Robertshaw 9600 Digital Programmable Thermostat

Model: 9600

Type: 5 - 2 Day Programmable, 1 Heat / 1 Cool

Document Type: User's Manual, Quick Start, Installation and Programming

Installation Guide

IMPORTANT SAFETY INFORMATION WARNING:

  • Always turn off power at the main power source by unscrewing the fuse or switching the circuit breaker to the off position before installing, removing, cleaning, or servicing the thermostat.
  • Read all of the information in this manual before installing or programming this thermostat.
  • This is a 24V AC low voltage thermostat. Do not install on voltages higher than 30V AC.
  • All wiring must conform to local and national building and electrical codes and ordinances.
  • Do not short (jumper) across terminals on the gas valve or at the system control to test installation. This will damage the thermostat and void the warranty.

Features

  • Four setpoints for weekday programming—two setpoints for weekend comfort.
  • Two AA ENERGIZER brand batteries retain program memory even during power outages.
  • Low battery indicator.
  • Fahrenheit/Celsius display option.
  • Programmable from 45°F (4°C) to 90°F (32°C).
  • Accuracy within ± 1 degree.
  • Adjustable temperature differential: 1-3 degrees.
  • Maintains summer and winter programming.
  • Low temperature freeze protection: While in heat mode, the thermostat will mechanically turn on heat if the temperature drops to 40°F (4°C)—even if batteries are missing or drained.
  • Automatic heating shutdown if temperature exceeds 90°F (32°C).

Replacing Existing Thermostat

  1. Turn off power to the heating and cooling system.
  2. Remove the cover of the old thermostat to expose wires. Do not disconnect wires. [See Figure 1: Diagram showing how to remove the old thermostat cover to expose wires.]
  3. Label wires per Table 1.

Table 1: Wire Labels

Old Label New Label Description
M, 4, RH, R5 or R RH Heat Transformer, hot side
V or RC RC Cooling Transformer, hot side
Y or Y6 Y Cooling control
H, W or 4 W Heating control
For G G Fan control relay
C* Y or None Either cooling control or common side of transformer

*NOTE: ON SOME OLDER MODELS, THE C TERMINAL CAN BE EITHER THE COOLING CONTROL OR THE COMMON SIDE OF THE TRANSFORMER. CHECK FURNACE WIRING DIAGRAM TO VERIFY C TERMINAL. IF IT IS THE COMMON SIDE OF THE TRANSFORMER, CAP THE WIRE AND TUCK INTO THE WALL. IF IT IS THE COOLING CONTROL, CONNECT TO THE Y TERMINAL.

  1. After labeling wires, remove wires from terminals.
  2. Remove existing thermostat base from wall.
  3. Refer to the following section for instructions on how to install the thermostat.

Installing Item 9600 Thermostat

NOTE: For NEW INSTALLATIONS, MOUNT THERMOSTAT ON AN INSIDE WALL, 4-5 FEET ABOVE THE FLOOR. DO NOT INSTALL BEHIND A DOOR, IN A CORNER, NEAR AIR VENTS, IN DIRECT SUNLIGHT, OR NEAR ANY HEAT OR STEAM GENERATING FIXTURES. INSTALLATION AT THESE PLACES WILL AFFECT THERMOSTAT OPERATION.

  1. Turn power off to the heating and cooling systems.
  2. Place the COOL-OFF-HEAT switch in the OFF position. [Diagram shows COOL-OFF-HEAT switch in OFF position.]
  3. Place the AUTO-ON switch into the AUTO position. [Diagram shows AUTO-ON switch in AUTO position.]
  4. Remove the cover using a coin or screwdriver. [Diagram shows thermostat cover being removed.]
  5. Place thermostat against the wall at the desired location. Make sure wires will feed through the opening on the base of the thermostat. [Diagram shows thermostat base against wall with wires feeding through.]
  6. Mark placement of mounting holes (see Figure 3). Set base aside. [Diagram shows mounting hole locations on the thermostat base.]
  7. Drill the marked holes using a 3/16" drill bit. Note: Enclosed plastic anchors do not require a drilled hole for drywall.
  8. Tap plastic anchors into the wall.
  9. Align base with plastic anchors and feed wires through opening (see Figure 4). [Diagram shows base aligned with anchors and wires fed through.]
  10. Secure base to wall with supplied screws.
  11. Connect wires to terminal strip. Refer to wiring diagrams on other side of this sheet. Make sure wire connections are secure.
  12. Place fan option switch into either the ELEC or GAS position depending on the type of furnace. Refer to Figure 5. [Diagram shows the fan option switch labeled ELEC and GAS.]
  13. Install two AA ENERGIZER brand batteries or equivalent into the battery compartment. Be sure to match positive (+) ends of batteries with positive (+) battery terminals in the battery compartment. The display will show as follows: [Diagram shows two AA batteries with positive and negative terminals.]
  14. Replace cover on thermostat by snapping into place.
  15. Turn on power to system. Test thermostat as described in the section "To Test Thermostat".

Programming Guide

Set Time of Day, Day of Week, Temperature Differential

  1. Press and hold SET. Press PROG/MAN. Release simultaneously. [Diagram shows pressing SET and PROG/MAN buttons.]
  2. Press or to change time of day. [Diagram shows UP and DOWN arrows.]
  3. Press SET. [Diagram shows pressing SET button.]
  4. Press or to change day of week. [Diagram shows UP and DOWN arrows and a list of days: 1=MO, 2=TU, 3=WE, 4=TH, 5=FR, 6=SA, 7=SU.]
  5. Press SET. [Diagram shows pressing SET button.]
  6. Press or to change temperature differential. [Diagram shows UP and DOWN arrows.]

*THE TEMPERATURE DIFFERENTIAL IS FACTORY PRESET AT 1°. THIS MEANS THAT WHENEVER THE ROOM TEMPERATURE CHANGES BY ONE FULL DEGREE FROM THE TEMPERATURE SETTING, THE SYSTEM WILL TURN ON. IF THE SYSTEM TURNS ON TOO OFTEN, INCREASE THE TEMPERATURE DIFFERENTIAL.

Changing Fahrenheit (F) to Celsius (C)

Press and hold SET. Press . Release both simultaneously. [Diagram shows pressing SET and UP arrow buttons.]

Setting Daily Programming

  1. Place COOL-OFF-HEAT switch in COOL position. [Diagram shows COOL-OFF-HEAT switch in COOL position.]
  2. Press SET. [Diagram shows pressing SET button.]
  3. Press or to change MORN time. [Diagram shows UP and DOWN arrows.]
  4. Press SET. [Diagram shows pressing SET button.]
  5. Press or to change MORN temperature. [Diagram shows UP and DOWN arrows.]
  6. Repeat Steps 2-5 for DAY, EVE, and NITE.
  7. Shift COOL-OFF-HEAT switch to HEAT position. [Diagram shows COOL-OFF-HEAT switch in HEAT position.]
  8. Repeat steps 2-6 to program HEAT (winter) settings.

NOTE: BOTH SUMMER AND WINTER PROGRAMS USE THE SAME TIME SETTINGS.

Your thermostat is now programmed for summer and winter operation. It will follow the four settings (MORN, DAY, EVE, NITE) for weekday operation and two settings (MORN and NITE) for weekend operation. Adjust the program at any time by following the steps as outlined above.

Begin Programmed Operation

  1. Place AUTO-ON switch into AUTO. [Diagram shows AUTO-ON switch in AUTO position.]
  2. Place COOL-OFF-HEAT switch into COOL or HEAT depending on the season. [Diagram shows COOL-OFF-HEAT switch in COOL or HEAT position.]
  3. Press PROG/MAN button until indicator is in PROG position. [Diagram shows PROG/MAN button being pressed to select PROG mode.]

Temporary Program Override

To temporarily increase or decrease temperature: Press or . [Diagram shows UP and DOWN arrows.]

The thermostat will automatically return to the program at the next scheduled setting change.

Manual Operation

  1. Press PROG/MAN until indicator is in MAN position. [Diagram shows PROG/MAN button being pressed to select MAN mode.]
  2. Press or to adjust temperature settings. [Diagram shows UP and DOWN arrows.]

Reset

To reset the thermostat to factory preprogrammed conditions, press the RESET button located directly to the right of the display. [Diagram shows the thermostat display and the location of the RESET BUTTON.]

To Test Thermostat

WARNING: DO NOT SHORT (JUMPER) ACROSS TERMINALS OF GAS VALVE OR SYSTEM CONTROL TO TEST OPERATION. THIS WILL DAMAGE THE THERMOSTAT AND VOID YOUR WARRANTY.

CAUTION: DO NOT SWITCH SYSTEM TO COOL IF THE TEMPERATURE IS BELOW 50°F (10°C). THIS CAN DAMAGE THE AIR CONDITIONING SYSTEM AND CAUSE PERSONAL INJURY.

  1. Place the COOL-OFF-HEAT switch into the COOL position. [Diagram shows COOL-OFF-HEAT switch in COOL position.]
  2. Press the button until the temperature setting is at least 3 degrees below the room temperature. The air conditioning system should turn on within a few seconds.
  3. NOTE: THERE IS A BUILT IN 5-MINUTE DELAY ON BREAK FOR COMPRESSOR PROTECTION. A SECOND ATTEMPT TO TURN ON THE AIR CONDITIONING WILL RESULT IN A 5-MINUTE DELAY IN COMPRESSOR ACTIVATION.
  4. Put the COOL-OFF-HEAT switch into the OFF position. The air conditioning system should turn off. The fan may continue to run for a short period of time. [Diagram shows COOL-OFF-HEAT switch in OFF position.]
  5. Put the COOL-OFF-HEAT switch into the HEAT position. [Diagram shows COOL-OFF-HEAT switch in HEAT position.]
  6. Press the button until the temperature setting is at least 3 degrees above room temperature. The heating system should turn on. The fan may not turn on immediately, depending on the fan delay built into the furnace.
  7. Put the COOL-OFF-HEAT switch into the OFF position. The heating system should turn off. Once again, the fan may have a delay. [Diagram shows COOL-OFF-HEAT switch in OFF position.]
  8. Put the AUTO-ON switch to the ON position. The blower fan should turn on. [Diagram shows AUTO-ON switch in ON position.]
  9. Put the AUTO-ON switch to the AUTO position. The blower fan should turn off. [Diagram shows AUTO-ON switch in AUTO position.]

Troubleshooting

Symptom Remedy
Thermostat does not turn on system. Check wiring. (See INSTALLATION)
Check fuse. Replace with 2 amp Slo-Blo fuse if fuse has opened.
Thermostat turns on and off too frequently. Increase temperature differential. (See PROGRAMMING)
Display is blank, flashing or constant LO BAT. Replace batteries.
Weekend program follows four adjustment settings. Verify that day of week is set correctly. (See PROGRAMMING)
System fan does not operate properly. Move fan option switch to either gas or electric, to match system. (See INSTALLATION)
Time shown on display is not the current time of day. Change time of day setting. (See PROGRAMMING)
Thermostat does not follow program. Thermostat in MANUAL mode. (See PROGRAMMING).
Thermostat may not have been programmed in HEAT or COOL position. Verify program.
Check AM/PM indicators at time of day and programmed time changes. (See PROGRAMMING)
Verify program and day of week are correct. (See PROGRAMMING)

If problems with thermostat cannot be solved, call:

Technical Support: (800) 445-8299
Monday-Friday 7:30-5:30 CST
For after hours service, a 24-hour automated help line is available.

For warranty returns, send thermostat, shipping prepaid to:

MAPLE CHASE COMPANY
Warranty Department
2820 Thatcher Road
Downers Grove, IL 60515

Wiring Diagrams

The following is just a sample of the most common types of HVAC systems. Refer to your system's installation manual for wiring information.

HEAT/COOL 4-WIRE SINGLE TRANSFORMER

Diagram shows connections from a transformer (120VAC/24VAC) to thermostat terminals RH, RC, W (Heating Control), Y (Cooling Control), and G (Fan Control). A factory-installed jumper is noted between RH and R.

HEAT ONLY 3-WIRE SINGLE TRANSFORMER

Diagram shows connections from a transformer (120VAC/24VAC) to thermostat terminals RH, W (Heating Control), and G (Fan Control). A factory-installed jumper is noted between RH and R.

HEAT ONLY 2-WIRE SINGLE TRANSFORMER

Diagram shows connections from a transformer (120VAC/24VAC) to thermostat terminals RH and W (Heating Control). A note indicates to remove the factory-installed jumper.

COOL ONLY 3-WIRE SINGLE TRANSFORMER

Diagram shows connections from a transformer (120VAC/24VAC) to thermostat terminals RC, Y (Cooling Control), and G (Fan Control). A note indicates to remove the factory-installed jumper.

HEAT/COOL 5-WIRE TWO TRANSFORMER

Diagram shows connections from two transformers (one for heating, one for cooling) to thermostat terminals RH, RC, W (Heating Control), Y (Cooling Control), and G (Fan Control). A note indicates to cut the center of the factory-installed jumper and bend it back. A caution states that both transformers must be in phase or damage to the equipment and thermostat may result.

FIVE-YEAR LIMITED WARRANTY

Maple Chase Company warrants to the original contractor installer or to the original consumer user, each new Robertshaw thermostat to be free from defects in materials and workmanship under normal use and service for a period of five (5) years from date of purchase. This warranty and our liability does not apply to batteries or the merchandise that has been damaged, caused by misuse, neglect, mishandling, alterations, improper installation, or use in a way other than in accordance with Maple Chase Company recommendations and instructions.

Maple Chase Company agrees to repair or replace at its option any thermostat under warranty provided it is returned within the warranty period, postage prepaid, with proof of the date of purchase. Cost of thermostat removal or reinstallation is not the responsibility of Maple Chase Company.

Repair or replacement as provided under this warranty is the exclusive remedy of the consumer. Maple Chase Company shall not be liable for any incidental or consequential damages for breach of any express or implied warranty on this product, or under any other theory of liability. Except to the extent prohibited by applicable law, any implied warranty of merchantability or fitness for a particular purpose on this product is limited to the duration of this warranty.

Some states do not allow the exclusion or limitation of incidental or consequential damages, or allow limitations on how long an implied warranty lasts, so the above limitations or exclusions may not apply to you. This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.

Maple Chase Company
2820 Thatcher Road
Downers Grove, Illinois 60515
United States of America

©2000 Maple Chase Company

PDF preview unavailable. Download the PDF instead.

User-Guide-Robertshaw-Thermostat-KWV Acrobat Distiller 5.0.5 for Macintosh

Related Documents

Preview Robertshaw 9600 Digital Programmable Thermostat User Manual
User's manual, quick start guide, installation, and programming instructions for the Robertshaw 9600 Digital Programmable Thermostat. Includes features, troubleshooting, wiring diagrams, and warranty information.
Preview Robertshaw RS9210 Programmable Thermostat Operation Manual
This operation manual provides detailed instructions for the Robertshaw RS9210 programmable thermostat, covering thermostat operation, quick reference, programming, installer setup, and terminal designations.
Preview Robertshaw RS9220 Programmable Thermostat Operation Manual
This manual provides detailed instructions for operating the Robertshaw RS9220 programmable thermostat, including setup, programming, and system settings.
Preview Robertshaw RS10420T Programmable WiFi Thermostat Installation Manual
This installation manual provides comprehensive instructions for the Robertshaw RS10420T Programmable WiFi Thermostat. It covers product features, application compatibility, wiring diagrams, technician setup procedures, programming options, and Wi-Fi connection. Learn how to install, configure, and operate your smart thermostat for optimal home climate control.
Preview Robertshaw RS10420T Programmable WiFi Thermostat - Multi-Stage HVAC Control
Explore the Robertshaw RS10420T, a versatile programmable WiFi thermostat designed for contractors and homeowners. This multi-stage unit offers advanced features like a large touchscreen, smartphone control via the Robertshaw app, and 7-day programmability for efficient HVAC management.
Preview Robertshaw Pro-Series Wall Thermostats: Simple, Powerful, Economical
A cross-reference guide for Robertshaw Pro-Series wall thermostats, detailing models RS8110, RS8210, RS9110, RS9110T, RS9210, RS9220, RS9320T, and RS10420T. Features include thermostat type, programming capabilities, display type, and compatibility with other brands like Honeywell, Braeburn, Emerson, and Aprilaire.
Preview Robertshaw RS8210 Thermostat Operation Manual
Comprehensive operation, programming, and installation guide for the Robertshaw RS8210 thermostat, detailing features, setup options, and terminal designations for HVAC systems.
Preview Robertshaw Pro-Series Wall Thermostats: Features and Model Comparison
Discover the Robertshaw Pro-Series wall thermostats, designed for simple, powerful, and economical heating and cooling control. This overview highlights key features, user-friendly design, easy installation, and provides a comprehensive model comparison chart for selecting the right thermostat for your project.