Carrier 45VMV054A---3 VRF Indoor Unit - Vertical AHU

Submittal Data

Job Name: _________________________ Location: _________________________ Tag: _________________________

Standard Features

Specifications

Indoor Unit Model45VMV054A---3
PERFORMANCE
Cooling Rated CapacityBtu/h54,000
Heating Rated CapacityBtu/h60,000
Airflow (H / M / L) 4CFM1808 / 1718 / 1627 / 1537 / 1447 / 1356 / 1266
Sound Pressure (H / M / L) 6dBA39 / 36 / 34 / 31.5 / 29 / 25 / 22
External Static Pressure 5in (wg)0.2 (0-0.8)
ELECTRICAL
Power SupplyV/Ph/Hz208-230/1/60
Motor TypeDC
Indoor Unit Fan Motor Rated Motor OutputW750
Minimum Circuit AmpsA5.65
Maximum Overcurrent ProtectionA15

Accessories (Optional)

Physical Data

Pipe Connection Size - Liquidin.3/8 (OD)
Pipe Connection Size - Suctionin.3/4 (OD)
Pipe Connection Size - Drainin.1 (OD)
RefrigerantR-454B
Unit Widthin.22-1/8
Unit Heightin.54-1/2
Unit Depthin.24
Net Weightlb157

Notes

  1. Indoor temperature 80°FDB, 67°F_WB; outdoor temperature 95°FDB, 75°F_WB; equivalent refrigerant piping length 295-1/4 in. with zero level difference.
  2. Indoor temperature 70°FDB, 60°F_WB; outdoor temperature 47°FDB, 43°F_WB; equivalent refrigerant piping length 295-1/4 in. with zero level difference.
  3. AHU adopts a brand-new special-shaped heat exchanger with different number of rows and different Tube pitch at different positions.
  4. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
  5. Stable operation external static pressure range. (Note: setting external static pressure outside the unit's optimal static pressure range may lead to higher noise levels and lower airflow rate. For the optimal external static pressure range refer to the unit's installation manual.)
  6. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 59-1/16 in. below the unit in an anechoic chamber.
  7. The dimension is only the body size, excluding the size of the installation lug, connecting copper pipe, etc. For detailed dimensions, please refer to the installation manual.

Dimensional Drawing - Indoor Unit Vertical AHU 45VMV054A---3

Note: 25" clearance is required in the front of the unit for filter and coil maintenance.

Description of Diagram: The diagram shows a vertical air handler unit with various connection points and dimensions. Key features indicated include:

© 2025 Carrier. All rights reserved.

Edition Date: 04/25 Printed in U.S.A.

Form No: 45VMV054A--3-C-01SD Replaces: New

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

PDF preview unavailable. Download the PDF instead.

45VMV054---3-C-1SD Acrobat Distiller 25.0 (Windows)

Related Documents

Preview Carrier 45VMV036A---3 Vertical AHU VRF Indoor Unit Submittal Data
Submittal data for the Carrier 45VMV036A---3 Vertical AHU VRF Indoor Unit, including performance specifications, physical data, standard features, and dimensional drawings.
Preview Carrier 45VMV024A---3 Vertical AHU VRF Indoor Unit Submittal Data
Submittal data for the Carrier 45VMV024A---3 Vertical AHU VRF Indoor Unit, including performance specifications, physical data, standard features, and dimensional drawings.
Preview Carrier 40VMV054A--3 Vertical AHU VRF Indoor Unit Submittal Data
Submittal data for the Carrier 40VMV054A--3 Vertical AHU VRF Indoor Unit, including performance specifications, physical data, electrical information, and optional accessories.
Preview Carrier 45VMV048A---3 Vertical AHU Submittal Data
Submittal data for the Carrier 45VMV048A---3 Vertical Air Handler Unit (AHU), including performance specifications, electrical data, physical dimensions, standard features, and optional accessories.
Preview Carrier 39M Aero® Indoor and Weathertight Outdoor Air Handlers Product Data
This document provides detailed product data for the Carrier 39M Aero® series of Indoor and Weathertight Outdoor Air Handlers, covering specifications, features, benefits, application data, and fan selection criteria for units ranging from 1,500 to 60,500 Nominal cfm.
Preview Carrier 45VML007---3 Low Static Duct Indoor Unit Submittal Data
Submittal data for the Carrier 45VML007---3 Low Static Duct Indoor Unit, including performance specifications, physical data, and dimensional drawings.
Preview Carrier 39CZST375 Air Handling Unit Technical Data Sheet
Technical data sheet for the Carrier 39CZST375 Air Handling Unit, detailing its specifications for ventilation, heating, cooling, humidification, dehumidification, and filtration in commercial and industrial environments. Features include energy efficiency and compliance with EN 13053 and EN 1886 standards.
Preview Carrier 45MBAAQ Split-Type Air Handler Indoor Unit Ductless System Owner's Manual
Comprehensive owner's manual for the Carrier 45MBAAQ Split-Type Air Handler Indoor Unit Ductless System (18K - 60K), covering safety, general information, controls, operation, maintenance, troubleshooting, and wiring diagrams.