Rheem Residential 120V plugin Heat Pump Water Heater (Dedicated Circuit)
Use & Care Manual With Installation Instructions for the Installer
Introduction
The purpose of this manual is twofold: one, to provide the installer with the basic directions and recommendations for the proper installation and adjustment of the water heater; and two, for the owner-operator, to explain the features, operation, safety precautions, maintenance and troubleshooting of the water heater. This manual also includes a parts list.
It is imperative that all persons who are expected to install, operate or adjust this water heater read the instructions carefully so they may understand how to perform these operations. If you do not understand these instructions or any terms within it, seek professional advice.
Any questions regarding the operation, maintenance, service or warranty of this water heater should be directed to the seller from whom it was purchased. If additional information is required, refer to the section on "If you need service."
DO NOT destroy this manual. Please read carefully and keep in a safe place for future reference.
Recognize this symbol ⚠ as an indication of Important Safety Information!
© 2022 Rheem Sales Company Inc. AP21914 Rev 02
Important Safety Information
FOR YOUR RECORDS
Write the model and serial numbers here: # # You can find them on a label on the appliance.
Staple sales slip or cancelled check here. Proof of the original purchase date is needed to obtain service under the warranty.
READ THIS MANUAL
Inside you will find many helpful hints on how to use and maintain your water heater properly. Just a little preventive care on your part can save you a great deal of time and money over the life of your water heater.
You'll find many answers to common problems in the Before You Call For Service section. If you review our chart of Troubleshooting Tips first, you may not need to call for service at all.
READ THE SAFETY INFORMATION
Your safety and the safety of others are very important. There are many important safety messages in this manual and on your appliance. Always read and obey all safety messages.
This is the safety alert symbol ⚠. This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER", "WARNING", "CAUTION" or "NOTICE".
These words mean:
- ⚠ DANGER: An imminently hazardous situation that will result in death or serious injury.
- ⚠ WARNING: A potentially hazardous situation that could result in death or serious injury and/or damage to property.
- ⚠ CAUTION: A potentially hazardous situation that may result in minor or moderate injury.
- NOTICE: Attention is called to observe a specified procedure or maintain a specific condition.
Water Temperature Setting
Safety and energy conservation are factors to be considered when selecting the water temperature setting of the water heater. Water temperatures above 125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined on the label pictured below. This label is also located on the water heater near the thermistor access panel.
⚠ DANGER
A diagram shows a faucet with water flowing, labeled "HOT" and "BURN".
Water temperature over 125°F (52°C) can cause severe burns instantly or death from scalds. Children, disabled and elderly are at highest risk of being scalded. See instruction manual before setting temperature at water heater. Feel water before bathing or showering. Temperature limiting valves are available, see manual.
Temperature | Time To Produce a Serious Burn |
---|---|
120°F (49°C) | More than 5 minutes |
125°F (52°C) | 1½ to 2 minutes |
130°F (54°C) | About 30 seconds |
135°F (57°C) | About 10 seconds |
140°F (60°C) | Less than 5 seconds |
145°F (63°C) | Less than 3 seconds |
150°F (65°C) | About 1½ seconds |
155°F (68°C) | About 1 second |
Table courtesy of Shriners Burn Institute
The chart shown above may be used as a guide in determining the proper water temperature for your home.
⚠ DANGER: Households with small children, disabled, or elderly persons may require a 120°F (49°C) or lower thermostat setting to prevent contact with "HOT" water.
The temperature of the water in the heater is regulated by the water heater interface control. To comply with safety regulations the temperature was set at 120°F (49°C) before the water heater was shipped from the factory.
The illustration below shows the water temperature setting. Refer to the Operating Instructions in this manual for detailed instructions in how to adjust the water temperature.
A diagram shows the control panel with buttons like ON/OFF, MODE, NEXT, ENTER, SCROLL, ALARM, WiFi, and a display showing temperature and status.
NOTICE: Mixing valves are recommended for reducing point of use water temperature by mixing hot and cold water in branch water lines. It is recommended that a mixing valve complying with the Standard for Temperature Actuated Mixing Valves for Hot Water Distribution Systems, ASSE 1017 be installed. See page 16 for more details and contact a licensed plumber or the local plumbing authority for further information.
When used in demand response applications a thermostatic mixing valve conforming to ASSE 1017 shall be installed on the hot water supply line following all manufacturer installation instructions. See page 32 for additional installation information.
⚠ DANGER: Hotter water increases the potential for Hot Water SCALDS.
General Warnings
⚠ WARNING! For your safety, the information in this manual must be followed to minimize the risk of fire or explosion, electric shock, or to prevent property damage, personal injury, or loss of life.
Be sure to read and understand the entire Use and Care Manual before attempting to install or operate this water heater. It may save you time and cost. Pay particular attention to the Safety Instructions. Failure to follow these warnings could result in serious bodily injury or death. Should you have problems understanding the instructions in this manual, or have any questions, STOP, and get help from a qualified service technician, or the local electric utility.
For Installations in the State of California
California Law requires that all new and replacement water heaters, and all existing residential water heaters, must be braced, anchored, or strapped to resist falling or horizontal displacement due to earthquake motion. At a minimum, any water heater shall be secured in accordance with the California Plumbing Code, or modifications made thereto by a city, county, or city and county pursuant to Section 17958.5. Generic instructions for California titled "Guidelines for Earthquake Bracing Residential Water Heaters" can be obtained by:
- Writing the California, Department of General Services, Division of State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95814
- Calling (916) 445-8100
- Following web address: https://www.buildingincalifornia.com/wp-content/uploads/2014/02/waterheaterbracing_08-11-04.pdf
A diagram shows the water heater installed with earthquake bracing straps.
Safety Precautions
Have the installer show you the location of the circuit breaker and how to shut it off if necessary. Turn off the circuit breaker if the water heater has been subjected to overheating, fire, flood, physical damage or if the ECO (temperature limiting control) fails to shut off.
- Read this manual entirely before installing or operating the water heater.
- Use this appliance only for its intended purpose as described in this Use and Care Manual.
- Be sure your appliance is properly installed in accordance with local codes and the provided installation instructions.
- DO NOT attempt to repair or replace any part of your water heater unless it is specifically recommended in this manual. All other servicing should be referred to a qualified technician.
- DO NOT attempt to repair or replace the compressor, refrigerant, or any part associated with the sealed refrigerant system.
- DO NOT turn on the electrical supply or operate this water heater unless it is completely full of water.
⚠ WARNING! Disconnect all power to unit before starting maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
⚠ WARNING! FLAMMABLE CONTENTS UNDER PRESSURE. The compressor is not a serviceable part. The compressor wiring terminals may arc allowing pressurized refrigerant and oil to escape, ignite and cause serious bodily injury, severe burns or death.
READ AND FOLLOW THIS SAFETY INFORMATION CAREFULLY. SAVE THESE INSTRUCTIONS
Refrigerant
This Hybrid Water Heater is factory charged with an environmentally friendly, non-chlorinated refrigerant, R134A. This refrigerant has zero ozone depletion potential.
Installing the Water Heater
The location chosen for the water heater must take into consideration the following:
Local Installation Regulations
This water heater must be installed in accordance with these instructions, local codes, utility codes, utility company requirements or, in the absence of local codes, the latest edition of the National Electrical Code. It is available from some local libraries or can be purchased from the National Fire Protection Association, Batterymarch Park, Quincy, MA 02269 as booklet ANSI/NFPA 70.
Canadian installations should refer to CSA22.1, a copy can be purchased from the Canadian Standards Association, 5050 Spectrum Way, Mississauga, ONT L4W 5N6
Location
Locate the water heater in a clean dry area as near as practical to the area of greatest heated water demand. Long un-insulated hot water lines can waste energy and water.
Place the water heater in such a manner that the thermistor access panels can be removed to permit inspection and servicing such as checking controls.
The water heater and water lines should be protected from freezing temperatures. DO NOT install the water heater in outdoor, unprotected areas.
Make certain the floor underneath the water heater is strong enough to sufficiently support the weight of the water heater once it is filled with water. Floor isolation kit is recommended to minimize vibrations (where applicable).
NOTICE: Auxiliary drain pan MUST conform to local codes. Drain Pan Kits are available from the store where the water heater was purchased, or any water heater distributor. Drain Pan should not obstruct cold inlet or drain valve.
⚠ CAUTION: The water heater should not be located in an area where leakage of the tank or connections will result in damage to the area adjacent to it or to lower floors of the structure. Where such areas cannot be avoided, it is recommended that a suitable drain pan, adequately drained, be installed under the water heater.
NOTICE: Installation in a confined space will lead to higher power consumption if adequate ventilation is not provided.
It is recommended that the hybrid water heater be installed where ambient temperatures DO NOT exceed 145°F (63°C). Insufficient air exchange will result in increased energy consumption levels.
Clearances
A diagram shows the water heater with recommended clearances: 0" Rear, 3" Sides, 9" Top. It also indicates A = Diameter of water heater plus 4" min., and B = Maximum 2". Text notes that to open the drain, the line should be at least 3/4" ID and pitched for proper drainage.
Locations that provide optimal efficiency
Heater: Not Ducted
Room size: Larger than 1200 ft² (e.g. 12' x 10' x 10'). Requirements: No additional ventilation needed.
Heater: Not Ducted
Room size: 400 ft² (e.g. 5' x 8' x 10') - 1200 ft³ (e.g. 12' x 10' x 10'). Requirements: Full louvered door OR two louvers top and bottom.
1. Minimum louver free opening area required for not ducted room installation application will be 2.9 sq ft.
2. Minimum louver free opening area required for ducted closet installation application will be 3.25 sq ft.
Heater: Ducted with outlet duct
Room size: For all closet installation (size smaller than 400 ft³). Requirements: Full louvered door.
NOTICE: If air temperature in installed location drops more than 15°F (8°C) during heating, air circulation is insufficient for efficient operation. Utilize ducting to direct cold exhaust air to another location. The room size are referring to the free unoccupied space inside the room.
Thermal Expansion
Determine if a check valve exists in the inlet water line. Check with your local water utility. It may have been installed in the cold water line as a separate back flow preventer, or it may be part of a pressure reducing valve, water meter or water softener. A check valve located in the cold water inlet line can cause what is referred to as a "closed water system". A cold water inlet line with no check valve or back flow prevention device is referred to as an "open" water system.
As water is heated, it expands in volume and creates an increase in the pressure within the water system. This action is referred to as "thermal expansion". In an "open" water system, expanding water which exceeds the capacity of the water heater flows back into the city main where the pressure is easily dissipated.
A "closed water system", however, prevents the expanding water from flowing back into the main supply line, and the result of "thermal expansion" can create a rapid and dangerous pressure increase in the water heater and system piping. This rapid pressure increase can quickly reach the safety setting of the relief valve, causing it to operate during each heating cycle. Thermal expansion, and the resulting rapid and repeated expansion and contraction of components in the water heater and piping system can cause premature failure of the relief valve, and possibly the heater itself. Replacing the relief valve WILL NOT correct the problem!
The suggested method of controlling thermal expansion is to install an expansion tank in the cold water line between the water heater and the check valve (refer to the illustration on the next page). The expansion tank is designed with an air cushion built in that compresses as the system pressure increases, thereby relieving the over pressure condition and eliminating the repeated operation of the relief valve. Other methods of controlling thermal expansion are also available. Contact your installing contractor, water supplier or plumbing inspector for additional information regarding this subject.
NOTICE: The inlet and outlet water nipple remain with the black markings pointed up.
Water Supply Connections
Refer to the illustration on the next page for suggested typical installation. The installation of flexible connectors is recommended on the hot and cold water connections. Flexible connections provide vibration isolation and allow the water heater to be easily disconnected for servicing if necessary. The HOT and COLD water connections are clearly marked and are 3/4in. NPT on all models. Install a shut-off valve in the cold water line near the water heater. See page 9 on "To Fill The Water Heater".
NOTICE: DO NOT apply heat to the HOT or COLD water connections. If sweat connections are used, sweat tubing to adapter before fitting adapter to the water connections on heater. Any heat applied to the water supply fittings will permanently damage the dip tube and/or heat traps.
Condensate Drains
NOTICE: Condensate from this unit is not Acidic and is not required to be neutralized.
Consult local codes or ordinances for specific requirements. Refer to page 5.
IMPORTANT: When making drain fitting connections to the drain tubing, use a thin layer of piping tape or silicone and install hand tight.
IMPORTANT: When making drain fitting connections to the drain tubing, DO NOT overtighten. Overtightening fittings can split pipe connections on the drain pan.
- This unit is equipped with a 3/4" NPT female primary condensate connection. Use MIP fittings for connections.
- DO NOT reduce drain line size less than connection size provided on condensate drain.
- All drain lines must be pitched downward away from the unit a minimum of 1/8" per foot of line to ensure proper drainage.
- Drain lines must include a P-trap if connected to a sewer pipe.
- If no drain is available, then a common condensate pump with a capacity no less than 2 gallon per day must be installed.
- DO NOT allow condensate to drain into the water heater drain pan.
- The drain line should be insulated where necessary to prevent sweating and damage due to condensate forming on the outside surface of the line.
Relief Valve
A diagram shows the water heater with plumbing connections: hot water outlet, T&P Valve, primary condensation outlet, drain valve, cold water supply, and optional thermal expansion tank. It also shows the air filter and clearance above the unit. Text indicates a piping tee for condensate access and flexible connections.
A new combination temperature and pressure relief valve, complying with the Standard for Relief Valves for Hot Water Supply Systems, ANSI Z21.22/CSA 4.4, is factory installed and must remain in the opening provided and marked for the purpose on the water heater. No valve of any type should be installed between the relief valve and the tank.
⚠ WARNING: The pressure rating of the relief valve must not exceed 150 PSI, the maximum working pressure of the water heater as marked on the rating plate.
The btu/h rating of the relief valve must not be less than the input rating of the water heater as indicated on the rating label located on the front of the heater (1 watt=3.412 btu/h).
Connect the outlet of the relief valve to a suitable open drain so that the discharge water cannot contact live electrical parts or persons and to eliminate potential water damage.
Piping used should be of a type approved for hot water distribution. The discharge line must be no smaller than the outlet of the valve and must pitch downward from the valve to allow complete drainage (by gravity) of the relief valve and discharge line. The end of the discharge line should not be threaded or concealed and should be protected from freezing. No valve of any type, restriction or reducer coupling should be installed in the discharge line.
⚠ WARNING: DO NOT connect other plumbing to the T&P plumbing; it must go directly to a suitable open drain. DO NOT connect the T&P plumbing to the condensate plumbing.
To Fill the Water Heater
Make certain the drain valve on the water heater is completely closed. Open the shut-off valve in the cold water supply line. Open each hot water faucet slowly to allow the air to vent from the water heater and piping. A steady flow of water from the hot water faucet(s) indicates a full water heater.
EcoNet™ Communication
EcoNet™ communication is provided for integration with home automation, energy management, and demand response systems. Connectivity is provided through the via wireless (Wi-Fi).
A diagram shows the right side view of the water heater, pointing out the Electrical Power Hookup Terminals and the EcoNet Port (Service Only).
Electrical Connections
⚠ WARNING: Turn off electric power at the fuse box or service panel before making any electrical connections. Disconnect all power to unit before starting maintenance. Failure to do so can cause electrical shock resulting in severe personal injury or death.
The unit must be grounded. Failure to do so can cause electrical shock resulting in severe personal injury or death.
If the water heater has been subjected to fire, flood or physical damage, DO NOT operate the water heater again until it has been checked by a qualified service technician.
NOTICE: DO NOT use this appliance if any part has been under water. Immediately call a qualified installer or service agency to replace a flooded water heater. DO NOT attempt to repair the unit! It must be replaced.
Electrical Connections continued...
A separate branch circuit with copper conductors, overcurrent protective device and suitable disconnecting means must be provided by a qualified electrician. All wiring must conform to local codes or latest edition of National Electrical Code ANSI/NFPA 70.
The voltage requirements and wattage load for the water heater are specified on the rating plate on the front of the water heater.
The branch circuit wiring should include either:
- Metallic conduit or metallic sheathed cable approved for use as a grounding conductor and installed with fittings approved for the purpose.
- Non-metallic sheathed cable, metallic conduit or metallic sheathed cable not approved for use as a ground conductor shall include a separate conductor for grounding. It should be attached to the ground terminals of the water heater and the electrical distribution box.
⚠ DO NOT turn on the electrical supply or operate this water heater unless it is completely full of water.
⚠ CAUTION: The presence of water in the piping and water heater does not provide sufficient conduction for a ground. Non-metallic piping, dielectric unions, flexible connectors etc. can cause the water heater to be electrically isolated.
NOTICE: This guide recommends minimum branch circuit sizing and wire size based on National Electric Code. Refer to wiring diagrams in this manual for field wiring connections.
Branch Circuit Sizing And Wire Size Guide
SINGLE PHASE WIRING | Rated current I (A) | Recommended Over Current Protection (Fuse or Circuit Breaker Amperage Rating) 120V | Copper Wire Size AWG based on N.E.C. Table 310-16 (75°C) 120V |
---|---|---|---|
I<12 A | 15 | 14 | |
12A<I<16A | 20 | 12 |
⚠ CAUTION: Use time delay fuse.
Insulation Blankets
Insulation blankets, available to the general public, for external use on electric water heaters are not necessary. The purpose of an insulation blanket is to reduce the standby heat loss encountered with storage tank heaters. This water heater meets or exceeds the National Appliance Energy Conservation Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary.
The manufacturer's warranty does not cover any damage or defect caused by installation, attachment or use of any type of energy saving or other unapproved devices (other than those authorized by the manufacturer) into, onto or in conjunction with the water heater. The use of unauthorized energy saving devices may shorten the life of the water heater and may endanger life and property. The manufacturer disclaims any responsibility for such loss or injury resulting from the use of such unauthorized devices.
⚠ CAUTION: If local codes require the application of an external insulation blanket to this water heater, pay careful attention to the following so as not to restrict the proper function and operation of the water heater:
- DO NOT cover the operating or warning labels attached to the water heater or attempt to relocate them on the exterior of insulation blanket.
- DO NOT cover air openings of the water heater .
- DO NOT cover the Controller Assembly, temperature and pressure relief valve or drain valve.
- Inspect the insulation blanket frequently.
A diagram shows the air filter location, controller assembly, and air outlet opening, noting the air filter must be accessible.
Hot and Cold Pipe Insulation Installation
Install the insulation on the cold water supply inlet and the hot water outlet as shown in the illustration.
A diagram shows the water heater with insulation installed on the hot water outlet pipe and cold water inlet pipe.
Ducting Requirements
Always check with local building and HVAC codes before designing the duct system. The water heater may be ducted to the outdoors or another space as described in these instructions. Ducting configurations that does not comply with these guidelines are not supported.
DO NOT connect this water heater to existing duct work; it must be ducted separately from other appliances. Ducting approved for HVAC applications is required. Ducting must be adequately supported along both vertical and horizontal lengths. UL Certified terminations must be used for ducting to the outside. These terminations have been evaluated to ensure there is sufficient protection from rain water entry and resistance to air flow is minimized. Indoor registers approved for HVAC applications is required. Rigid ducting must be isolated from floor joists or other structural members to minimize the transmission of noise and vibration. A short section (12 inch minimum) of flexible duct must be used between the water heater and rigid ducting as an isolation method.
Every foot of flexible ducting counts as three feet of rigid ducting. Ducting must be insulated per HVAC codes (to prevent condensation). Ensure cold air exhaust is sufficiently away from structures to prevent condensation on surfaces. Maximum heater performance is obtained by lowering the resistance to air flow (regular filter maintenance is beneficial) and providing the unit with warm moist air.
Considerations when planning the duct system:
- Run the ducting the most direct route possible.
- Limit the number of elbows/bends.
- Use the largest duct size possible.
- Use the largest termination possible.
- Consider placement and direction of terminations (reduce recirculation of exhaust into the intake).
Calculated length of duct is the length on the inlet plus the length on the outlet. Any combination of duct lengths on the inlet and outlet is supported up to the maximum duct length (Table 1).
Duct System Configuration
8, 7, 6 and 5 inch diameter ducting is supported. Table 1 lists the total feet of ducting allowed. For duct diameters smaller than 8 inch diameter, Table 1 takes into account the duct reducer(s) and up to 10 feet of 8 inch rigid ducting (two elbows) before the duct reducer(s) at the unit. Duct Reducers must be installed within 10 feet (two elbows) of the unit or within 2 feet of the end of the duct.
Table 1.- Maximum Duct Length.
Duct Type / Diameter | 8" | 7" | 6" | 5" |
---|---|---|---|---|
Rigid | 340' | 160' | 65' | 17' |
Flexible | 125' | 65' | 25' | -- |
Equivalent feet for Duct Accessories
Elbows/Bends
Rigid duct elbows and flex bends greater than 45° is considered an elbow. Flexible ducting bends' inner radius cannot be less than its diameter. If bends with tighter radiuses are needed, a rigid elbow must be used. Maximum number of elbows/bends allowed are shown in [brackets] in Table 2.
Terminations/Registers
Table 2 equivalent feet for terminations includes the rodent screen. For terminations and registers with smaller diameters than the duct diameter, Table 2 accounts for the duct reducer and termination/register. Smaller diameter terminations and registers with more than a 2 ft. connection is not supported.
Damper
If ducting to the outside using an exhaust duct only (no intake duct), an approved Rheem damper should be installed no further than 10 ft. of rigid ducting total (two elbows equivalent) from the unit. This prevents outside air from coming into the living space. If ducting air from the outside to the inlet of the heater, no provision is made to prevent outside air from flowing into the living space.
Table 2.- Equivalent feet for Duct Accessories.
Description | 8" | 7" | 6" | 5" |
---|---|---|---|---|
Elbows/Flexible Bends (Each) [Maximum Allowed] | 5' [8] | 5' [6] | 5' [4] | 5' [2] |
8 inch UL Certified Termination for ducting outside (Each) | 5' | 5' | 5' | 5' |
Reduced diameter UL Certified Termination for ducting outside (Each) | N/A | 10' | 15' | 20' |
8 inch Register for ducting inside (Each) | 5' | 5' | 5' | 5' |
Reduced diameter Register for ducting inside (Each) | N/A | 10' | 15' | 20' |
Rodent Screen (must be greater than 83% open area) (Each) | 1' | 1' | 1' | 1' |
Rheem approved 8" diameter Duct Damper | 25' | 20' | 10' | 5' |
Table 2 lists equivalent feet for duct accessories and reduced diameter terminations.
Accessory Kits
Part Number | Description | User For |
---|---|---|
SP20882 | Earthquake Isolation Kit for Hybrid Water Heater | Installations in Seismic Region. |
SP20883 | Vibration Isolation Kit for Hybrid Water Heater | Installation on Non-concrete floors. |
SP20884 | 8" Dia. UL Certified Termination kit | Termination to the outside or to attic with 8" diameter |
SP20885 | 7" Dia. UL Certified Termination kit | Termination to the outside or to attic with 7" diameter |
SP20886 | 6" Dia. UL Certified Termination kit | Termination to the outside or to attic with 6" diameter |
SP20887 | 5" Dia. UL Certified Termination kit | Termination to the outside or to attic with 5" diameter |
SP20888 | 8" Rheem Approved Damper Kit | Exhaust only to the outside ducting configuration (No inlet Duct). |
SP20889 | 25' Flexible 8" dia. Duct kit | For up to 25' of Ducting. |
SP21189 | Thor exhaust air adapter kit | For outlet exhaust duct pipe as adaptor |
Ducting Example
NOTICE: These seven questions should be answered to ensure correct duct configuration. See Ducting Example.
Ducting Example:
- Exhaust/Inlet or both? Only Outlet
- Ducting to outside of building or another room? Outside building.
- Length of duct from water heater to termination? 20 ft.
- Flexible or Rigid ducting? Flexible.
- Diameter of ducting used? 8 in. Diameter
- Diameter of wall penetrations? 5 in. Diameter
- Number of elbows/bends? 3 Total – One on inlet and Two on Outlet
I. Does calculated ducting length exceed maximum allowable table?
a. 20 ft. (Outlet duct length)
b. 10 ft. (1 rigid elbow and 1 bend on outlet)
c. 20 ft. (reduced diameter termination outlet)
d. Total = 20+10+20= 50 ft.
Using flexible 8 in. diameter duct, the maximum duct length allowed is 125 ft.; therefore, because 95 ft. is less than 125 ft., this is an acceptable ducting configuration.
Accessory Kits SP20887 (2 Kits), SP20889 (2 Kits) and SP20890 (1 Kit) are available for this installation.
Horizontal Duct Installation
Once the duct terminal location has been determined, make a hole through the exterior wall to accommodate the UL Certified Termination. Termination must exit exterior wall horizontally only. Complete rest of the duct pipe installation to the water heater's duct connector fitting. If necessary, support horizontal run as previously mentioned.
A diagram illustrates horizontal duct installation, showing flex duct, rigid duct, reducers, UL certified termination, and HVAC tape.
Mixing Valve Installations
A thermostatic mixing valve conforming to ASSE 1017 shall be installed on the hot water supply line following all manufacturer installation instructions. Nominal 3/4" size mixing or tempering valve (refer to warning above). Follow mixing or tempering valve manufacturer's instructions for installation of the valve.
A diagram shows the hot water outlet connected to a 3/4" tempered domestic hot water supply via a mixing valve.
Installation Checklist
A. Water Heater Location
- Close to area of heated water demand.
- Indoors and protected from moisture, wet conditions, freezing temperatures (below 32°F (0°C)) and High temperatures (above 145°F (62°C)).
- Area free of flammable vapors.
- Provisions for Air Circulation (Louvered doors on ducting).
- Provisions made to protect area from water damage.
- Sufficient room to service heater.
- Twelve inches (12") of clearance from ceiling to top of Hybrid Water Heater to allow for filter maintenance.
- Access to condensate disposal.
- Vibration Isolation Kit (Non-Concrete floors).
- Hybrid seismic Kit (if required).
B. Water Supply
- Water heater completely filled with water.
- Air purged from water heater and piping.
- Water connections tight and free of leaks.
- Flexible water connections.
C. Relief Valve
- Temperature and Pressure Relief Valve properly installed and discharge line run to open drain.
- Discharge line protected from freezing.
D. Wiring
- Power Supply voltage agrees with water heater rating plate.
- Branch circuit wire and fusing or circuit breaker of proper size. (Recommended 15 amp & 20 amp breaker for select models).
- Electrical connections tight and unit properly grounded.
- 12 gauge wire for 20A breaker and 14 gauge wire for 15 A breaker.
E. Condensate Lines
- Condensate lines from heat pump installed correctly.
- Condensate lines from heat pump run to a suitable drain location.
F. Ducting
- HVAC approved ducting.
- Calculated length of duct no greater than maximum allowed.
- UL Certified terminations (For ducting to the outside).
- Insulated duct.
- Ducting adequately supported.
- Ducting adequately isolated from structure.
Operating the Water Heater
⚠ CAUTION: Hydrogen gas can be produced in a hot water system served by this water heater that has not been used for a long period of time (generally two weeks or more). HYDROGEN GAS IS EXTREMELY FLAMMABLE!! To dissipate such gas and to reduce risk of injury, it is recommended that the hot water faucet be opened for several minutes at the kitchen sink before using any electrical appliance connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipe as the water begins to flow. DO NOT smoke or use an open flame near the faucet at the time it is open.
Safety Precautions
- Disconnect all power to water heater if it has been subjected to over heating, fire, flood, physical damage.
- DO NOT turn on water heater unless it is filled with water.
- DO NOT turn on water heater if cold water supply shut-off valve is closed.
If there is any difficulty in understanding or following the Operating Instructions or the Care and Cleaning section, it is recommended that a qualified person or serviceman perform the work.
⚠ WARNING: If the water heater has been subjected to fire, flood or physical damage, disconnect all power to water heater, and DO NOT operate the water heater again until it has been checked by a qualified service technician.
NOTICE: DO NOT use this appliance if any part has been under water. Immediately call a qualified installer or service agency to replace a flooded water heater. DO NOT attempt to repair the unit! It must be replaced.
Safety Controls
The water heater is equipped with a temperature limiting control (ECO) that is located in upper cavity cover in contact with the tank surface. If for any reason the water temperature becomes excessively high, the temperature limiting control (ECO) breaks the power circuit to the heating system. Once the control opens, it must be reset manually.
⚠ CAUTION: The cause of the high temperature condition must be investigated by qualified service technician and corrective action must be taken before placing the water heater in service again.
To reset the temperature limiting control: (Refer to Illustration in Cavity Insert section):
- Disconnect all power to unit before starting maintenance.
- Remove the upper cavity cover and insulation.
- Press the red RESET button.
- Replace the insulation, jacket access panel and plastic housing before turning on the power to the water heater.
⚠ DANGER: There is a hot water scald potential if the thermostat is set too high. Households with small children, disabled, or elderly persons may require a 120°F (49°C) or lower thermostat setting to prevent contact with HOT water.
Water Temperature Setting
The temperature of the water in the water heater can be regulated by selecting the desired temperature on control display. Safety and energy conservation are factors to be considered when selecting the water temperature setting of the water heater. The lower the temperature setting, the greater the savings in energy and operating costs.
To comply with safety regulations the temperature is factory set at 120°F (49°C) or less where local codes require. This is the recommended starting point. Water temperatures above 125°F (52°C) can cause severe burns or death from scalding. Be sure to read and follow the warnings outlined in this manual and on the label on the water heater. This label is located on the front of the water heater.
Mixing valves are recommended for reducing point of use water temperature by mixing hot and cold water in branch water lines. It is recommended that a mixing valve complying with the Standard for Temperature Actuated Mixing Valves for Hot Water Distribution Systems, ASSE 1017 be installed. See page 3 for more details and contact a licensed plumber or the local plumbing authority for further information. When used in demand response applications a thermostatic mixing valve conforming to ASSE 1017 shall be installed on the hot water supply line following all manufacturer installation instructions. See page 32 for additional installation information. The chart on the page 3 may be used as a guide in determining the proper water temperature for your home.
Local Startup
User Interface
A diagram shows the water heater's control panel with labels for Current Mode, Fault Indicator, Temp & Value Adjustment, Current Alarm & History, Scroll Available, Enable/Disable, Clear Alarm, Current Set Point, Scald Warning, Mode Toggle, Next Screen / Option, Text Display, Enter / Select, and WiFi Setup & Indicator.
ICONS show the current state of the entire system.
- Current Mode - Illuminated when the system is working on the corresponding mode.
- Wi-Fi Indicator - Illuminated when the display detects valid connection to a Wi-Fi network. Blinking when in provisioning mode.
- Fault Indicator - Illuminated when the display detects OBJECT codes ALMCODE 1, 2, 3 or 4 is greater than "0". This indicates the Control Board has detected either an Alarm or an Alert.
- Scroll Available Indicator - Illuminated when the display detects the Up/Down arrows are enabled to scroll.
- Scald Warning - Illuminated when the display detects potential scalding water temperatures. Use water at own risk.
- Enable/Disable Indicator - Illuminated when the display is Enabled (ON).
Enabling / Disabling Unit
A diagram shows the control panel with the unit displayed as "DISABLED". Instructions indicate pressing the "ON/OFF" button to turn on/enable the unit. The unit will be disabled upon initial startup.
A second diagram shows the control panel with the unit enabled. Instructions indicate pressing the "ON/OFF" button to turn off/disable the unit.
Adjusting Temperature
A diagram shows the control panel displaying "119°F" with the scald warning indicator illuminated. Instructions indicate pressing the "UP" button to increase temperature.
A second diagram shows the control panel displaying "120°F" with the scald warning indicator illuminated. Instructions indicate pressing the "DOWN" button to decrease temperature.
*Scald warning will automatically appear at 120°F and higher.
Lock/Unlock Display
Press and hold for 5 seconds both UP and DOWN buttons to Lock/Unlock the Display. This prevents any change in Mode of operation or set-point if any button is pressed.
Change Mode of Operation
A diagram shows the control panel displaying "119°F" and the "ELECTRIC" mode. Instructions indicate pressing the "MODE" button to select operating mode.
Modes of Operation
- Heat Pump
- Vacation
Mode | Efficiency | Recovery |
---|---|---|
Heat Pump | High | Fast |
Vacation | Very High | None |
Setting Menu
A diagram shows the control panel displaying "ALARM HISTORY". Instructions indicate pressing the "NEXT" button to access the settings.
Keep pressing "NEXT" button to scroll through the following menu items:
- ALARM BEEP: Enable/Disable Alarm Sound. a. Use the Up/Down arrows to change from Yes (Default) to No sound.
- TEMP DISPLAY: Change the temperature units (°F or °C). a. Use the Up/Down arrows to change from F° (Default) to °C.
- CURRENT ALARMS a. Use the Up/Down arrows to scroll through the current alarms. b. To clear alarms press the Clear Alarm button.
- ALARM HISTORY a. Use the Up/Down arrows to scroll through the alarm history.
- CLEAR HISTORY a. Press ENTER to clear alarm history.
- MAC ADDRESS: WiFi MAC Address.
- NETWORK INSTANCE: Instance of the current unit. a. Use the Up/Down arrow to change Network Instance if needed.
- SOV INSTALLED: a. A Shut-Off Valve (SOV) is installed? - This will say yes if a SOV is installed.
WiFi Setup
1. Press, hold for 5 seconds and release the WiFi button.
2. WiFi LED will start to blink when it is ready to start WiFi setup.
3. WiFi signal will start to broadcast for 30 minutes and user can use EcoNet Application to setup WiFi.
4. If setup is not completed in the next 30 minutes, WiFi will stop broadcasting. User should perform these steps again to re-start WiFi setup.
5. Once correctly connected, LED will turn solid blue.
A diagram shows the control panel with the WiFi button being pressed.
WiFi Soft Reset
If WiFi needs to be reseted while keeping the same WiFi login information:
- Press, hold for 3 seconds and release the WiFi button. 1 beep will be heard.
- WiFi will try to re-connect to the same network that was configured previously.
WiFi Hard Reset
If WiFi needs to be reset because there is a new network to be used:
- Press, hold for 5 seconds and release the WiFi button. 3 beeps will be heard.
- Follow the same steps as in WiFi Setup section.
EcoNet App
EcoNet App 2.0 Instructions
Download EcoNet app and create profile.
- Open and log into your EcoNet app and select the "Add Product" option on the main equipment screen.
- Add a location by either selecting "Use my current location" or entering your zip code, then hit "Next".
- Place your Water Heater in WiFi setup and click the "Continue" button.
- Select your WiFi module's mac address from the network list. You can find your MAC address in the Water Heater WiFi menu.
- Return to the app, where you should see the following screen. Click "Available Networks".
- Select your router and enter your password. Click "Connect".
- The app should proceed to provision your WiFi module using a secure connection. You should see message shown in the image on the left.
- Once connected, product home screen will be displayed.
Screenshots illustrate the step-by-step process for setting up the EcoNet App.
Care and cleaning of the water heater
Draining the Water Heater
⚠ CAUTION: Shut off power to the water heater before draining water.
⚠ DANGER: Before manually operating the relief valve, make certain no one will be exposed to the hot water released by the valve. The water drained from the tank may be hot enough to present a scald hazard and should be directed to a suitable drain to prevent injury or damage.
In order to drain the water heater, turn off the cold water supply. Open a hot water faucet or lift the handle on the relief valve to admit air to the tank. Attach a garden hose to the drain valve on the water heater and direct the stream of water to a drain. Open the valve.
⚠ DANGER: Before manually operating the relief valve, make certain no one will be exposed to the danger of coming in contact with the hot water released by the valve. The water may be hot enough to create a scald hazard. The water should be released into a suitable drain to prevent injury or property damage.
NOTICE: If the temperature and pressure relief valve on the water heater discharges periodically, this may be due to thermal expansion in a closed water system. Contact the water supplier or your plumbing contractor on how to correct this. DO NOT plug the relief valve outlet.
Routine Preventative Maintenance
Properly maintained, your water heater will provide years of dependable trouble-free service. It is suggested that a routine preventive maintenance program be established and followed by the user.
Most electrical appliances, even when new, make some sound when in operation. If the hissing or singing sound level increases excessively, Contact a qualified installer or plumbing contractor to inspect.
IMPORTANT: See "DANGER on left". At least once a year, lift and release the lever handle on the temperature pressure relief valve, located on the side of the water heater, to make certain the valve operates freely. Allow several gallons to flush through the discharge line to an open drain.
It is recommended to clean the filter on top of the heat pump when "Clean filter reminder" alert appears. Clean by washing with mild detergent and water. Dry and replace. Remove the filter by lifting up, then replace by lowering back into the filter slot on top of the unit. See Figure below.
A diagram shows the filter handle and vertical flexible filters on top of the unit.
At least once a year pour a cup of bleach in the access opening of the condensate drain to kill any algae, mold, or mildew that has formed in the pipe. Ensure the condensate can flow freely; unclog if needed.
A water heater's tank can act as a setting basin for solids suspended in the water. It is therefore not uncommon for hard water deposits to accumulate in the bottom of the tank. It is suggested that a few quarts of water be drained from the water heater's tank every month to clean the tank of these deposits.
Rapid closing of faucets or solenoid valves in automatic water using appliances can cause a banging noise heard in a water pipe. Strategically located risers in the water pipe system or water hammer arresting devices can be used to minimize the problem.
Vacation and Extended Shut-Down
NOTICE: Refer to the Hydrogen Gas Caution in the Operating Instructions.
If the water heater is to remain idle for an extended period of time, the power and water to the appliance should be turned off to conserve energy and prevent a build-up of dangerous hydrogen gas. The water heater and piping should be drained if they might be subjected to freezing temperatures.
After a long shut-down period, the water heater's operation and controls should be checked by qualified service personnel. Make certain the water heater is completely filled again before placing it in operation.
Anode Rod
NOTICE: DO NOT remove the anode rod from the water heater's tank. Operation with the anode rod removed will greatly shorten the life of the glass lined tank and will exclude warranty coverage.
This water heater is equipped with an anode rod designed to prolong the life of the glass-lined tank. The anode rod is slowly consumed, thereby eliminating or minimizing corrosion of the glass-lined tank.
Water sometimes contains a high sulfate and/or mineral content and together with cathodic protection process can produce a hydrogen sulfide, or rotten egg odor in the heated water. Chlorination of the water supply should minimize the problem.
Troubleshooting
Before You Call For Service...
Save time and money! Review the chart on this page first and you may not need to call for service.
Problem | Possible Causes | What to Do |
---|---|---|
Rumbling noise | Water conditions in your home caused a build up of scale or mineral deposits in the water heater. | Allow a few quarts of water to run from drain valve to remove sediment settlings. |
Relief valve producing popping noise or draining | Pressure build up caused by thermal expansion in a closed system | This is an unacceptable condition and must be corrected. Contact the water supplier or plumbing contractor on how to correct this. DO NOT plug the relief valve outlet. |
Not enough or no hot water | Water usage may have exceeded the capacity of the water heater. | Wait for the water heater to recover after an abnormal demand. |
A fuse is blown or a circuit breaker tripped | Replace fuse or reset circuit breaker. | |
Electric supply may be off | Confirm electric supply to water heater and see installation section of this manual. | |
The thermostat may be set too low. | See the Temperature regulation of the water heater section of this manual. | |
Leaking or open hot water faucets | Make sure all faucets are closed. | |
Electric service to your home may be interrupted | Contact the local electric utility. | |
Improper wiring. | See the Installing the water heater section of this manual. | |
Manual reset limit (ECO) | See the Temperature regulation of the water heater. Refer to page 3 for more information. | |
Cold water inlet temperature may be colder during the winter months | This is normal. The colder inlet water takes longer to heat. | |
Not enough air exchange for Efficient Heat Pump Operation. | If air temperature drops more than 15°F (8°C) during Heat Pump Operation, more air circulation around heater is needed. | |
Water is too hot | The thermostat is set too high. | See the Temperature regulation of the water heater section of this manual. |
⚠ CAUTION: For your safety DO NOT attempt repair of electrical wiring, thermostats, or other safety devices. Refer repairs to qualified service personnel.
Troubleshooting Alarm Codes
Save time and money! Review the charts on this section first and you may not need to call for service.
The water heater will make an audible beep for notification of Alarms and ⚠ icon. The following steps should be used in determining the Alarm code:
- Press "Next" button until "Current Alarm" is visible.
- Press "Down" arrow button ↓ to scroll through the active alarms.
A diagram shows the control panel with the "Next" button being pressed to view "Current Alarm". Another diagram shows scrolling through alarms with the "Down" arrow.
Alarm Code Table
Code | Troubleshooting Guide | Possible Causes | What to Do |
---|---|---|---|
A004 | Comp.Shutdown: Discharge-Suction Trip | Heating source defaults to elements due to compressor malfunction | 1. Confirm fan is operational while compressor is on. (If the fan is not operational, check continuity from middle(ground)terminal to either out-side terminal. If there is a 60V or higher reading, the fan should be running and will need to be replaced. If not, replace the control board (rare)). 2. Confirm filter screen is clean. 3. Inspect compressor and surrounding components for any obvious signs of refrigerant leak (oily residue). If the compressor is not operational or there are signs of leakage, the unit will need to be replaced as we do not service sealed system parts. |
A005 | Compressor Shutdown: Discharge Temp High | Heating source defaults to elements due to low airflow | |
T005 | Compressor Shutdown: Discharge Temp High | Heating source defaults to elements due to compressor malfunction | |
A006 | Suction Temperature Too Low | Heating source defaults to elements due to compressor malfunction | |
T006 | Suction Temperature Too Low | Heating source defaults to elements due to compressor malfunction | |
T009 | Compressor wiring may be faulty | Heating source default to elements due to compressor malfunction | 1. Check connections of the wiring and sensors. 2. Get an Ohm reading on the thermistors (if multimeter is available) (See Ohm chart for correct readings based on ambient temperature). 3. Check on display by selecting Service-->Sensors-->If sensor shows - 40°F, the circuit is open. +250°F indicates the circuit has shorted. Note: To confirm reading, power down the unit and unplug the thermistor from the board. Check Ohm reading. (See ohms chart) |
A009 | Compressor wiring may be faulty | Heating source defaults to elements due to heat pump temperature sensor malfunction | |
A101 | Suction Temperature Sensor Failure | Heating source defaults to elements due to heat pump temperature sensor malfunction | |
A102 | Ambient Temperature Sensor Failure | Lower tank temperature sensor malfunction. Heater disabled. | |
A103 | Lower Heater Temp Sensor Failure | Heating source defaults to elements due to heat pump temperature malfunction. | |
A104 | Upper Heater Temp Sensor Failure | ||
A105 | Evaporator Temp Sensor Failure | ||
A106 | Discharge Temp Sensor Failure | ||
A107 | Water Detected on Floor: Check For Leaks | Water is detected in the drain pan | 1. Check for obvious water leaks (If leak is present, service for unit leakage). 2. If obvious leakage is not present, disconnect rope sensor from the board and if the code is no longer present, dry (a blow dryer is an acceptable method) or replace rope sensor. 3. If error is still present once the rope sensor has been replaced, the board will need to be replaced. 4. Press and hold the "Clear Alarm" button ⌘ for 5 seconds to override the alarm for 24 hrs. |
A108 | Condensate Blocked: Unclog Line | Heating source defaults to elements due to condensate drain blockage | 1. Remove top cover from tank. 2. Visually inspect to ensure condensate line is clear and there is not excessive condensate in condensate pan. 3. If water is present, locate blockage and unlock. 4. Ask customer to where the condensate is being routed. 5. If pan is dry and no blockage is present, replace condensate sensor. |
A130 | Unit Off/Air Temp Freezing: Enable Unit | Ambient temperature is below freezing. --FREEZE WARNING | Select mode to enable heater (Turn it on). |
T131 | Clean Filter Reminder | Air filter routine maintenance reminder | 1. Set mode to Electric or OFF. 2. Remove air filters and clean by washing with a mild detergent. 3. Dry air filter and reinstall. 4. Set unit to desired mode. |
T132 | Water Heater difficulty satisfying demand | Water heater can not satisfy demand | 1. Check for open faucets. 2. Check for water leaks. 3. If none present, unit may be improperly sized. |
A120 | Shutoff Valve Can't Close Error | Shut-Off Valve malfunction | 1. Check connections of the wiring. 2. Unplug and plug back the Shut-Off valve. 3. If alarm persists, call customer service. |
A121 | Shutoff Valve Can't Open Error | ||
A122 | Shutoff Valve Inputs in Error | ||
A123 | Shut-Off Valve Not Installed | ||
A200 | High Water Temp! [ECO] Call Tech Service | ECO Tripped. Heater Disabled | 1. Disconnect power to unit. 2. Check elements from screw to ground. 3. Check resistance to thermistors. 4. If the issue is neither the elements or thermistor, replace board. |
T300 | Water vor Not Installed | Water Leak Sensor Not Installed | 1. Check to ensure water leak sensor is installed. 2. Check wiring connections to sensor from board. 3. Check resistance to sensor to determine whether sensor or board should be replaced (See ohm reading chart for correct readings). |
A502 | Time Clock needs to be programmed | ||
A503 | Time Clock not advancing time properly | ||
T504 | WiFi Chip Communication Error | ||
A900 | Controller Fault: Call Tech Service | Controller malfunction. Heater disabled. | Replace Control Board |
T901 | Controller Fault: Call Tech Service | ||
A902 | Controller Fault: Call Tech Service | ||
A903 | Controller Fault: Call Tech Service | ||
A904 | Controller Fault: Call Tech Service | ||
A905 | Controller Fault: Call Tech Service | ||
A906 | Power Board Temp. Protection Sensor Failure | Controller getting too hot. |
Customer Service
CTA Module Wiring
Water Heater Junction Box
A diagram shows the water heater junction box with conduit connector and CTA Adaptor.
Power cord should be directly plugged into receptacle with proper ground. Never plug unit into a circuit which might already be loaded with more than half of breaker ampage rating. If chose to wire differently, a qualified electrician is needed to establish the connection.
All wiring must conform to local codes or latest edition of National Electrical Code ANSI/NFPA 70.
*NOTE: A CTA2045 compliant Module can be connected to the water heater's top connector. Follow the instructions from the CTA2045 Module supplier to connect.
JA13 Offline Schedule Setting & Battery Replacement
A diagram shows the front cover, BR2032 battery, and control board assembly.
Before uploading and enabling JA13 offline schedule (Utility Contractor Only):
- Power ON Water Heater.
- Press, hold for 5 seconds and release the WiFi button.
- WiFi LED will start to blink when it is ready to start WiFi setup.
- WiFi signal will start to broadcast for 30 minutes and user can use the EcoNet Contractor Portal and Contractor Application to setup JA13 Offline Schedule.
- If setup is not completed in the next 30 minutes, WiFi will stop broadcasting. User should go to these steps again to re-start WiFi setup.
- Once setup is completed, the Demand Response Icon will light up which will indicate the Water Heater is following a schedule.
To override JA13 offline schedule:
- The user can override the JA13 offline schedule for 72 hrs by pressing the MODE button and changing the Mode of operation of the water heater to the user desired Mode and set-point.
- Once the user override Time elapses, the Demand Response will continue to follow the predetermined schedule.
- To completely opt-out from JA13 scheduling, contact your utility company.
To replace the battery follow these steps:
- Remove the front cover of the Control assembly.
- Remove the BR2032 battery from the battery holder.
- Replace the battery with an approved BR2032 cell coin battery.
- Re-Install the front cover of the Control assembly.
Replacement Parts.
Instructions For Placing a Parts Order
Address parts orders to the distributor or store where the heater was purchased. All parts orders should include:
- The model and serial number of the water heater from the rating plate located on the tank jacket.
- Specify voltage and wattage as marked on the rating plate.
- Part description (as noted below) and number of parts desired.
*NOTICE: Check the water heater's rating label on the front of the unit.
A diagram shows the water heater with various components labeled: Air Filters, CTA Module, Capacitor, Controller Assembly, Upper Thermistor & ECO, Outlet J-tube, Drain Valve, Cavity Covers, and Inlet Diffuser Tube.
⚠ CAUTION: For your safety DO NOT attempt repair of electrical wiring, heat pump or electronic controls. Refer repairs to qualified service personnel.
⚠ WARNING! FLAMMABLE CONTENTS UNDER PRESSURE. The compressor is not a serviceable part. The compressor wiring terminals may arc allowing pressurized refrigerant and oil to escape, ignite and cause serious bodily injury, severe burns or death.
Parts List
Part Number | Description |
---|---|
AP18087 | Thermistor |
AP18296 | Sanhua coil harness EXV |
AP20509 | Wire harness thermistor |
AP20590 | Wire harness compressor |
AP20915 | Filter |
AP20946 | Condensate sensor |
AP20947J | Characterization plug - HB40G5120 |
AP20947K | Characterization plug - HB50G5120 |
AP21045 | Capacitor |
AP21182 | Filter |
AP21397 | Lower tank thermistor bracket |
AP21548 | Fan |
AP21924 | Controller assembly |
AS49422-AE | Cavity cover upper |
AS49604-AE | Cavity cover lower |
AP11526T-2 | Anode |
AS49240 | ECO assemble (ECO with bracket and thermistor) |
AP14837G | T&P valve |
AP16830D | Drain valve |
AP8878N | J tube |
AP21903 | Diffuser tube |
AP21666 | Power cord |
AP20624 | CTA housing (2 pcs) |
AP20625 |
Cavity Insert Instructions
The following instructions are intended for qualified service personnel ONLY, and should only be done when necessary.
A diagram shows the cavity insert with the ECO Reset Button labeled.
In order to replace the ECO or thermistor, remove the cavity insert crossbar by following the instructions below:
- Disconnect all power to unit before to starting maintenance.
- Remove the jacket access panel(s) and insulation.
- Replace the ECO,thermistor and/or element as necessary.
- Replace the insulation, jacket access panel(s) and plastic housing before turning on the power to the water heater.
NOTICE: The cavity insert crossbar is necessary for the manufacturing process only. The removal of the crossbar will not interfere with the operation of the water heater.
Wiring Diagram
A comprehensive wiring diagram is provided, showing component codes, wiring information, and wire color codes.
If You Need Service
1. Should you have any questions about your new water heater, or if it requires adjustment, repair, or routine maintenance, it is suggested that you first contact your installer, plumbing contractor or previously agreed upon service agency. In the event the firm has moved, or is unavailable, refer to the telephone directory, commercial listings or local utility for qualified service assistance.
2. Should your problem not be solved to your complete satisfaction, you should then contact the Manufacturer's National Service Department at the following address:
800 Interstate Park Drive
Montgomery, Alabama 36109
Phone: 1-800-432-8373.
When contacting the manufacturer, the following information will be requested:
- Model and serial number of the water heater as shown on the rating label located on front of the water heater.
- Address where the water heater is located and physical location.
- Name and address of installer and any service agency who performed service on the water heater.
- Date of original installation and dates any service work was performed.
- Details of the problems as you can best describe them.
- List of people, with dates, who have been contacted regarding your problem.
3. Should you have any issue or need assistance with the WiFi Module/EcoNet App then contact the EcoNet Customer Service:
Phone: 1-800-255-2388
Website: www.Rheem.com/EcoNet