (-40 °C to 49 °C) -40 °F to 250 °F (-40 °C to 121 °C) -40 °F to 199 °F (-40 °C to 93 °C) 50 °F to 90 °F (10 °C to 32 °C) 100 Ohms to 100K Ohms 0 - 10 VDC OpenCircuit  3000 Ohms ClosedCircuit < 3000 Ohms

CIPer Model 30 and Expansion IO - Product Data Sheet | www.honeywell.com | 6

STANDARDS AND APPROVALS
· UL/CUL (E87741) listed under UL 60730-1 and CSA E60730-1, UL 60730-2-9:2010.
· Meets FCC Part 15, Subpart B:2017, Class B (radiated emissions) requirements.
· Meets Canada ICES-003:2016. · EMC Directive: 2014/30/EU. Standards Applied:
· EN 61000-6:2005 · EN 61000-6-3:2007 + A1 · EN 60730-1: 2011, EN 60730-2-9: 2010 · RoHS Directive: 2011/65/EU. Standards Applied: · EN 50581: 2012

CONFORMANCE STATEMENT
This digital apparatus complies with CAN ICES-3 (B)/ NMB-3 (B).
FCC NOTICE
This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions:

· This device may not cause harmful interference, and
· This device must accept any interference received, including interference that may cause undesired operation.

APPLICABLE TECHNICAL LITERATURE

TITLE

REFERENCE

CIPer Model 30 Installation Instruction 31-00183

CIPer Model 30 System

31-00207

Engineering User Guide

CIPer Model 30 Software

NA

Release Bulletin

SAFETY INFORMATION AS PER EN60730-1
The Open System is intended for residential, commercial, and light-industrial environments. The Open System is an independently mounted electronic control system with fixed wiring.

The CIPer 30 controllers (WEB-C3036EPUBNH and WEB-C3036EPVBNH) and Expansion IO (WEB-O9056H and WEB-O3022H) are suitable for mounting in the fuse boxes conforming with standard DIN43880, and having a slot height of max. 1.77 inches (45 mm).

It is suitable for panel rail mounting on 1.38 inches (35 mm) standard panel rail (both horizontal and vertical rail mounting possible).

Safety information as per EN-60730-1

PARAMETER Electric Shock Protection
Pollution Degree
Installation Overvoltage Category Rated Impulse Voltage Automatic Action Software Class
Purpose of control
Enclosure degree of protection
Ball-pressure Test Temperature
Electromagnetic Interference System
Transformer

DESCRIPTION
PELV
Pollution Degree 2, suitable for use in industrial environments. Class 3 24 V - powered controls: Category I 330 VAC for Category I (SELV) Type 1 Class A Operating Control, Open Energy Management Equipment.
IP20
> 167 °F (75 °C) for all housing and plastic parts. > 257 °F (125 °C) in the case of devices applied with voltage-carrying parts, connectors, and terminals. Tested at 230 VAC, with the Modules in normal condition. Europe: safety isolating transformers according to IEC61558-2-6. U.S.A. and Canada: NEC Class-2 transformers.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any liability, cost, or damages, including attorneys' fees, arising out of, or resulting from, any modification to the literature by you.

Honeywell Building Technologies

1985 Douglas Drive North

Golden VAlley, MN 55422 customer.honeywell.com buildings.honeywell.com

@U.S. Registered Trademark © 2021 Honeywell International Inc. 31-00236EFS-03 | Rev. 08-21



References

Adobe PDF Library 15.0 , Alerton Technical Communications