Carrier 45VMV054A---3 VRF Indoor Unit - Vertical AHU
Submittal Data
Job Name: _________________________ Location: _________________________ Tag: _________________________
Standard Features
- Dual Drainage Spouts
- Three Fan Speeds: High, Medium, and Low
- Multipose installation in vertical, horizontal left, horizontal right, and downflow configurations
- DC Fan Motor
- Built-in EXV (Electronic Expansion Valve) for Installation Ease
- Removable Front Panel for Easy Access
- Configurable for downflow operation
- Internal A2L Refrigerant Sensor
Specifications
Indoor Unit Model | 45VMV054A---3 | |
---|---|---|
PERFORMANCE | ||
Cooling Rated Capacity | Btu/h | 54,000 |
Heating Rated Capacity | Btu/h | 60,000 |
Airflow (H / M / L) 4 | CFM | 1808 / 1718 / 1627 / 1537 / 1447 / 1356 / 1266 |
Sound Pressure (H / M / L) 6 | dBA | 39 / 36 / 34 / 31.5 / 29 / 25 / 22 |
External Static Pressure 5 | in (wg) | 0.2 (0-0.8) |
ELECTRICAL | ||
Power Supply | V/Ph/Hz | 208-230/1/60 |
Motor Type | DC | |
Indoor Unit Fan Motor Rated Motor Output | W | 750 |
Minimum Circuit Amps | A | 5.65 |
Maximum Overcurrent Protection | A | 15 |
Accessories (Optional)
- Wireless Remote Controller: 45VM900001
- Wired Remote Controller - Non-Prog.: 45VM900002
- 5 kW Heat Strip: 45VM910005
- 7.5 kW Heat Strip: 45VM910007
- 10 kW Heat Strip: 45VM910010
- 15 kW Heat Strip: 45VM910015
- 20 kW Heat Strip: 45VM910020
Physical Data
Pipe Connection Size - Liquid | in. | 3/8 (OD) |
Pipe Connection Size - Suction | in. | 3/4 (OD) |
Pipe Connection Size - Drain | in. | 1 (OD) |
Refrigerant | R-454B | |
Unit Width | in. | 22-1/8 |
Unit Height | in. | 54-1/2 |
Unit Depth | in. | 24 |
Net Weight | lb | 157 |
Notes
- Indoor temperature 80°FDB, 67°F_WB; outdoor temperature 95°FDB, 75°F_WB; equivalent refrigerant piping length 295-1/4 in. with zero level difference.
- Indoor temperature 70°FDB, 60°F_WB; outdoor temperature 47°FDB, 43°F_WB; equivalent refrigerant piping length 295-1/4 in. with zero level difference.
- AHU adopts a brand-new special-shaped heat exchanger with different number of rows and different Tube pitch at different positions.
- Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
- Stable operation external static pressure range. (Note: setting external static pressure outside the unit's optimal static pressure range may lead to higher noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit's installation manual.)
- Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 59-1/16 in. below the unit in an anechoic chamber.
- The dimension is only the body size, excluding the size of the installation lug, connecting copper pipe, etc. For detailed dimensions, please refer to the installation manual.
Dimensional Drawing - Indoor Unit Vertical AHU 45VMV054A---3
Note: 25" clearance is required in the front of the unit for filter and coil maintenance.
Description of Diagram: The diagram shows a vertical air handler unit with various connection points and dimensions. Key features indicated include:
- Electrical connections exiting top or right side.
- High voltage connection knock-outs (7/8", 1-3/8", 1-3/4" diameter).
- Wire group connections for thermostat and outdoor unit.
- EHK knock-out hole.
- Vapor line connection (copper, braze).
- Liquid line connection (copper, braze).
- Auxiliary drain connections (3/4" Female pipe thread, NPT) - two indicated.
- Primary drain connection (3/4" Female pipe thread, NPT).
- Supply air outlet.
- Flanges provided for field installation.
- Overall dimensions: Width 22-1/8" (560), Depth 24" (610), Height 54-1/2" (1385).
- The unit is shown in an upflow configuration, but can be installed in upflow, downflow, horizontal right, or horizontal left air supply configurations.
© 2025 Carrier. All rights reserved.
Edition Date: 04/25 Printed in U.S.A.
Form No: 45VMV054A--3-C-01SD Replaces: New
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.