Carrier 45VML007---3 VRF Indoor Unit - Low Static Duct
Submittal Data
Unit Information
Job Name:
Tag:
Location:
Indoor Unit Model
45VML007---3
Performance
Specification | Value | Unit |
---|---|---|
Cooling Rated Capacity | 7,000 | Btu/h |
Heating Rated Capacity | 8,000 | Btu/h |
Airflow (H/M/L) | 325/250/175 | CFM |
Sound Pressure (H/M/L) | 32/27.5/25 | dBA |
Electrical
Specification | Value | Unit |
---|---|---|
Power Supply | 208-230/1/60 | V/Ph/Hz |
Fan Motor Rated Motor (Output) | 20 | W |
Minimum Circuit Amps (MCA) | 1.13 | A |
Maximum Overcurrent Protection | 15.0 | A |
Motor Type | DC |
Physical Data
Specification | Value | Unit |
---|---|---|
Pipe Connection Size - Liquid | 1/4 | in. |
Pipe Connection Size - Suction | 1/2 | in. |
Pipe Connection Size - Drain | 1 | in. |
External Static Pressure (ESP) | 0.04(0-0.2) | in. wg |
Refrigerant | R-454B | |
Unit Width | 21-5/8 | in. |
Unit Height | 7-13/16 | in. |
Unit Depth | 18-7/8 | in. |
Net Unit Weight | 27.6 | lb |
Standard Features
- Rear Return Air Opening is standard and bottom return is optional.
- Three Fan Speeds - High, Medium, and Low.
- Knockout for Outside Air.
- Built-in Drain Pump from factory.
- Built in EEV (Electronic Expansion Valve) for installation ease.
- Internally installed A2L Refrigerant Leak Sensor.
Accessories
- Wireless Remote Controller 45VM900001
- Wired Remote Controller - Non-Prog. 45VM900002
Dimensional Drawing
The unit dimensions are provided in inches.
External dimensions, air outlet size, and size of fresh air outlet:
Size of return air inlet (back return air mode):
Dimension of pipe and water pipe:
Size of return air inlet (bottom return air mode), and the distance between the lugs:
Capacity (kBTU/h) | A | B | C | D | E | F | G | H | I |
---|---|---|---|---|---|---|---|---|---|
07 | 27-9/16 (700) | 20-7/8 (530) | 23-3/4 (605) | 8-7/8 (200) | 4-5/16 (109.5) | 24-3/8 (619) | 29-5/16 (745) | 3/4-16 UNF | 7/16-20 UNF |
Note: All dimensions are shown in inches.
Edition Date: 04/25
Printed in U.S.A.
Form No: 45VML007--3-C-1SD
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.